9
<After replacing the battery during operation...>
Press the beep stop/test button for 10 sec. to perform a self-diagnostic test. Normal operation
resumes after the 10-second test. If the beep sounds, it will stop the first time the switch is
pressed. Press the switch again to start the test.
If the battery replacement indicator and beep were activated before replacing the battery, the
indicator and beep stop after the test is complete, and normal operation resumes.
<After replacing the battery with operation stopped...>
Connect the AC input plug to a wall outlet (commercial power), and turn ON the power switch
of the UPS. When operation starts, the self-diagnostic test is automatically performed. Normal
operation resumes after the 10-second test.
Also, if using the UPS monitoring software included with the UPS, keep a record of the
software usage start date.
This unit uses a lead acid battery.
ALead acid batteries are a valuable recyclable resource. Please recycle.
For information about recycling, please contact our Electronic Systems & Equipments
repair center.
♦
Notes
♦
4. Replacing the battery unit
The UPS (BH60PCW/BH100PCW) battery unit (BHM60PC/BHM100PC) can be replaced without stopping
output when used in the ways described below.
●
Replacement without stopping output can be performed in the following case, only when the bypass
function is available.
When replacement is being performed, the unit switches to bypass output.
(1) Input/output synchronization operation
(Normal usage, where output frequency is synchronized with input frequency before output)
Battery connection
Available
SW8 Cold start
OFF
Setting switch selection SW9 Synchronized/ Non-synchronized selection OFF
SW10 50/Hz selection
OFF/ON
Bypass switch
ON