background image

OMEGA-VSHPe.F-IOM-2205

 

 

19 

 

 

 

 

Troubleshooting Guide

 

Problem

Mode

Time To 

Trip

Possible Cause(s)

Likelyhood to 

occur

Correction Method

Heating/Cooling

Main power off 

Med

Check unit circuit breaker.

Heating/Cooling

Blown transformer / Blown 

Low Voltage Fuse

High

3 Amp fuse pops usually when there is a short to ground.  Check thermostat wiring, control wiring, 
and verfiy wiring in chassis has no short to ground.

Heating/Cooling

Blown transformer / Blown 

Low Voltage Fuse

High

Short to ground inside chassis. Open top cover of chassis cover, check for shorts, signs of arcing, 
loose connectors and worn shielding especially near refrigerant piping.

Heating/Cooling

Blown transformer / Blown 

Low Voltage Fuse

High

Confirm there is no short to ground before replacing transformer.  Built in 3A fuse is designed to 
protect transformer.  If no short to ground found, replace transformer.

Heating/Cooling

Broken or loose connection

High

Check for loose thermostat connections at the control board and at thermostat base. Repair and/or 
tighten as required.

Heating/Cooling

Damaged thermostat cable

Low

Check for damaged wires on the thermostat cable

Heating/Cooling

Defective thermostat

Med

Check and replace

Unit short cycles

Heating/Cooling

Thermostat improperly located

Low

Relocate thermostat away from supply registers.

Breaker Trip

Heating/Cooling

0min

Short to ground on high 

voltage side

Low

Isolate main components: disconnect chassis harnesses and fan harness from electrical box. Check 
by turning on breaker and then disconnect. If Breaker trips again, the short to ground inside the 
electrical box.  Using ohm meter check for short to ground inside electrical (check for loose wires, or 
damaged wire shielding). Otherwise short to ground is located inside the chassis or at the fan motor.

Heating/Cooling

0min

Tripped Circuit Breaker

Low

Disconnect chassis power harness only. Power up unit.  If breaker trips only when chassis is 
connected, check chassis power wiring for a potnential locked rotor.  Compare current reading 
(Amps) to nameplate.

Heating/Cooling

Burnt out compressor 

overload

High

Check and replace if required. Located on top of Rotary compressor. Remove plastic cap, check 
resistance (size 020-060 units only).

Heating/Cooling

Defective compressor 

contactor

Low

Check 24VAC coil on contactor is getting power. If powered but coil does not close line voltage 
contacts or stays open/close replace contractor. Replace every 5-7 years.

Heating/Cooling

Supply voltage too low

Low

Correct incoming supply voltage setting at Transformer. Check that the line voltage is matched to 
208V or 240V transformer taps

Heating/Cooling

Defective compressor 

capacitor

Med

Check capacitor and replace if required.  Should be replaced every 4-5 years.

Heating/Cooling

Defective compressor 

windings

Low

Check compressor windings for damage. Replace if required

Heating/Cooling

0 - 3min

Limit switches open

Check for faulty pressure switches. Switches are normally closed. Check for bad connections at wire 
terminals. Replace if switches are open when unit is shutdown and there are no wire connections 
issues.

Heating/Cooling

0min

Clogged Drain Pan / 

Condensate hose / Faulty 

Sensor

Condensate switch detects overflow condition in drain pan, check for obstruction. If no water is 
present and condensate switch is circuit is open, check switch, and replace if required.

Heating/Cooling

Dirty filter

High

Check and replace

Heating/Cooling

Blower RPM too low

Low

Set to blower to higher fan speed using unit mounted 3-speed fan switch.

Heating/Cooling

Loss of conditioned air due to 

ductwork leaks

Low

Check for duct leaks and repair

Heating/Cooling

Low on refrigerant charge

Med

Possible leak in system or low charge. Check for low suction pressure (<110PSI); coil freeze up. If 
confirmed check for leaks at piping joints and coil. Repair if possible, and recharge to unit nameplate 
charge rating.

Heating/Cooling

Defective reversing valve

Low

Check and replace

Heating/Cooling

Thermostat improperly located

Med

Relocate thermostat

Heating/Cooling

Inadequate water flow

Low

Increase GPM

Cooling

Entering Water Temperature 

too hot

Med

Adjust EWT Loop temperature lower

Heating/Cooling

Entering Water Temperature 

too cold

Low

Adjust EWT Loop temperature higher

Cooling

30sec - 2min

Inadequate GPM

High

If auto shut-off valve is installed, check that control valve actuator opens during call for Heating.  Set 
valve to manual mode and remove power connections from actuator and re-test. If manual mode re-
test confirms proper water flow, actuator is likely faulty.

