10
CONVERSION TO DIFFERENT TYPES OF GAS
Before performing any maintenance operation, disconnect the appliance from the ga s supply and
electricity network.
REPLACING THE NOZZLES TO OPERATE WITH ANOTHER TYPE OF GAS
When converting to LPG remove the NG gas regulator (if fitted) and fit LPG test point adaptor.
If converting to Natural Gas, fit gas regulator
Follow the instructions below to change the burner nozzles on the work surface:
1) Pull out the plug from the electric outlet to avoid any type of electric contact.
2) Remove the grids from the work surface (Fig. 10).
3) Remove the burners (Fig. 10).
Fig. 10 (representation only)
4) Unscrew the nozzles using a 7 mm spanner, and replace them (Fig.11) with those needed for the new type of gas
according to what is indicated in the Energy Consumption Table.
Fig. 11
5) Burner "MINIMUM" adjustment:
Work surface burner adjustment: follow the instructions below to adjust the work surface burner minimum:
Light the burner and set the knob to the MINIMUM position (small flame).
Remove the knob of the valve that is press fit on the rod of that valve.
For all burners except for the wok burner, insert a small slotted screwdriver into the hole on the valve rod (Fig. 12) and
turn the choke screw to the right or left until the burner flame is adjusted to minimum.
The wok burner has 2 adjustment screws on either side of the body of the valve (Fig. 13). Screw A is for the outer ring
and screw B is for the inner ring. Turn the choke screw to the right or left until the burner flam e is adjusted to minimum.
Ensure sure that the flame does not go out when s witching quickly from the MAXIMUM to the MINIMUM position.
Fig. 12
Fig. 13