Safety Precautions

„

Indications and Meanings of Safety Information

In this user's manual, the following precautions and signal words are used to provide infor-
mation to ensure the safe use of the JX Inverter. The information provided here is vital to 
safety. Strictly observe theprecautions provided.

„

Meanings of Signal Words

„

Alert Symbols in this Document

Precautions for Safe Use

„

Installation and Storage

Do not store or use the product in the following places.

• Locations subject to direct sunlight.
• Locations subject to ambient temperature exceeding the

specifications.

• Locations subject to relative humidity exceeding the specifications.
• Locations subject to condensation due to severe temperature

fluctuations.

• Locations subject to corrosive or flammable gases.
• Locations subject to exposure to combustibles.
• Locations subject to dust (especially iron dust) or salts.
• Locations subject to exposure to water, oil, or chemicals.
• Locations subject to shock or vibration.

„

Transporting, Installation, and Wiring

• Do not drop or apply strong impact on the product. Doing so may result in damaged 

parts or malfunction.

• Do not hold by the front cover, but hold by the fins during transportation.
• Do not connect an AC power supply voltage to the control input/output terminals. Doing 

so may result in damage to the product.

• Be sure to tighten the screws on the terminal block securely. Wiring work must be done 

after installing the unit body.

• Do not connect any load other than a three-phase inductive motor to the U, V, and W 

output terminals.

• Take sufficient shielding measures when using the product in the following locations. 

Not doing so may result in damage to the product.

• Locations subject to static electricity or other forms of noise.
• Locations subject to strong magnetic fields.
• Locations close to power lines.

„

Operation and Adjustment

• Be sure to confirm the permissible range of motors and machines before operation be-

cause the inverter speed can be changed easily from low to high.

• Provide a separate holding brake if necessary.

„

Maintenance and Inspection

• Be sure to confirm safety before conducting maintenance, inspection or parts replace-

ment.

Precautions for Correct Use

„

Installation

• Mount the product vertically on a wall or on a DIN Rail (optional) with  the product's long-

er sides upright.
The material of the wall has to be noninflammable such as a metal plate.

„

Main Circuit Power Supply

• Confirm that the rated input voltage of the Inverter is the same as AC power supply volt-

age.

„

Error Retry Function

• Do not come close to the machine when using the error retry function because the ma-

chine may abruptly start when stopped by an alarm.

• Be sure to confirm the RUN signal is turned off before resetting the alarm because the 

machine may abruptly start.

„

Non-Stop Function at Momentary Power Interruption

• Do not come close to the machine when selecting reset in the non-stop function at mo-

mentary power interruption selection (b050) because the machine may abruptly start af-
ter the power is turned on.

„

Operation Stop Command

• Provide a separate emergency stop switch because the STOP Key on the Operator is 

valid only when function settings are performed.

• When checking a signal during the power supply and the voltage is erroneously applied 

to the control input terminals, the motor may start abruptly. Be sure to confirm safety be-
fore checking a signal.

„

Product Disposal

• Comply with the local ordinance and regulations when disposing of the product.

UL Cautions

The warnings and instructions in this section summarizes the procedures necessary to en-
sure an inverter installation complies with Underwriters Laboratories guidelines.

• Use 60/75°C Cu wire only or equivalent.

(For models:X200-015L(A2015), -022L(A2022), -037L(A2037), -055L(A2055),

-075L(A2075), -007S(AB007), -015S(AB015), -022S(AB022))

• Use 75°C Cu wire only or equivalent.

(For models:X200-002L(A2002), -004L(A2004), -007L(A2007), -022H(A4022),

-040H(A4040), -055H(A4055), -075H(A4075), -002S(AB002), 
-004S(AB004))

• Use 60°C Cu wire only or equivalent.

(For models:X200-004H(A4004), -007H(A4007), -015H(A4015))

• Open Type Equipment.
• Suitable for use on a circuit capable of delivering not more than 100k rms symmetrical 

amperes, 240 V maximum when protected by Class CC, G, J or R fuses or circuit break-
er having an interrupting rating not les than 100,000 rms symmetrical amperes, 
240 volts maximum.
(For models:200 V class)

• Suitable for use on a circuit capable of delivering not more than 100k rms symmetrical 

amperes, 480 V maximum when protected by Class CC, G, J or R fuses or circuit break-
er having an interrupting rating not les than 100,000 rms symmetrical amperes, 
480 volts maximum.
(For models:400 V class)

• Install device inn pollution degree 2 environment.
• Maximum Surrounding Air Temperature 50°C or equivalent.
• Caution-Risk of electric shock, -capacitor discharge time is at least 5 minutes.
• Solid state motor overload protection is provided in each model.
• Integral solid state short circuit protection does not provide branch circuit protection. 

Branch circuit protection must be provided in accordance with the National Electric 
Code and any additional local codes or equivalent.

„

Terminal Tightening Torque and Wire Size

The wire size range and tightening torque for field wiring terminals are presented in the ta-
bles below.

„

Wire Connectors

Field wiring connections must be made by a UL Listed and CSA certified ring lug terminal 
connector sized for the wire gauge being used. The connector must be fixed using the 
crimping tool specified by the connector manufacturer.

„

Circuit breaker and Fuse Size

The Inverter's connections to input power must include UL Listed inverse time circuit break-
ers with 600 V rating, or UL Listed fuses as shown in the table below.

„

Motor Overload Protection

JX Inverters provide solid state motor overload protection, which depends on the proper 
setting of the following parameters:

•  b012: electronic overload protection
•  b212: electronic overload protection, 2nd motor

Set the rated current [Amperes] of the motor(s) with the above parameters. The setting 
range is 0.2 rated current to 1.0 rated current.
When two or more motors are connected to the Inverter, they cannot be protected by the 
electronic overload protection. Install an external thermal relay on each motor.

Conformance to EC Directives

• For earthing, selection of cable, and any other conditions for EMC-compliance, please 

refer to the manual for installation.

• This is a class A product in residential areas it may cause radio interference, in which 

case the user may be required to take adequate measures to reduce interference.

„

JX series Inverter has integrated EMC filter as shown below

• 200 V class: EN61800-3 category C1
• 400 V class: EN61800-3 category C2

DANGER

Indicates an imminently hazardous situation which, 
if not avoided, is likely to result in serious injury or 
may result in death. Additionally there may be 
severe property damage.

CAUTION

Indicates a potentially hazardous situation which, if 
not avoided, may result in minor or moderate injury 
or in property damage.

DANGER

Turn off the power supply and implement wiring correctly. Not doing so may 
result in a serious injury due to an electric shock.

Wiring work must be carried out only by qualified personnel. Not doing so 
many result in a serious injury due to an electric shock.

Be sure to ground the unit. Not doing so may result in a serious injury due to 
an electric shock or fire.
(200 V class: type-D grounding, 400 V class: type-C grounding)
Do not remove the front cover during the power supply and 5 minutes after 
the power shut off. Doing so may result in a serious injury due to an electric 
shock.
Do not operate the Operator or switches with wet hands. Doing so may result 
in a serious injury due to an electric shock.

Inspection of the Inverter must be conducted after the power supply has 
been turned off. Not doing so may result in a serious injury due to an electric 
shock.
The main power supply is not necessarily shut off even if the emergency shut 
off function is activated.
Do not change wiring, mode change switches (S7, S8), optional devices or 
replace cooling fans while power is being supplied.
Doing so may result in a serious injury due to an electric shock.

CAUTION

Do not connect resistors to the terminals (+1, +, –) directly.
Doing so might result in a small-scale fire, heat generation or damage to the 
unit.
Install a stop motion device to ensure safety. Not doing so might result in a 
minor injury. (A holding brake is not a stop motion device designed to ensure 
safety.)
Be sure to use a specified type of braking resistor/regenerative braking unit. 
In case of a braking resistor, install a thermal relay that monitors the temper-
ature of the resistor. Not doing so might result in a moderate burn due to the 
heat generated in the braking resistor/regenerative braking unit. Configure a 
sequence that enables the Inverter power to turn off when unusual overheat-
ing is detected in the braking resistor/regenerative braking unit.
The Inverter has high voltage parts inside which, if short-circuited, might 
cause damage to itself or other property. Place covers on the openings or 
take other precautions to make sure that no metal objects such as cutting bits 
or lead wire scraps go inside when installing and wiring.
Do not touch the Inverter fins, braking resistors and the motor, which become 
too hot during the power supply and for some time after the power shut off. 
Doing so may result in a burn.
Take safety precautions such as setting up a molded-case circuit 
breaker(MCCB) that matches the Inverter capacity on the power supply side. 
Not doing so might result in damage to property due to the short circuit of the 
load.
Do not dismantle, repair or modify this product. 
Doing so may result in an injury.

Input 

Voltage

Motor Output

Inverter Model 

X200- (3G3JX-)

Power Terminal 

Wiring Size 

Range (AWG)

Torque

kW

HP

Ft-lbs

(N·m)

200 V class 0.2

1/4

002LFRF/SFEF
(A2002/AB002)

14
(75°C only)

0.6

0.8

0.4

1/2

004LFRF/SFEF
(A2004/AB004)

0.75

1

007LFRF/SFEF
(A2007/AB007)

0.9

1.2

1.5

2

015LFRF/SFEF
(A2015/AB015)

12

2.2

3

022LFRF/SFEF
(A2022/AB022)

10

3.7

5

037LFRF
(A2037)

5.5

7 1/2

055LFRF
(A2055)

8

2.3

3.0

7.5

10

075LFRF
(A2075)

400 V class 0.4

1/2

004HFEF
(A4004)

16
(60°C only)

0.9

1.2

0.75

1

007HFEF
(A4007)

1.5

2

015HFEF
(A4015)

2.2

3

022HFEF
(A4022)

14
(75°C only)

4

5

040HFEF
(A4040)

5.5

7 1/2

055HFEF
(A4055)

10

2.3

3.0

7.5

10

075HFEF
(A4075)

Terminal Conector Wiring Size Range (AWG)

Torque

Ft-lbs

(N·m)

Logic and Analog
connectors

30-16

0.16-0.19

0.22-0.25

Relay connector

30-14

0.37-0.44

0.5-0.6

Input 

Voltage

Inverter Model

X200- (3G3JX-)

Circuit Breaker/Fuse

Ratings (A)

200V class

002LFRF/SFEF
(A2002/AB002)

Inverse timecircuit Breaker 10

004LFRF/SFEF 
(A2004/AB004)
007LFRF/SFEF
(A2007/AB007)

15

015LFRF/SFEF 
(A2015/AB015)

20

022LFRF/SFEF
(A2022/AB022)

30

037LFRF
(A2037)
055LFRF
(A2055)

40

075LFRF
(A2075

50

400V class

004HFEF 
(A4004)

Distribution Fuse (Class J) 3

007HFEF 
(A4007)

6

015HFEF 
(A4015)

10

022HFEF 
(A4022)
040HFEF 
(A4040)

15

055HFEF
(A4055)

20

075HFEF
(A4075)

25

Cable support

Terminal (ring lug)

Cable

„