background image

 12 

4 - ALARM 

With these settings, it is determined how the flow rate will be monitored and the functionality of the transistor outputs be deter-
mined. 

ALARM 
4.1 

Setting the function of the Alarm  
The following settings can be selected: 
Off: 

Function disabled. 

Operate: 

Full function of the low flow alarm. 

Hidden:  

Does not display alarms on LCD. 

ALARM VALUE 
ZERO 
4.2 

The Zero alarm is set with this setting. An alarm will be generated as long as there is no flow rate. 
Select Off to disable 

ALARM VALUE 
LOW 
4.3 

The low alarm is set with this setting. An alarm will be generated as long as the flow rate is lower 
than this. 
With value 0.0 this function is disabled. 

ALARM VALUE 
HIGH 
4.4 

The high alarm is set with this setting. An alarm will be generated as long as the flow rate is higher 
than this. 
With value 0.0 this function is disabled. 

DELAY TIME ALARM 
4.5 

This function allows a delay period before the alarm is activated 0—99 seconds. 

6 - ANALOG OUTPUT 

A linear analog (0)4-20mA signal is generated according to the flow rate with a 10 bits resolution. The settings for flow rate 
(SETUP - 2) influence the analog output directly. 
The relationship between rate and analog output is set with the following functions: 

MINIMUM FLOWRATE 
6.1 

Enter here the flowrate at which the output should generate the minimum  signal (0/4mA or 0V) - in 
most applications at flow rate "zero". 
The number of decimals displayed depend upon SETUP 23. 
The time and measuring units (L/min for example) are dependant upon SETUP 21 and 22 but are 
not displayed. 

MAXIMUM FLOWRATE 
6.2 

Enter here the flow rate at which the output should generate the maximum signal (20mA or 10V) - 
in most applications at maximum flow. 
The number of decimals displayed depend upon SETUP 23. 
The time and measuring units (L/min for example) are dependant upon SETUP 21 and 22 but can 
not be displayed. 

TUNE MIN / 4MA 
6.3 

The initial minimum analog output value is 4mA . However, this value might differ slightly due to 
external influences such as temperature for example. The 4mA value can be tuned precisely with 
this setting. 

Before tuning the signal, be sure that the analog signal is not being used for any 

application! 

After pressing PROG, the current will be about 4mA The current can be increased / decreased with 
incrementing or decrementing the numbers and is directly active. Press ENTER to store the new 
value. 
Remark: the analog output value can be programmed “up-side-down” if desired, so 20mA at mini-
mum flowrate for example! 

TUNE MAX / 20MA 
6.4 

The initial maximum analog output value is 20mA. However, this value might differ slightly due to 
external influences such as temperature  for example. The 20mA value can be tuned precisely with 
this setting. 

Before tuning the signal, be sure that the analog signal is not being used for any 

application! 

After pressing PROG, the current will be about 20mA. The current can be increased / decreased 
with incrementing or decrementing the numbers and is directly active. Press ENTER to store the 
new value. 
Remark: the analog output value can be programmed “up-side-down” if desired, so 4mA at maxi-
mum flow rate for example! 

FPD3100-D-A DIGITAL REGISTER 

Set-up Functions 

Summary of Contents for FPD3100-D Series

Page 1: ...e mail info omega com For latest product manuals www omegamanual info FPD3100 D and FPD3100 D A Series 12mm LC Digital Display with Analog Output Options Shop online at omega com User sGuide...

Page 2: ...6 USA Canada only Tel 203 359 1660 Fax 203 359 7700 e mail info omega com For Other Locations Visit omega com worldwide omega com info omega com The information contained in this document is believed...

Page 3: ...ge 6 Wiring Diagram Page 7 Parts Listing Page 7 Technical Specifications Page 8 Type FPD3100 D A Digital Register Program Overview Page 10 Set up Functions Page 11 13 Wiring Diagram Page 13 Outputs Pa...

