OMEGA-VSHPe.F-IOM-2205

 

 

33 

 

 

 

 

ERV Fan Data 

0

0.05

0.1

0.15

0.2

0.25

0.3

0.35

0.4

0.45

0.5

0.55

0.6

SCFM

SCFM

SCFM

SCFM

SCFM

SCFM

SCFM

SCFM

SCFM

SCFM

SCFM

SCFM

SCFM

WHISPER* 

MODE

N/A

N/A

225

210

195

175

160

145

130

115

100

85

70

-

-

MED

350

340

335

325

315

305

295

285

275

265

255

245

235

HIGH

-

-

365

355

350

340

330

320

310

305

295

285

275

WHISPER* 

MODE

N/A

N/A

250

230

225

205

180

160

145

125

110

90

75

-

-

MED

460

450

445

440

430

425

415

405

395

385

375

365

355

HIGH

-

-

-

-

470

465

455

445

435

430

420

410

400

WHISPER* 

MODE

N/A

N/A

450

430

410

390

370

350

320

300

270

250

220

-

-

MED

-

-

550

540

520

505

485

470

450

430

410

390

375

HIGH

-

-

-

-

-

-

555

540

525

510

490

475

460

WHISPER* 

MODE

N/A

N/A

450

430

410

390

370

350

320

300

270

250

220

-

-

MED

640

620

610

595

580

565

555

540

525

510

490

475

460

HIGH

-

-

675

670

655

650

640

620

610

595

580

565

550

WHISPER* 

MODE

N/A

N/A

620

580

560

520

480

440

410

380

340

300

260

-

-

MED

880

860

840

820

800

780

750

720

700

670

650

625

600

HIGH

-

-

-

-

895

880

860

820

805

795

780

770

760

WHISPER* 

MODE

N/A

N/A

620

580

560

520

480

440

410

380

340

300

260

-

-

MED

1080

1060

1040

1010

990

970

950

930

900

880

860

840

820

HIGH

-

-

-

-

1110

1090

1070

1060

1040

1020

990

980

960

WHISPER* 

MODE

N/A

N/A

620

580

560

520

480

440

410

380

340

300

260

-

-

MED

1230

1200

1185

1170

1150

1130

1110

1095

1080

1055

1040

1020

1000

HIGH

1320

1290

1275

1260

1240

1225

1205

1190

1175

1160

1140

1120

1100

External Static Pressure (in w.g.)

900

750

600

450

375

300

220

1200

1010

820

630

530

460

350

Unit 
Size

EC Motor 

Speed

Minimum 

SCFM

Rated 
SCFM

030

050

040

080

060

120

100

Note: All airflow ratings are taken at lowest voltage rating of dual rating (ie. 208 volt).

 

Airflow ratings include resistance of dry coil, Return Air panel and clean MERV10 air filters. 

 

*Standard 

Whisper

” 

mode is Fan On, Compressor Off mode for constant fresh air circulation. LOW Fan Speed 

tap is not available with Whisper mode.

 

Notes: 

 

• 

All airflow ratings are taken at lowest voltage rating of dual rating (ie. 208 volt).

 

• 

ERV external static setting is based on exhaust duct run.

 

• 

ESP capability shown per fan.

 

• 

Recommended ERV fan speeds are field set to match duct static. Default factory settings may not match site conditions and 

requirements. 

 

• 

Watts includes both ERV fans.

 

• 

Internal Manual OA Slider Damper may be used to control OA introduction in the event of variable OA conditions (i.e. wind stack 

effect)

 

 

0.00

0.025

0.05

0.075

0.10

0.15

0.20

0.25

0.30

0.40

0.50

25% Speed @ 6 Watts

10 O'clock

43

34

28

22

18

12

-

-

-

-

-

37% Speed @ 13 Watts

11 O'clock

70

54

43

34

27

15

7

-

-

-

-

45% Speed @ 18 Watts

12 O'clock

85

67

55

44

35

23

15

-

-

-

-

57% Speed @ 30 Watts

1 O'clock

111

95

83

74

68

54

45

37

30

21

15

69% Speed @ 43 Watts

2 O'clock

139

124

114

106

104

91

82

73

63

53

44

82% Speed @ 61 Watts

3 O'clock

168

155

150

141

139

127

119

107

96

85

72

95% Speed @ 82 Watts

4 O'clock

187

172

166

157

156

145

137

124

115

105

91

ESP (External Static) inwg

% PWM Signal / Power

Potentiometer 

Dial Setting

ECM Fan Data 

Summary of Contents for VSHPe Series

Page 1: ...at Pumps w Integrated ERV MODEL VSHPe SE VSHPe G HE FAN CABINET DEV F CHASSIS DEV F DEV G CONTROL BOARD V3 DOCUMENT RELEASE OMEGA VSHPe F IOM 2205 Supersedes document OMEGA VSHPe F IOM 2108 Revision N...

