Names of Parts

Installation and Wiring

„

Dimensions

„

Standard Connection Diagram

* Connect a single-phase 200 VAC input to terminals L1 and N.
* Factory default settings for relay output are NC contact for AL1 and NO contact for AL2.

„

Terminal symbols, Screw size and Tightening Torque

* For  AB

@ @ @

, L1, /, N are indicated instead R/L1, S/L2, T/L3 respectively.

Keys

Parameter List

3G3JX-

W

W1

H

H1

D

A2002-E, AB002-EF

80

67

155

143

95.5

A2004-E, AB004-EF

109.5

A2007-E

132.5

A4004-EF, AB007-EF

110

98

189

176

130.5

AB015-EF, AB022-EF
A2015-E, A2022-E, A2037-E, A4007-EF, 
A4015-EF, A4022-EF, A4040-EF, 

157.5

A2055-E, A2075-E, 
A4055-EF, A4075-EF

180

164

250

235

167.5

[mm]

TYPE 3G3JX-A

@

Model X200 Series Inverter

Thank you for purchasing JX inverter.
To ensure safe operation, please be sure to read the safety precautions provided in 
this document along with all of the user manuals for the inverter. Please be sure you 
are using the most recent versions of the user manuals. Keep this instruction manual 
and all of the manuals in a safe location and be sure that they are readily available to 
the final user of the products.

Name

Cat. No.

JX Series User’s Manual

I558-E2-03-X

OMRON Corporation

INSTRUCTION MANUAL

NT305XD-EN

Main circuit

terminal block

(input side)

Communications

connector

Relay output

 terminal block

Main circuit

terminal block

(output side)

Digital Operator

For factory 

maintenance only

Do not touch

Emergency shut 

off function 

selector (S8)

OPE/485

communications

selector (S7)

Control circuit

terminal block

W

W1

H1 

1.9 

Type

Terminal symbol

A2002 to A2007

AB002 to AB004

A2015 to A2037
A4004 to A4037

AB007 to AB022

A2055 to A2075
A4055 to A4075

Main 
circuit

R/L1,S/L2,T/L3
U/T1, V/T2, W/T3 
Ground
(symbol)

M3.5

0.8 N·m

(max. 0.9 N·m)

M4

1.2 N·m

(max. 1.3 N·m)

M5

3.0 N·m

(max. 3.3 N·m)

Option

-,+,+1

Control 
circuit

AM,H,O,OI,L
5, 4, 3, 2,1,L, 
PCS,P24, CM2,11

M2 / 0.2 N·m (max. 0.25 N·m)

Relay

AL0,AL1,AL2

M2.5 / 0.5 N·m (max. 0.6 N·m)

Ground —

M4

M5

Name

Description

  Mode key

Switches between the command setting and the data 
settings, and between the basic function mode and the 
expended function mode.

„

Status transition

* Hold down the Mode key for 3 seconds to jump to 

'd001'.

  Increment key

Changes the set values, parameters and
Commands.

  Decrement key

  RUN key

Starts the operation. Forward/Reverse rotation 
depends on the 'F004' setting.

  STOP/RESET 

key

Stops the operation. Functions as the Reset key if an 
error occurs.

  Enter key

Enters and stores the data.

R/L1 

T/L3 

S/L2 

U/T1 

W/T3 

V/T2 



 





 

PCS 

+1 

 - 

AL1

AL0 

AL2 

 


OI 

P24 

11 

CM2 

AM 

(L1) 
(/) 
(N) 

Regenerative Braking unit

Relay output

Common

Common

Multi-function 

output

Analog monitor 

output

Frequency 

reference 

(voltage)

Frequency 

reference 

1k ~ 2 k

Ω

Frequency reference 

(current)

Power supply

Common

Frequency reference

Common

Multi-function input

3-phase 200 VAC

Single-phase 200 VAC

3-phase 400 VAC

DC reactor

Parameter

No.