Page 4: ...polypropylene housing offers IP65 environmental protection Configuration of the unit The FPD3100 Series has been designed to be implemented in many types of applications For that reason a SETUP level...

Page 5: ...seconds Default 35 4 METER 4 METER SIGNAL Reed Switch Only 4 1 K FACTOR Pulses per Unit 0000 000 to 9999 999 5 OTHERS 6 1 TYPE DR 6 2 SOFTWARE VERSION 03 xx xx 6 3 SERIAL NO xxxxxxx GENERAL Configura...

Page 6: ...per litre and unit adjustment is done automatically TIME UNIT 3 2 The flow rate can be calculated per second SEC minute MIN hour HR or day DAY DECIMALS 3 3 This setting determines for flow rate the n...

Page 7: ...nput this sensor has been selected as the most common sensor and requires very little power with small effect on battery life The 2 position terminal block is not polarity conscious so the reed switch...

Page 8: ...A size Terminal connections Type Terminal strip Wire max 1mm Data protection Type Backup of all settings and running totals in flash memory Environment Electromagnetic compatibility Compliant ref EN...

Page 9: ...9 NOTES...

Page 10: ...m3 US GAL UK GAL US bbl UK bbl OIL bbl L 22 DECIMALS 0 1 2 3 0 FLOWRATE DEFAULT 31 UNIT L m3 US GAL UK GAL US bbl UK bbl OIL bbl L 32 TIME UNIT sec min hour min 33 DECIMALS 0 1 2 3 0 34 CALCULATION p...

Page 11: ...entered in 5 1 should be in pulses per litre and unit adjustment is done automatically TIME UNIT 3 2 The flow rate can be calculated per second SEC minute MIN hour HR or day DAY DECIMALS 3 3 This sett...

Page 12: ...endant upon SETUP 21 and 22 but are not displayed MAXIMUM FLOWRATE 6 2 Enter here the flow rate at which the output should generate the maximum signal 20mA or 10V in most applications at maximum flow...

Page 13: ...l be emptied It might be that pulses will be missed due to a buffer overflow so it is advised to program this setting within it s range PULSE PER 7 3 According to the measurement unit settings for tot...

Page 14: ...e output must be programmed as follows In menu 7 1 set 2222 22 In menu 7 2 set 10 or more 10mS or more if needed In menu 7 3 set 1 00 Example Pulse Alarm Output Setup Passive 4 20mA setup 9 10 Pulse O...

Page 15: ...15 FPD3100 D A DIGITAL REGISTER Parts Description...

Page 16: ...years 20 C ER17505 3 6V A size Terminal connections Type Terminal strip Wire max 1mm Data protection Type Backup of all settings and running totals in flash memory Environment Electromagnetic compati...

Page 17: ...the 4 00mA and 20 00mA levels precisely within set up Minimum operating voltage 8V DC Power supply 18 30V DC Switch outputs Function One scaled pulse output transmitting accumulated total One high fl...

Page 18: ...n 33 decimals 0000000 34 calculation pulses 010 35 cut off time 30 0 sec 4 Alarm 41 alarm disabled 42 flow zero on 43 alarm low 0 44 alarm high 9999 45 delay alarm 0 5 FLOWMETER 51 k factor 1 000 6 AN...

Page 19: ...PD3100 series is available with a Wall Mount Bracket option for applications requiring remote mount display Both the models D and D A are available with this option Following is a dimensional drawing...

Page 20: ...therwise shall not exceed the purchase price of the component upon which liability is based In no event shall OMEGA be liable for consequential incidental or special damages CONDITIONS Equipment sold...

Page 21: ...bine Paddlewheel Systems M U Totalizers Batch Controllers pH CONDUCTIVITY M U pH Electrodes Testers Accessories M U Benchtop Laboratory Meters M U Controllers Calibrators Simulators Pumps M U Industri...

Reviews: