![Omntec FuelCheck Installation & Operating Manual Download Page 31](http://html1.mh-extra.com/html/omntec/fuelcheck/fuelcheck_installation-and-operating-manual_740733031.webp)
30
FuelCheck
®
System Specifications
FuelCheck
®
Probe
Part No.
FU-PR-24
Sensor type:
dual reflection critical angle fiberoptic refractometer
Fiber
type:
duplex
200/230
µm
HCP
Fiberoptic connector type:
ST crimp and cleave
Maximum fiber length:
2 km (~7,500 ft)
Probe construction:
½” OD X 0.095” WT TV9426 304 stainless tubing
Standard connection:
1” MNPT to access valve
Max. operating pressure:
1,500 PSI (10.3 MPa)
Max. probe insertion/removal pressure:
1,500 PSI (10.3 MPa) with optional high-pressure in-
sertion tool, 300 PSI (2.1 MPa) with standard insertion
handle
FuelCheck
®
Controller
Part No.
FU-CT-*I (* represents number of channels up to 3, ie. FU-CT-1I)
Enclosure size:
2 - tandem mounted 8”W X 10”H X 6.63” Total width 19.5”
Enclosure type
fiberglass NEMA-4X
Conduit connections:
2 - ½” female connectors on 3.75” centers (bottom of enclosure)
Power requirement:
24 VDC standard, AC optional
Operating temperature:
50°F - 130°F (do not mount in direct sunlight, requires sunshade)
Signal output:
4 - 20 ma with user-adjustable zero, span, and polarity
normal polarity proportional to refractive index and specific gravity
reverse polarity proportional to °API.