Function name

Monitor or data range

d001

Output frequency moni-
tor

0.0 to 400.0

d002

Output current monitor

0.0 to 999.9

d003

Rotation direction moni-
tor

F:forward/o:stop/r:reverse

d004

PID feedback value 
monitor

0.00 to 9999
(Valid when the PID function is selected.)

d007

Output frequency moni-
tor (after conversion)

0.00 to 9999
1000 to 3996 (at 10000 to 39960)
(Output frequency × conversion factor of b086)

d013

Output voltage monitor

0 to 600

d016

Total RUN time

0 to 9999

d017

Power ON time monitor

0 to 9999

d018

Fin temperature monitor 0.0 to 200.0

d080

Fault frequency monitor 0 to 9999

d081

Fault monitor 1 (latest)

Error code (condition of occurrence)

 

Output frequency

 Output current

 

Internal DC voltage

 RUN time

 ON time

d082

Fault monitor 2

d083

Fault monitor 3

d102

DC voltage monitor

0.0 to 999.9

d104

Electric thermal monitor 0.0 to 100.0

F001

Output frequency set-
ting / monitor

Starting frequency to max. frequency

F002/F202

Acceleration time1/2nd 
acceleration time1

0.01 to 3000

F003/F203

Deceleration time1/2nd 
deceleration time1

0.01 to 3000

F004

Operator rotation direc-
tion selection

00:forward/01:reverse

A001/A201

Frequency reference 
selection/2nd frequency 
reference selection

00:Digital Operator (volume)/01:Terminal/
02:Digital Operator (F001)/
03:Modbus communication/
10:Frequency operation result

A002/A202

RUN command selec-
tion/2nd RUN command 
selection

01:Terminal/02:Digital Operator/
03:Modbus communication

A003/A203

Base frequency/ 
2nd base frequency

30 to max. frequency [A004/A204]

A004/A204

Maximum frequency/ 
2nd maximum frequency

30 to 400

A005

O/OI selection

02: Switch between O/Volume via terminal AT
03: Switch between OI/Volume via terminal AT
04: O input only/05:OI input only

A020/A220

Multi-step speed 
reference0/2nd
multi-step speed 
reference0

0.0/Starting frequency to max. frequency

A021 to 
A035

Multi-step speed 
reference1~15

0.0/Starting frequency to max. frequency

A038

Jogging frequency

0.00/Strating frequency to 9.99

A039

Jogging stop selection

00:Free run on jogging stop
01:Deceleration stop on jogging stop
02:DC injection braking on jogging stop

A045/A245

Output voltage gain/ 2nd 
output voltage gain

20 to 100

A097

Acceleration pattern 
selection

00:Line/01:S-shape curve

A098

Deceleration pattern 
selection

b001

Retry selection

00: Alarm/01:0 Hz start
02: Frequency matching start
03: Trip after frequency matching deceleration 