Cooling

>2min

Water too hot

Med

Reduce water loop temperature

Heating

>2min

Inadequate air flow

Med

Check for clogged filter, check blower for obstruction and adequate airflow.

Heating

>5min

Dirty filter

Med

Clean/replace

Heating/Cooling

>5min

Overcharged with refrigerant

Low

TXV will hunt, Superheat will oscillate, read close to zero.  Decrease charge/Confirm charge matches 
nameplate.

Heating/Cooling

0min

Bad pressure switch

Low

Check continuity, should be closed circuit. If open circuit, check wiring inside chassis: tab, 
connectors.

No response to any 

thermostat setting

Insufficient capacity

High Pressure Fault

Only blower runs, 

but not compressor

Summary of Contents for VSHPe Series

Page 1: ...at Pumps w Integrated ERV MODEL VSHPe SE VSHPe G HE FAN CABINET DEV F CHASSIS DEV F DEV G CONTROL BOARD V3 DOCUMENT RELEASE OMEGA VSHPe F IOM 2205 Supersedes document OMEGA VSHPe F IOM 2108 Revision N...

Page 2: ...Heating Season 7 Operating Limits 7 6 Chassis Installation 8 Installation of Fittings and Hoses 8 Chassis Install 8 7 Unit Start Up 9 Checklist 9 Initial Start Up 10 8 Controls 11 Microprocessor Cont...

Page 3: ...result in death of serious injury ALL FIELD WIRING MUST BE PER FORMED ONLY BY A QUALIFIED ELECTRICIAN All wiring must be in accord ance of with the manufacturer s specifications Wiring that is improp...

Page 4: ...x 8 8 x 14 10 x 14 12 x 12 VSHPe 050 1 1 4 14 x 8 8 x 14 10 x 16 14 x 12 VSHPe 060 1 1 2 14 x 8 8 x 14 10 x 16 14 x 12 VSHPe 080 2 18 x 8 8 x 18 14 x 18 14 x 14 VSHPe 100 2 1 2 18 x 8 8 x 18 14 x 20 1...

Page 5: ...the front of the unit Unit includes hose kits and manual shut off valves Optional risers are furnished with type L M copper Available 3 inch deep swage connections on same size piping Contractor to p...

Page 6: ...1 1 2 duct flange 3 ERV Ports Bathroom Exhaust Exhaust Air Outside Air 4 Removable ERV core 5 Heat pump chassis 6 Chassis service cover panel 7 1 air filter 8 Acoustic return air R A panel for chassis...

Page 7: ...on nect switch The panel is removed by swinging out and lifting it off the support pegs The middle panel is a removable swing panel for ac cessing and servicing the ERV core sensors and fans The upper...

Page 8: ...o not allow stub outs to rest or contact the sheet metal opening Do not allow the risers to bottom out when installing into the swage FOR SHIPPED LOOSE RISER SHUT OFF VALVES Visually inspect riser stu...

Page 9: ...ng solution Chassis installation is permitted once the riser system is thoroughly flushed cleaned and water loop is chemical ly treated and commissioned by the riser treatment com pany and contractor...

Page 10: ...ale NPSM riser shut off valves Do not apply pipe dope or pipe sealant to NPSM fittings Always use a back up wrench Fin ger tighten hose and tighten with back up wrench approximately 1 6 turn DO NOT OV...

Page 11: ...nsure the building fluid loop system has been cleaned flushed re filled chemically treated and commissioned by the water treatment company Verify that the main system strainers or mechanical filtratio...

Page 12: ...line is cool and no frosting is forming in the refrigeration circuit 4 Set thermostat to the OFF position Unit compressor and fan should stop running 5 Allow the system to equalize for approximately 5...

Page 13: ...ing HEAT COOL thermostat set DIP 1 set to the OFF position See table below for connecting thermostat to unit termi nal blocks Thermostat Cable Field wire thermostat cable pigtail to the control board...

Page 14: ...com pressor contactor will then be energized so long as none of the following fault conditions are present High Pressure Alarm Low Pressure Alarm Optional High Pressure Water Alarm Optional Condensate...

Page 15: ...oning for both high speed mode P1 and low speed mode P2 Use the ERV board mounted low LO SPD and high speed HI SPD potentiometers to adjust the fan speed and static to meet site conditions SW2 toggle...

Page 16: ...28 22 18 12 37 Speed 13 Watts 11 O clock 70 54 43 34 27 15 7 45 Speed 18 Watts 12 O clock 85 67 55 44 35 23 15 57 Speed 30 Watts 1 O clock 111 95 83 74 68 54 45 37 30 21 15 69 Speed 43 Watts 2 O cloc...

Page 17: ...laptop Wireless router is the preferred method for fewer configuration steps and works with Tablets or Smartphones Wireless Router Method 1 To connect to the controller you will need the follow ing E...

Page 18: ...nge the IP address to 192 168 0 99 and Subnet mask to 255 255 255 0 as shown below Then click OK 7 Open up your internet browser i e Explorer Google Chrome and type in the following address 192 168 0...

Page 19: ...minal was ener gized Y 1 when the Cooling CLG 1 and tripped on Low Pressure fault LP 0 Captured unit controller details indicate a binary value 0 or 1 to signify if there was a call or not for that pa...

Page 20: ...eration 4 Visually inspect the air coil for signs of dirt accumu lation Use a mild detergent or coil cleaning agent DO NOT use any cleaning solutions that contain an acid including acetic acid vinegar...

Page 21: ...ing supply voltage setting at Transformer Check that the line voltage is matched to 208V or 240V transformer taps Heating Cooling Defective compressor capacitor Med Check capacitor and replace if requ...

Page 22: ...REV HPS High Pressure Switch Check continuity between that switch is Normally Closed LPS Low Pressure Switch Check continuity between that switch is Normally Closed RST Refrigerant Suction Temperature...

Page 23: ...rm Soft Lock Out Red Solid Leaving water temperature too hot Non latching alarm Red Blinking Sensor open missing or close shorted Non latching alarm replace sensor Red Solid Entering water temperature...

Page 24: ...or RS return condensate supply Risers can be ordered from factory with 3 inch deep swage Contractor to provide riser transition pieces when joining dissimilar riser sizes All handing s determined by...

Page 25: ...earance Height Slab Thickness 2 inch overlap Rounded up to 120 or 144 Omega supplies two standard riser lengths 120 10 and 144 12 to be field cut on site Omega does not supply extension tailpieces or...

Page 26: ...e 060 1 2 24 VSHPe 080 3 4 30 VSHPe 100 3 4 30 VSHPe 120 3 4 30 Model Hose Kit Isolation Valve Notes Standard NPSM sweat connected isolation valves are provided for Factory or Field Supplied Copper Ri...

Page 27: ...RA panels with supply grille apply gasket tape to supply grille throat to insert into unit sup ply discharge flange Acoustic ERV RA Panel Dimensional Drawing Acoustic ERV RA Panel Sizes A B C VSHPe 03...

Page 28: ...Cabinet Base Height Min 5 1 increments B BH G 1 Note Include flooring thickness underlayment and any concrete leveling as part of calculation Example If using a 6 baseboard with 1 Finished Flooring h...

Page 29: ...y Grille Removable core with door Notes Perimeter Panel shown above with Optional Supply Grille Panel is lined with acoustic insulation for enhanced sound attenuation Return air panel supplied in stan...

Page 30: ...ir opening Optionally insulate the drywall enclosure with plenum rated acoustical insulation for additional sound attenuation Acoustic RA Panel shown Perimeter Panel rough in dimensions are equivalent...

Page 31: ...shown as 3 Supply and Return and 1 25 Condensate Risers can be positioned on any side Back Left Right RA Panel Furring Details Stud Furring EA OA BE BE OA EA OA OA BE BE EA EA EA EA EA EA OA OA OA OA...

Page 32: ...120 Y 18 21 1 2 20 1 8 78 1 2 Model Cabinet Size Cabinet Dimensions in Rough In in Z 22 25 1 2 24 1 8 78 1 2 B Cabinet Base Height Min 5 increases in 1 increments C Panel Flange Height from Base of C...

Page 33: ...OMEGA VSHPe F IOM 2205 31 VHSPe Electrical Schematic ECM Fan...

Page 34: ...actory supplied 6 wire thermostat cable shown Whisper Mode standard on VSHPe units Jumper between R and G1 factory installed Heat Pump Thermostat R 24VAC G1 Whisper Mode Cont Fan On G2 Fan Speed 2 Med...

Page 35: ...0 1140 1120 1100 External Static Pressure in w g 900 750 600 450 375 300 220 1200 1010 820 630 530 460 350 Unit Size EC Motor Speed Minimum SCFM Rated SCFM 030 050 040 080 060 120 100 Note All airflow...

Page 36: ...al balancing valve see name plate for GPM rating Air Temperature Measure the difference in tem perature across air coil for measuring sensible capacity T LAT EAT Sensible Capacity Btuh T x CFM x 1 08...

Page 37: ...ctory Set confirm that settings have not been adjusted to non standard settings SW1 ERV Board Power Switch Set to ON ____ Yes No SW2 ERV Toggle Switch Set to Neutral Middle Position _____ Yes No Fan E...

Page 38: ...______ __________________________________________________________________________________________________________________ ______________________________________________________________________________...

Reviews: