Names of Parts
Installation and Wiring
Dimensions
Standard Connection Diagram
* Connect a single-phase 200 VAC input to terminals L1 and N.
* Factory default settings for relay output are NC contact for AL1 and NO contact for AL2.
Terminal symbols, Screw size and Tightening Torque
* For AB
@ @ @
, L1, /, N are indicated instead R/L1, S/L2, T/L3 respectively.
Keys
Parameter List
3G3JX-
W
W1
H
H1
D
A2002-E, AB002-EF
80
67
155
143
95.5
A2004-E, AB004-EF
109.5
A2007-E
132.5
A4004-EF, AB007-EF
110
98
189
176
130.5
AB015-EF, AB022-EF
A2015-E, A2022-E, A2037-E, A4007-EF,
A4015-EF, A4022-EF, A4040-EF,
157.5
A2055-E, A2075-E,
A4055-EF, A4075-EF
180
164
250
235
167.5
[mm]
TYPE 3G3JX-A
@
Model X200 Series Inverter
Thank you for purchasing JX inverter.
To ensure safe operation, please be sure to read the safety precautions provided in
this document along with all of the user manuals for the inverter. Please be sure you
are using the most recent versions of the user manuals. Keep this instruction manual
and all of the manuals in a safe location and be sure that they are readily available to
the final user of the products.
Name
Cat. No.
JX Series User’s Manual
I558-E2-03-X
OMRON Corporation
INSTRUCTION MANUAL
NT305XD-EN
Main circuit
terminal block
(input side)
Communications
connector
Relay output
terminal block
Main circuit
terminal block
(output side)
Digital Operator
For factory
maintenance only
Do not touch
Emergency shut
off function
selector (S8)
OPE/485
communications
selector (S7)
Control circuit
terminal block
W
W1
H1
H
D
1.9
Type
Terminal symbol
A2002 to A2007
AB002 to AB004
A2015 to A2037
A4004 to A4037
AB007 to AB022
A2055 to A2075
A4055 to A4075
Main
circuit
R/L1,S/L2,T/L3
U/T1, V/T2, W/T3
Ground
(symbol)
M3.5
0.8 N·m
(max. 0.9 N·m)
M4
1.2 N·m
(max. 1.3 N·m)
M5
3.0 N·m
(max. 3.3 N·m)
Option
-,+,+1
Control
circuit
AM,H,O,OI,L
5, 4, 3, 2,1,L,
PCS,P24, CM2,11
M2 / 0.2 N·m (max. 0.25 N·m)
Relay
AL0,AL1,AL2
M2.5 / 0.5 N·m (max. 0.6 N·m)
Ground —
M4
M5
Name
Description
Mode key
Switches between the command setting and the data
settings, and between the basic function mode and the
expended function mode.
Status transition
* Hold down the Mode key for 3 seconds to jump to
'd001'.
Increment key
Changes the set values, parameters and
Commands.
Decrement key
RUN key
Starts the operation. Forward/Reverse rotation
depends on the 'F004' setting.
STOP/RESET
key
Stops the operation. Functions as the Reset key if an
error occurs.
Enter key
Enters and stores the data.
R/L1
T/L3
S/L2
U/T1
W/T3
V/T2
2
1
3
4
5
1
2
3
4
5
PCS
L
+1
+
-
AL1
AL0
AL2
H
O
L
OI
M
P24
11
CM2
AM
(L1)
(/)
(N)
Regenerative Braking unit
Relay output
Common
Common
Multi-function
output
Analog monitor
output
Frequency
reference
(voltage)
Frequency
reference
1k ~ 2 k
Ω
Frequency reference
(current)
Power supply
Common
Frequency reference
Common
Multi-function input
3-phase 200 VAC
Single-phase 200 VAC
3-phase 400 VAC
DC reactor
Parameter
No.
Function name
Monitor or data range
d001
Output frequency moni-
tor
0.0 to 400.0
d002
Output current monitor
0.0 to 999.9
d003
Rotation direction moni-
tor
F:forward/o:stop/r:reverse
d004
PID feedback value
monitor
0.00 to 9999
(Valid when the PID function is selected.)