stop

b002

Allowable momentary 
power interruption time

0.3 to 25.0

b083

Carrier frequency

2.0 to 12.0

b084

Initialization selection

00:Clear the trip monitor
01:Initialize data
02:Clear and initialize

b130

Overvoltage LAD stop 
function

00:Disable/01:Enable

b131

Overvoltage LAD stop 
function level

200V class:330 to 395
400V class:660 to 790

C001/C201

Multi-function input1 
selection/2nd 
multi-function input1 
selection

00:FW(forward)/01:RV(reverse)/
02:CF1(multi-step speed setting binary1)/
03:CF2(multi-step speed setting binary2)/
04:CF3(multi-step speed setting binary3)/
05:CF4(multi-step speed setting binary4)/
06:JG(jogging)/07:DB(external DC injection/
braking)/08:SET(2nd control)/09:2CH(2-step 
acceleration/deceleration)/11:FRS(free run 
stop)/12:EXT(external trip)/13:USP(USP func-
tion)/15:SFT(soft lock)/16:AT(analog input 
switch)/18:RS(reset)/19:PTC(thermistor input)/
20:STA(3-wire start)/21:STP(3-wire stop)/22:F/
R(3-wire forward/reverse)/23:PID(PID enable/
disable)/24:PIDC(PID integral/reset)/
27:UP(UP/DWN function accelerated)/
28:DWN(UP/DWN function decelerated)/
29:UDC(UP/DWN function data clear)/
31:OPE(forward operator)/50:ADD(frequency 
addition)/51:F-TM(forced terminal block)/
52:RDY(ready function)/53:SP-SET(special 
2nd function)/64:EMR(emergency shut off)/
255:No function

C002/C202

Multi-function input2
selection/2nd
multi-function input2
selection

C003/C203

Multi-function input3
selection/2nd
multi-function input3
selection

C004/C204

Multi-function input4
selection/2nd
multi-function input4
selection

C005/C205

Multi-function input5
selection/2nd
multi-function input5
selection

C011 to
C015

Multi-function input 1-5 
operation selection

00:NO
01:NC

C021

Multi-function output
terminal 11 selection

00:RUN(during RUN)/01:FA1(constant speed 
reached)/02:FA2(set frequency min. reached)/
03:OL(overload warning)/04:OD(PID exces-
sive deviation)/05:AL(alarm output)/06:Dc(dis-
connection defected)/07:FBV(PID FB value 
output)/08:NDc(Network error)/09:LOG(logic 
operation output)/10:ODc(communication 
option, disconnected)/43:LOC(light load defec-
tion)

C026

Relay output (AL1,AL2)
function selection

C028

AM selection

00:Output frequency/01:Output current

C031

Multi-function output
Terminal 11 contact
selection

00:NO contact at AL1, NC contact at AL2
01:NC contact at AL1, NO contact at AL2

C036

Relay output (AL1,AL2)
contact selection

H003/H203

Motor capacity 
selection/2nd motor 
capacity selection

200V class: 0.2 to 7.5
400V class: 0.4 to 7.5

H004/H204

Motor pole number 
selection/2nd motor pole 
number selection

2/4/6/8

Parameter

No.

Function name

Monitor or data range

OMRON Corporation
Industrial Automation Company

Control Devices Division H.Q.
Motion Control Division

Shiokoji Horikawa, Shimogyo-ku,
Kyoto, 600-8530 Japan
Tel: (81) 

75-344-7173

Fax: (81) 75-344-7149

2-2-1 Nishikusatsu, Kusatsu-shi,
Shiga, 525-0035 Japan
Tel: (81) 

77-565-5223

Fax: (81) 77-565-5568

Regional Headquarters

OMRON EUROPE B.V.

Wegalaan 67-69-2132 JD Hoofddorp
The Netherlands
Tel. (31)2356-81-300
Fax: (31)2356-81-388

SUITABILITY FOR USE

OMRON shall not be responsible for conformity with any standards, code, 
or regulations that apply to the combination of products in the customer’s 
application or use of the products.

Take all necessary steps to determine the suitability of the product for the systems, machines, and 
equipment with which it will be used.
Please know and observe all prohibitions of use apllicable to the products.
NEVER USE THE PRODUCTS FOR AN APPLICATION INVOLVING SERIOUS RISK TO LIFE OR 
PROPERTY WITHOUT ENSURING THAT THE SYSTEM AS A WHOLE HAS BEEN DESIGNED TO 
ADDRESS THE RISKS, AND THAT THE OMRON PRODUCTS ARE PROPERLY RATED AND IN-
STALLED FOR THE INTENDED USE WITHIN THE OVERALL EQUIPMENT OR SYSTEM.
See also product catalogs for Warranty and Limitations of Liability.

Note:

In the interest of product improvement, specifications are subject to change without notice

.

Printed in Japan

Sales and Service: OMRON EUROPE B.V

Manufacturer: Hitachi Industrial Equipment Systems Co.,Ltd.