11 | 

P a g e

 

 

 

5

 

Appendix: SP-014 Registers 

The following Appendix provides the registers and list index for the Layer N SP-014 Process Monitoring Smart Probe. This 

information is intended to aid users who will be making configurations and adjustments to their Layer N SP-014 Process 

Monitoring Smart Probe through the Command Line Interface or other custom interfaces. 

 

Smart Probe devices share a common platform architecture that provides extensive monitoring and control capabilities thru 

a set of platform generic registers. These registers may be accessed using I2C based commands directly to the Smart Probe 

devices or thru a set of Modbus based registers when using Omega Interface devices. Refer to the 

Smart Sensor Device 

Interface

 manual for further information. 

 

When powered on or after a device reset each Smart Sensor based device will enumerate 1 or more sensor instances which 

are described by the device specific Sensor Descriptors which include configuration options, measurement type and units of 

measure for the corresponding sensor values. Additional sensor information is provided in sensor specific IPSO object 

descriptions which include extended measurement type, precision and tracking of minimum/maximum readings.  

 

Each enumerated Sensor has a Descriptor Base address location and a Sensor IPSO / Configuration structure address 

location based on the sensor mix selected. 

 

Sensor  Descriptor Base  IPSO/Configuration 

Enumerated Sensors 

0x0060 (0xf030) 

0x08a8 (0xf454) 

Process 0 

0x0068 (0xf034) 

0x09a8 (0xf4d4) 

Process 1 

DIO (SP-014-1) 

0x0070 (0xf038) 

0x0aa8 (0xf554) 

Process 2 

DIO (SP-014-1) 

0x0078 (0xf03c) 

0x0ba8 (0xf5d4) 

DIO (SP-014-1) 

 

 

5.1

 

Process Interface 

The Process Input interface provides single ended voltage and current loop inputs. The Sensor Configuration and Sensor 

Device fields may be written to provide control of the overall function of the channel and the signal types used. 

 

Offset 

Name 

Value 

Description 

0x00 

Measurement 

Type 

0x?? 

Analog Voltage and Current – set by Sensor Type 

field in Configuration byte. 

0x01 

Data Type/Format 

0x46 

Float, writeable 

0x02 

Configuration 

0x?? 

Determines Process input type/range 

0x03 

Sensor Device 

0x?? 

Determines AIO signal types 

0x04..0x08 

UOMR 

“??” 

Units of measure 

 

5.1.1

 

Process Measurement Types 

The Process interface provides a measurement dependent on the input range/type selected. The units of measure 

may be changed by the user. 

 

Sensor Type 

SI Derived 

Units 

Measurement 

0x11 

mV 

Process Voltage (0 - 1.0 V) 

0x13 

mA 

Process Current (0-24 mA current loop, common return) 

 

 

 

Summary of Contents for SP-014

Page 1: ...1 P a g e TM User sGuide Shop online at omega com e mail info omega com For latest product manuals www omegamanual info SP 014 Process Monitoring Smart Probe...

Page 2: ...nly Customer Service 1 800 622 2378 USA Canada only Engineering Service 1 800 872 9436 USA Canada only U S A Headquarters Tel 203 359 1660 e mail info omega com Fax 203 359 7700 The information contai...

Page 3: ...5 1 2 4 Smart Sensor 12 5 1 3 Process Input Configuration 12 5 1 3 1 Sensor Type Range 12 5 1 3 2 Apply Scaling 12 5 1 3 3 Lock 12 5 1 3 4 Assigned 12 5 1 3 5 Available 12 5 1 4 Process Input Sensor D...

Page 4: ...4 P a g e 5 3 2 Active State 17 5 3 3 Output Drive 17 5 3 4 Output Type 17 6 Specifications 18 7 Errata 18...

Page 5: ...vice as it contains important information relating to safety and EMC Failure to follow all the safety precautions may result in injury and or damage to your equipment The following labels identify inf...

Page 6: ...onfigured as 0 24 mA or 0 1 0 VDC inputs The Layer N SP 014 features 2 configurable digital I O pins These can be used for a myriad of applications including driving relays physical alarms or sensing...

Page 7: ...process inputs through its M12 5 Pin connector If you are connecting wires directly to the SP 014 view the wiring diagrams provided below Pin Name Function Pin 1 DIO 0 Discrete I O Signal 0 Pin 2 INT...

Page 8: ...ly detect your device follow these instructions to manually connect it Step 1 Click on the icon located on the top left of the SYNC interface Step 2 Proceed through the Add Device Wizard and click End...

Page 9: ...rols bits per second DataBits The number of bits in each character sent Parity A means of checking correctness of character by adding an extra bit to the character and setting the value based on all t...

Page 10: ...Action section The alarm can be set to be latching or non latching in the Recovery section 4 5 ON OFF Control To configure ON OFF Control on a device navigate to the Output Configuration Tab in SYNC...

Page 11: ...extended measurement type precision and tracking of minimum maximum readings Each enumerated Sensor has a Descriptor Base address location and a Sensor IPSO Configuration structure address location b...

Page 12: ...Writeable The writable bit is cleared indicating that the sensor values may not be overwritten 5 1 2 4 Smart Sensor Refer to the Smart Sensor Device Interface documentation 5 1 3 Process Input Config...

Page 13: ...0 0x04 Sensor Trigger Write any value to force reset of min max 0x08 Min Measured Minimum reading since last reset 0x0c Max Measured Maximum reading since last reset 0x10 Min Range Range Minimum Maxi...

Page 14: ...ed digital inputs 5 2 2 DIO Data Type Format DIO Data Type 7 6 5 4 3 2 1 0 Smart Sensor Sensor Writable Factory Calibrate reserved Data Type 0 0 0 0 6 Floating point Note Please refer to the Smart Sen...

Page 15: ...ert Bit is set the signal will be Active Low DIO Device Configuration 7 6 5 4 3 2 1 0 Reserved DIN 1 DIN 0 0 0 0 0 ENABLE INVERT ENABLE INVERT 1 1 1 1 5 2 4 1 Invert If the Invert bit is set the input...

Page 16: ...uts and all bits should be written as 0 5 2 6 DIO Input Circuitry The DIO input circuitry shares the output circuitry The internal processor drives the Output Control signal to turn on the output driv...

Page 17: ...10 Hz PWM signal has constant 10 Hertz frequency 100 msec repetition rate with 0 100 duty cycle 2 1 Hz PWM signal has constant 1 Hertz frequency 1 second repetition rate with 0 100 duty cycle 3 0 1 H...

Page 18: ...ature 0 02 FS C ENVIRONMENTAL Operating Temperature 40 to 85 C 40 to 185 F Rating IP67 when mated MECHANICAL Dimensions 22 1 mm W x 96 7 mm L 0 87 x 3 80 not including mounting tabs GENERAL Agency App...

Page 19: ...A if the unit is found to be defective it will be repaired or replaced at no charge OMEGA s WARRANTY does not apply to defects resulting from any action of the purchaser including but not limited to m...

Page 20: ...s M U Turbine Paddlewheel Systems M U Totalizers Batch Controllers pH CONDUCTIVITY M U pH Electrodes Testers Accessories M U Benchtop Laboratory Meters M U Controllers Calibrators Simulators Pumps M U...

Reviews: