Lable 

Item

Setting range

Description

SPx 

(Note1)

OUT upper limit

-

~

99999 99999

Upper limit value of transistor output 

Rpx

OUT lower limit

-

~

99999 99999

Lower limit value of transistor output 

SPDTx

OUT output delay

0 0 60.0(S)

. ~

Delay time before transistor output active

RPDTx

OUT reset delay

0 0 60 0(S

. ~

.

)

Delay time before transistor output reset 

Modex

OUT 
working mode

Modex=0

No output. OUTx keeps reset state 

Modex=1

Measured value > SPx, delay SPDTx, OUTx active (Note2)

Measured value < RPx, delay RPDTx, OUTx reset (0V, the same below)

Modex=2

Measured value > SPx, delay SPDTx, OUTx reset

Measured value < RPx, delay RPDTx, OUTx active

Modex=3

RPx < measured value < SPx, delay SPDTx, OUTx active

Measured value > SPx or measured value < RPx, delay RPDTx, OUTx reset

Modex=4

Measured value > SPx or measured value < RPx, delay SPDTx, OUTx active

RPx < measured value < SPx, delay RPDTx, OUTx reset

Notes: 1. x =1 or 2, SPx ≥ RPx
           2. Active electrical level is 2V lower than power supply level. Eg, power supply level is 24V, then active electrical level is 22V.

P

SP

x

RP

x

OUT

Active

Reset

T

T

OUT

Active

Reset

T

OUT

Active

Reset

T

OUT

Active

Reset

T

OUT

Active

Reset

T

P: pressure
T: time
x=1 or 2

Modex 0

No output

= ,

Modex 1

HNO

Upper limit alarm/ hysteresis function

= ,

Modex 2

HNC

Lower limit alarm/ hysteresis function

= ,

SPDTx

RPDTx

RPDTx

SPDTx

Modex 3

FNO

Window mode/ delayed alarm in window

= ,

Modex 4

FNC

Window mode/ delayed alarm out window

= ,

RPDTx

RPDTx

SPDTx

SPDTx

SPDTx

SPDTx

RPDTx

RPDTx

High level alarm

Output alarm signal when pressure is higher than 145Psi. 
Normal setting: SP1=145Psi, RP1=137.78Psi, Mode1=1, SPDT1=1, 
RPDT1=1. Pressure rises to 145Psi, delay 1s, OUT1 active (on); 
pressure drops to 137.78Psi, delay 1s, OUT1 reset (off) 

Output alarm signal when pressure is lower than 145Psi. 
Normal setting: RP1=145Psi, SP1=152.28Psi, Mode1=2, SPDT1=1, 
RPDT1=1. Pressure drops to 145Pssi, delay 1s, OUT1 active (on); 
pressure rises to 152.28Psi, delay 1s, OUT1 reset (off) 

Low level alarm

Starting devices normally requires pressure is within the range 
72.51~145Psi. Normal setting: SP1=145Psi, RP1=72.51Psi, Mode1=3, 
SPDT1=1, RPDT1=1. Pressure rises to 145Psi, delay 1s, OUT1 active 
(on); pressure rises to 145Psi, delay 1s, OUT1 reset (off); Pressure 
drops to 145Psi, delay 1s, OUT1 active (on); pressure drops to 
72.51Psi, delay 1s, OUT1 reset (off) 

Window function

Applying pressure on a device by a compressor and keeping the 
pressure within the range 72.51~145Psi need two ways output. The 
first way output controls the compressor and the second way output 
controls the device. The first way output setting: SP1=130.53Psi, 
RP=87.02Psi, Model=2, SPDT1=1, RPDT1=1. The first way contact 
controls the power supply of compressor through intermediate relay 
to disconnect once the pressure is higher than 130.53Psi and connect 
once the pressure is lower than 87.02Psi. The pressure value needs to 
be controlled within 87.02~130.53MPa. The second way output setting: 
SP2=145Psi, RP2=72.51Psi, Mode2=3, SPDT2=1, RPDT2=1. Once 
the working pressure of device is not within the range 
72.51Psi~145Psi, after 1s, the second way contact controls the alarm 
output of  the device through intermediate relay to ensure the abnormal 
working pressure of the device can be discovered and handled in time.

Automatically keep pressure function

Summary of Contents for PSW2100

Page 1: ...INSTRUCTION SHEET For latest product manuals omegamanual info Shop online at omega com e mail info omega com PS 2100 M 5762 0320 W ...

Page 2: ...n be installed with adapters on the pipe directly Can be used for liquid level measurement in open container Media compatibility should be considered Two pressure switches can be used to create a differential measurement system commonly used in the filter control or closed container level measurement Light weight pressure can be mounted directly on the pressure leading tube When the maximum torque...

Page 3: ...lt in transient resistance module is only effective if properly grounded The metal body and internal grounding terminals should be directly grounded To safeguard against liquid media potentially traveling along the cable into the terminal box the cable should be configured in a U shape as shown with the bottom of the U lower than the bottom of the pressure switch Do not store outside Keep dry and ...

Page 4: ...i Normal setting SP1 145Psi RP1 137 78Psi Mode1 1 SPDT1 1 RPDT1 1 Pressure rises to 145Psi delay 1s OUT1 active on pressure drops to 137 78Psi delay 1s OUT1 reset off Output alarm signal when pressure is lower than 145Psi Normal setting RP1 145Psi SP1 152 28Psi Mode1 2 SPDT1 1 RPDT1 1 Pressure drops to 145Pssi delay 1s OUT1 active on pressure rises to 152 28Psi delay 1s OUT1 reset off Low level al...

Page 5: ... Psi Press at the same time at least 3 seconds Z S 0 010 Rotating Success 010 0 Measuring interface Press at the same time at least 3 seconds S M Finished interface Measuring interface Press at least 3 seconds M Measuring interface with lock Successful interface Finished interface 0 010 Psi Press M 0 010 Psi Press at least 3 seconds S 100 00 M key for exit 0 010 Psi Measuring interface Measuring i...

Page 6: ... 10 01 Ran 99999 99999 confirm and enter next menu Z Ran 99999 99999 Ran 99999 99999 URV Ran 99999 99999 URV kPa kPa Mpa Unit Unit confirm and enter next menu M Display selected parameters Display selected parameters confirm and enter next menu Z 0 1 2 3 4 5 6 7 8 9 10 11 12 0 1 2 Pressure Unit Two rows display PV Unit Three rows display percentage pv unit Three rows display SP1 RP1 alternate disp...

Page 7: ...ode1 enter settings Z Current parameters 0 0 0 No Out 0 1 Hysteresis P SPn Ran 0 00 60 0S SPDT1 Ran 0 00 60 0S 0 0 SPDT1 Display selected parameters Ran 0 00 60 0S 0 1 SPDT1 confirm and enter next menu Z No Out Mode1 Mode1 Measuring interface Display selected parameters Display modified parameters 0 0 60 0S 0 1 2 3 4 No Out Hysteresis P SPn Hysteresis P RPn Window RPn P SPn Window P RPn P SPn SP1 ...

Page 8: ...isplay modified parameters Display modified parameters enter settings Z modify parameters S confirm and enter next menu Z 0 0 Ran 0 00 60 0S 0 0 SPDT2 Ran 0 00 60 0S SPDT2 Ran 0 00 60 0S 0 1 SPDT2 Display modified parameters Current parameters Display modified parameters enter settings Z modify parameters S SP2 enter settings Z modify parameters S Measuring interface 0 010 kPa Press Z Current para...

Page 9: ...20 800 24 000mA Current parameters Display modified parameters Note 1 By default the system shows optimal precision according to measuring range Eg While the measuring range of product is 0 10kPa measuring value shows 0 000 10 000 while the measuring range of product is 0 100kPa the measuring value shows 0 00 100 00 If DotPos parameters value and measuring range do not match the system will automa...

Page 10: ...8 ...

Reviews: