CIBANO 500 Getting Started
4
OMICRON
1.3
Safe operation
When operating the
CIBANO 500
test system and its accessories, observe the following safety
instructions.
1.3.1
Test equipment integrity
►
Do not modify, extend, or adapt
CIBANO 500
and its accessories.
►
Use only the
CIBANO 500
original accessories and cables and only use the OMICRON accessories
together with OMICRON devices as described in this manual.
►
Operate
CIBANO 500
and its accessories only under ambient conditions specified in "Technical data"
in the CIBANO 500 User Manual.
1.3.2
CIBANO 500
►
Use only adequately rated power cords.
►
Supply
CIBANO 500
only from a power outlet with protective earth (PE).
►
To run
CIBANO 500
at the maximum power level, we recommend mains overcurrent protection with
a 16 A automatic circuit breaker.
►
Position the measurement setup so that you can easily disconnect
CIBANO 500
from mains.
►
Do not use extension cables on a cable reel to prevent overheating of the cord. Instead, run out the
extension cord.
►
Do not operate
CIBANO 500
without a solid connection to ground of at least 6 mm
2
cross-section.
Ground
CIBANO 500
as close as possible to the operator.
►
The warning symbol on the side panel of
CIBANO 500
(see 3.2.2 "Side panel" on page 11) indicates
dangerous voltage on one of the
CIBANO 500
sockets, either from an internal source or from an
external one, for example, from the station battery.
►
After booting
CIBANO 500
either the red or the green warning light on the front panel should be on.
If after booting both warning lights are on or off,
CIBANO 500
might be defective. In this case, do not
use
CIBANO 500
and contact your regional OMICRON service center.
►
Do not operate
CIBANO 500
and its accessories in the presence of explosives, dangerous gases or
vapors.
►
If
CIBANO 500
or its accessories do not seem to function properly, stop using them and contact your
regional OMICRON service center.