FLOW CHART

CONFIGURATION

MENU 

Mode:

Flashing display in MENU Mode means you can make your
selection by pressing 

b

button. If the flashing display is not

a four digit value, pressing 

c

button will always direct the

instrument one step backward of the top menu item. The
second push on the 

c

button will reset the instrument

except after the setpoint and the alarms, that will go to the
RUN Mode without resetting the instrument. The 

a

button

will always sequence the instrument thru the menu items.

The 

d

button has two functions:

1.

To save a selected flashing display

2.

To direct the instrument to the next submenu level

RUN 

Mode:

b

causes the display to flash the PEAK with the 
corresponding value. Press again to go back to RUN 
Mode.

c

causes the display to flash VALLEY with the 
corresponding value. Press again to go back to RUN 
Mode.

d

causes flashing PEAK or VALLEY to reset corresponding 
values. Pressing 

d

 twice will cause the display to flash 

STBY

 and put the instrument into standby, which disables

all outputs and alarms. Press 

d

one more time to go 

back to RUN Mode.

OPERATION - (For Thermocouple Input)

Step 1. Apply Power to the Instrument

When your device is first powered up it will display the
ambient temperature (assume 75°F).

Step 2. Enter Setpoint 1 Menu

Press 

a

one time from run mode to get to 

SP1

Setpoint 1. 

Step 3. Enter the Setpoint 1 Value Submenu

Press 

d

. Display shows the previous selection of Setpoint 1.

Step 4. Change the Setpoint 1 Value 

Press 

b

or 

c

until desired value is displayed.

Step 5. Store the Setpoint 1 Value 

Set the Setpoint 1 to 10 degree higher than Process value
(SP1 = 85) and press 

d

to store, display flashes 

STRD

message and advances to 

SP2

Setpoint 2 Menu.

Step 6. Store the Setpoint 2 Value

Repeat steps 3 and 4. Set the Setpoint 2 to 5 degree higher
than Process value (SP2 =  80) and press 

d

to store,

display flashes 

STRD

message and advances to 

CNFG

Configuration Menu.

Step 7. Enter the Input Type Menu

Press 

d

to enter 

INPT

Input Type Menu.

Step 8. Enter to the submenu items of Input Menu

Press 

d

to display Input: Process, RTD or Thermocouple. 

If flashing 

T.C

is displayed press 

a

and proceed to Step 11.

Step 9. Scroll through available selection of Input Menu

Press 

b

until a flashing 

T.C

for Thermocouple is displayed.

Step 10. Enter to the Thermocouple Input Submenu

Press 

d

to store Thermocouple Input. The display will stop

flashing and show the top menu for Thermocouple types. If
you press 

a

controller will step to next menu item (Skip to Step 14). 

_____

Underline denotes factory default setup

Mounting Big Display Through Panel:
1.

Using the panel cutout diagram shown, cut an opening in
the panel.

2. 

Remove six screws at the back of Big Display to remove 
back cover.

3.

Insert the unit into the opening from the front of the panel, 
so the gasket seals between the bezel and the front of the
panel.

4.

Align back cover to Big Display and reinstall screws.

Mounting Big Display on Bail:
1.

Mark the location of mounting screws on the flat surface.

2. 

Be sure to leave enough room around the bail to allow for 
removal and rotation of the display.

3.

The display can be rotated for the best viewing angle.

Disassembly Instruction:

Warning: Disconnect all ac power from the unit
before proceeding.

1.

Remove all wiring connections from the rear of the 
instrument, by unscrewing the power and input connectors.

2.

Remove six screws at the back of the display and back cover.

3.

Remove the Big Display from the panel.

4.

To remove the Big Display from the bail, unscrew the two 
knobs at each end of the mounting brackets.

WIRING

Wire the instrument according to the Input and Output
Wiring Connections described in your Operator’s Manual.

Warning: Do not connect ac power to your
device until you have completed all input and
output connections. This device must only be
installed by a specially trained electrician with
corresponding qualifications. Failure to follow
all instructions and warnings may result in injury!

Connect the main ac power connections as shown in the figure
below.

POWER

1  2  3

1  2

1  2  3 4  5

L N

+  -

1  2  3

1  2  3

4  5  6

1  2 3  4 5  6 7  8

1 2 3 4 5 6

1  3  5

     2  4  6 

+   -

OUTPUT2  OUTPUT1

RTN Rx Tx

AC

PWR

TB1

DC

PWR

REMOTE
PROGRAMMER

TB2

TB3

TB4

TB9

TB7 TB8

PJ3

COMMUNICATION

OUTPUTS

T/C INPUT

INPUTS

TB5

This Quick Start Reference provides information on
setting up your instrument for basic operation. The
latest complete Communication and Operational
Manual as well as free Software and ActiveX
Controls are available at 

www.omega.com or on

the CD-ROM enclosed with your shipment

.

SAFETY CONSIDERATION

This device is marked with the international
Caution symbol.

The instrument is a panel mount device protected in
accordance with EN 61010-1:2001, electrical safety
requirements for electrical equipment for measurement, control
and laboratory. Remember that the unit has no power-on
switch. Building installation should include a switch or circuit-
breaker that must be compliant to IEC 947-1 and 947-3.

SAFETY:

• Do not exceed voltage rating on the label located on 

the back of the instrument housing.

• Always disconnect power before changing signal and 

power connections.

• Do not use this instrument on a work bench without 

its case for safety reasons.

• Do not operate this instrument in flammable or 

explosive atmospheres.

EMC:

• Whenever EMC is an issue, always use shielded cables. 
• Never run signal and power wires in the same conduit.
• Use signal wire connections with twisted-pair cables.
• Install Ferrite Bead(s) on signal wire close to the 

instrument if EMC problems persist.

MOUNTING