Attach the clamping block (3) to the base plate of
OTMC 100
as shown in the figure.
Use a tightening torque of 5 Nm for the fastening
screws.
Exclusively use the two M6 x 16 screws delivered
with the mast mounting kit! Do not use longer screws!
The threaded holes in the base plate are only 9 mm
deep.
3
Insert the connecting pipe (4) to the clamping blocks
on the mast clamp and
OTMC 100
as shown in the
figure.
5
4
Align
OTMC 100
in an upright position as shown in
the figure and tighten both clamping screws (5) of the
clamping blocks evenly with a tightening torque of
5 Nm.
Assemble the delivered waterproof RJ45 connector
to the Ethernet cable according to the accompanying
assembly instructions and insert it to the RJ45
connector on the base plate of
OTMC 100
. Use
suitable cable ties to fasten the Ethernet network
cable to the connecting pipe and the mast.
Always use the waterproof RJ45 Ethernet
connector supplied with
OTMC 100
in order
to maintain the watertightness of the
device. Do not use
OTMC 100
outdoors
without a waterproof connector inserted.
The clamping blocks provide holes for
horizontal and vertical mounting of the
connecting pipe. Therefore, it is also
possible to mount
OTMC 100
on the top of
a vertically mounted connecting pipe.
Mounting
OMICRON
11