Page 2: ...Heating Season 7 Operating Limits 7 6 Chassis Installation 8 Installation of Fittings and Hoses 8 Chassis Install 8 7 Unit Start Up 9 Checklist 9 Initial Start Up 10 8 Controls 11 Microprocessor Cont...

Page 3: ...result in death of serious injury ALL FIELD WIRING MUST BE PER FORMED ONLY BY A QUALIFIED ELECTRICIAN All wiring must be in accord ance of with the manufacturer s specifications Wiring that is improp...

Page 4: ...x 8 8 x 14 10 x 14 12 x 12 VSHPe 050 1 1 4 14 x 8 8 x 14 10 x 16 14 x 12 VSHPe 060 1 1 2 14 x 8 8 x 14 10 x 16 14 x 12 VSHPe 080 2 18 x 8 8 x 18 14 x 18 14 x 14 VSHPe 100 2 1 2 18 x 8 8 x 18 14 x 20 1...

Page 5: ...the front of the unit Unit includes hose kits and manual shut off valves Optional risers are furnished with type L M copper Available 3 inch deep swage connections on same size piping Contractor to p...

Page 6: ...1 1 2 duct flange 3 ERV Ports Bathroom Exhaust Exhaust Air Outside Air 4 Removable ERV core 5 Heat pump chassis 6 Chassis service cover panel 7 1 air filter 8 Acoustic return air R A panel for chassis...

Page 7: ...on nect switch The panel is removed by swinging out and lifting it off the support pegs The middle panel is a removable swing panel for ac cessing and servicing the ERV core sensors and fans The upper...

Page 8: ...o not allow stub outs to rest or contact the sheet metal opening Do not allow the risers to bottom out when installing into the swage FOR SHIPPED LOOSE RISER SHUT OFF VALVES Visually inspect riser stu...

Page 9: ...ng solution Chassis installation is permitted once the riser system is thoroughly flushed cleaned and water loop is chemical ly treated and commissioned by the riser treatment com pany and contractor...

Page 10: ...ale NPSM riser shut off valves Do not apply pipe dope or pipe sealant to NPSM fittings Always use a back up wrench Fin ger tighten hose and tighten with back up wrench approximately 1 6 turn DO NOT OV...

Page 11: ...nsure the building fluid loop system has been cleaned flushed re filled chemically treated and commissioned by the water treatment company Verify that the main system strainers or mechanical filtratio...

Page 12: ...line is cool and no frosting is forming in the refrigeration circuit 4 Set thermostat to the OFF position Unit compressor and fan should stop running 5 Allow the system to equalize for approximately 5...

Page 13: ...ing HEAT COOL thermostat set DIP 1 set to the OFF position See table below for connecting thermostat to unit termi nal blocks Thermostat Cable Field wire thermostat cable pigtail to the control board...

Page 14: ...com pressor contactor will then be energized so long as none of the following fault conditions are present High Pressure Alarm Low Pressure Alarm Optional High Pressure Water Alarm Optional Condensate...

Page 15: ...oning for both high speed mode P1 and low speed mode P2 Use the ERV board mounted low LO SPD and high speed HI SPD potentiometers to adjust the fan speed and static to meet site conditions SW2 toggle...

Page 16: ...28 22 18 12 37 Speed 13 Watts 11 O clock 70 54 43 34 27 15 7 45 Speed 18 Watts 12 O clock 85 67 55 44 35 23 15 57 Speed 30 Watts 1 O clock 111 95 83 74 68 54 45 37 30 21 15 69 Speed 43 Watts 2 O cloc...

Page 17: ...laptop Wireless router is the preferred method for fewer configuration steps and works with Tablets or Smartphones Wireless Router Method 1 To connect to the controller you will need the follow ing E...

Page 18: ...nge the IP address to 192 168 0 99 and Subnet mask to 255 255 255 0 as shown below Then click OK 7 Open up your internet browser i e Explorer Google Chrome and type in the following address 192 168 0...