d007
Output frequency moni-
tor (after conversion)
0.00 to 9999
1000 to 3996 (at 10000 to 39960)
(Output frequency × conversion factor of b086)
d013
Output voltage monitor
0 to 600
d016
Total RUN time
0 to 9999
d017
Power ON time monitor
0 to 9999
d018
Fin temperature monitor 0.0 to 200.0
d080
Fault frequency monitor 0 to 9999
d081
Fault monitor 1 (latest)
Error code (condition of occurrence)
→
Output frequency
→
Output current
→
Internal DC voltage
→
RUN time
→
ON time
d082
Fault monitor 2
d083
Fault monitor 3
d102
DC voltage monitor
0.0 to 999.9
d104
Electric thermal monitor 0.0 to 100.0
F001
Output frequency set-
ting / monitor
Starting frequency to max. frequency
F002/F202
Acceleration time1/2nd
acceleration time1
0.01 to 3000
F003/F203
Deceleration time1/2nd
deceleration time1
0.01 to 3000
F004
Operator rotation direc-
tion selection
00:forward/01:reverse
A001/A201
Frequency reference
selection/2nd frequency
reference selection
00:Digital Operator (volume)/01:Terminal/
02:Digital Operator (F001)/
03:Modbus communication/
10:Frequency operation result
A002/A202
RUN command selec-
tion/2nd RUN command
selection
01:Terminal/02:Digital Operator/
03:Modbus communication
A003/A203
Base frequency/
2nd base frequency
30 to max. frequency [A004/A204]
A004/A204
Maximum frequency/
2nd maximum frequency
30 to 400
A005
O/OI selection
02: Switch between O/Volume via terminal AT
03: Switch between OI/Volume via terminal AT
04: O input only/05:OI input only
A020/A220
Multi-step speed
reference0/2nd
multi-step speed
reference0
0.0/Starting frequency to max. frequency
A021 to
A035
Multi-step speed
reference1~15
0.0/Starting frequency to max. frequency
A038
Jogging frequency
0.00/Strating frequency to 9.99
A039
Jogging stop selection
00:Free run on jogging stop
01:Deceleration stop on jogging stop
02:DC injection braking on jogging stop
A045/A245
Output voltage gain/ 2nd
output voltage gain
20 to 100
A097
Acceleration pattern
selection
00:Line/01:S-shape curve
A098
Deceleration pattern
selection
b001
Retry selection
00: Alarm/01:0 Hz start
02: Frequency matching start
03: Trip after frequency matching deceleration
stop
b002
Allowable momentary
power interruption time
0.3 to 25.0
b083
Carrier frequency
2.0 to 12.0
b084
Initialization selection
00:Clear the trip monitor
01:Initialize data
02:Clear and initialize
b130
Overvoltage LAD stop
function
00:Disable/01:Enable
b131
Overvoltage LAD stop
function level
200V class:330 to 395
400V class:660 to 790
C001/C201
Multi-function input1
selection/2nd
multi-function input1
selection
00:FW(forward)/01:RV(reverse)/
02:CF1(multi-step speed setting binary1)/
03:CF2(multi-step speed setting binary2)/
04:CF3(multi-step speed setting binary3)/
05:CF4(multi-step speed setting binary4)/
06:JG(jogging)/07:DB(external DC injection/
braking)/08:SET(2nd control)/09:2CH(2-step
acceleration/deceleration)/11:FRS(free run
stop)/12:EXT(external trip)/13:USP(USP func-
tion)/15:SFT(soft lock)/16:AT(analog input
switch)/18:RS(reset)/19:PTC(thermistor input)/
20:STA(3-wire start)/21:STP(3-wire stop)/22:F/
R(3-wire forward/reverse)/23:PID(PID enable/
disable)/24:PIDC(PID integral/reset)/
27:UP(UP/DWN function accelerated)/
28:DWN(UP/DWN function decelerated)/
29:UDC(UP/DWN function data clear)/
31:OPE(forward operator)/50:ADD(frequency
addition)/51:F-TM(forced terminal block)/
52:RDY(ready function)/53:SP-SET(special
2nd function)/64:EMR(emergency shut off)/
255:No function
C002/C202
Multi-function input2
selection/2nd
multi-function input2
selection
C003/C203
Multi-function input3
selection/2nd
multi-function input3
selection
C004/C204
Multi-function input4
selection/2nd
multi-function input4
selection
C005/C205
Multi-function input5
selection/2nd
multi-function input5
selection
C011 to
C015
Multi-function input 1-5
operation selection
00:NO
01:NC
C021
Multi-function output
terminal 11 selection
00:RUN(during RUN)/01:FA1(constant speed
reached)/02:FA2(set frequency min. reached)/
03:OL(overload warning)/04:OD(PID exces-
sive deviation)/05:AL(alarm output)/06:Dc(dis-
connection defected)/07:FBV(PID FB value
output)/08:NDc(Network error)/09:LOG(logic
operation output)/10:ODc(communication
option, disconnected)/43:LOC(light load defec-
tion)
C026
Relay output (AL1,AL2)
function selection
C028
AM selection
00:Output frequency/01:Output current
C031
Multi-function output
Terminal 11 contact
selection
00:NO contact at AL1, NC contact at AL2
01:NC contact at AL1, NO contact at AL2
C036
Relay output (AL1,AL2)
contact selection
H003/H203
Motor capacity
selection/2nd motor
capacity selection
200V class: 0.2 to 7.5
400V class: 0.4 to 7.5
H004/H204
Motor pole number
selection/2nd motor pole
number selection
2/4/6/8
Parameter
No.
Function name
Monitor or data range
OMRON Corporation
Industrial Automation Company
Control Devices Division H.Q.
Motion Control Division
Shiokoji Horikawa, Shimogyo-ku,
Kyoto, 600-8530 Japan
Tel: (81)
75-344-7173
Fax: (81) 75-344-7149
2-2-1 Nishikusatsu, Kusatsu-shi,
Shiga, 525-0035 Japan
Tel: (81)
77-565-5223
Fax: (81) 77-565-5568
Regional Headquarters
OMRON EUROPE B.V.
Wegalaan 67-69-2132 JD Hoofddorp
The Netherlands
Tel. (31)2356-81-300
Fax: (31)2356-81-388
SUITABILITY FOR USE
OMRON shall not be responsible for conformity with any standards, code,
or regulations that apply to the combination of products in the customer’s
application or use of the products.
Take all necessary steps to determine the suitability of the product for the systems, machines, and
equipment with which it will be used.
Please know and observe all prohibitions of use apllicable to the products.
NEVER USE THE PRODUCTS FOR AN APPLICATION INVOLVING SERIOUS RISK TO LIFE OR
PROPERTY WITHOUT ENSURING THAT THE SYSTEM AS A WHOLE HAS BEEN DESIGNED TO
ADDRESS THE RISKS, AND THAT THE OMRON PRODUCTS ARE PROPERLY RATED AND IN-
STALLED FOR THE INTENDED USE WITHIN THE OVERALL EQUIPMENT OR SYSTEM.
See also product catalogs for Warranty and Limitations of Liability.
Note:
In the interest of product improvement, specifications are subject to change without notice
.