Page 19: ...minal was ener gized Y 1 when the Cooling CLG 1 and tripped on Low Pressure fault LP 0 Captured unit controller details indicate a binary value 0 or 1 to signify if there was a call or not for that pa...

Page 20: ...eration 4 Visually inspect the air coil for signs of dirt accumu lation Use a mild detergent or coil cleaning agent DO NOT use any cleaning solutions that contain an acid including acetic acid vinegar...

Page 21: ...ing supply voltage setting at Transformer Check that the line voltage is matched to 208V or 240V transformer taps Heating Cooling Defective compressor capacitor Med Check capacitor and replace if requ...

Page 22: ...REV HPS High Pressure Switch Check continuity between that switch is Normally Closed LPS Low Pressure Switch Check continuity between that switch is Normally Closed RST Refrigerant Suction Temperature...

Page 23: ...rm Soft Lock Out Red Solid Leaving water temperature too hot Non latching alarm Red Blinking Sensor open missing or close shorted Non latching alarm replace sensor Red Solid Entering water temperature...

Page 24: ...or RS return condensate supply Risers can be ordered from factory with 3 inch deep swage Contractor to provide riser transition pieces when joining dissimilar riser sizes All handing s determined by...

Page 25: ...earance Height Slab Thickness 2 inch overlap Rounded up to 120 or 144 Omega supplies two standard riser lengths 120 10 and 144 12 to be field cut on site Omega does not supply extension tailpieces or...

Page 26: ...e 060 1 2 24 VSHPe 080 3 4 30 VSHPe 100 3 4 30 VSHPe 120 3 4 30 Model Hose Kit Isolation Valve Notes Standard NPSM sweat connected isolation valves are provided for Factory or Field Supplied Copper Ri...

Page 27: ...RA panels with supply grille apply gasket tape to supply grille throat to insert into unit sup ply discharge flange Acoustic ERV RA Panel Dimensional Drawing Acoustic ERV RA Panel Sizes A B C VSHPe 03...

Page 28: ...Cabinet Base Height Min 5 1 increments B BH G 1 Note Include flooring thickness underlayment and any concrete leveling as part of calculation Example If using a 6 baseboard with 1 Finished Flooring h...

Page 29: ...y Grille Removable core with door Notes Perimeter Panel shown above with Optional Supply Grille Panel is lined with acoustic insulation for enhanced sound attenuation Return air panel supplied in stan...

Page 30: ...ir opening Optionally insulate the drywall enclosure with plenum rated acoustical insulation for additional sound attenuation Acoustic RA Panel shown Perimeter Panel rough in dimensions are equivalent...

Page 31: ...shown as 3 Supply and Return and 1 25 Condensate Risers can be positioned on any side Back Left Right RA Panel Furring Details Stud Furring EA OA BE BE OA EA OA OA BE BE EA EA EA EA EA EA OA OA OA OA...

Page 32: ...120 Y 18 21 1 2 20 1 8 78 1 2 Model Cabinet Size Cabinet Dimensions in Rough In in Z 22 25 1 2 24 1 8 78 1 2 B Cabinet Base Height Min 5 increases in 1 increments C Panel Flange Height from Base of C...

Page 33: ...OMEGA VSHPe F IOM 2205 31 VHSPe Electrical Schematic ECM Fan...

Page 34: ...actory supplied 6 wire thermostat cable shown Whisper Mode standard on VSHPe units Jumper between R and G1 factory installed Heat Pump Thermostat R 24VAC G1 Whisper Mode Cont Fan On G2 Fan Speed 2 Med...

Page 35: ...0 1140 1120 1100 External Static Pressure in w g 900 750 600 450 375 300 220 1200 1010 820 630 530 460 350 Unit Size EC Motor Speed Minimum SCFM Rated SCFM 030 050 040 080 060 120 100 Note All airflow...

Page 36: ...al balancing valve see name plate for GPM rating Air Temperature Measure the difference in tem perature across air coil for measuring sensible capacity T LAT EAT Sensible Capacity Btuh T x CFM x 1 08...

Page 37: ...ctory Set confirm that settings have not been adjusted to non standard settings SW1 ERV Board Power Switch Set to ON ____ Yes No SW2 ERV Toggle Switch Set to Neutral Middle Position _____ Yes No Fan E...

Page 38: ...______ __________________________________________________________________________________________________________________ ______________________________________________________________________________...

Reviews: