The FP7002 flow/temperature transmitter is ideal for monitoring of 

typical industrial water flows and temperature, from hard-to-handle 

corrosive aqueous solutions to high purity fluids. The FP7002 uses a 

paddlewheel-like rotor whose motion is converted into a pulse output. 

This pulse output is converted to a 4 - 20 mA (or 1 - 5 Vdc) analog 

output by the built-in signal conditioner. A solid state temperature 

sensor built into the sensor body provides a separate 4 - 20 mA (or 

1 - 5 Vdc) analog output directly proportional to changes in fluid 

temperature. These independent analog outputs can be run long 

distances to a panel meter, controller or computer.
A complete flow measurement system consists of the flow sensor/

transmitter, the installation fitting and a readout device. The FP7002 

has polypropylene, 316SS, and FKM wetted parts. The schedule 40 PVC 

tee fittings are supplied with a PVC locking nut, and the galvanized 

iron tee fittings are supplied with a brass locking nut to provide a 

secure metal to-metal mounting to the threaded brass insert.

Section 2 - Installation

2.1 Unpacking

Remove the Packing List and verify that you have received all 

equipment. If you have any questions about the shipment, please call 

the OMEGA Customer Service Department.
When you receive the shipment, inspect the container and equipment 

for any signs of damage. Note any evidence of rough handling in 

transit. Immediately report any damage to the shipping agent.

  

N O T E

The carrier will not honor any claims unless all shipping 

material is saved for their examination. After examining 

and removing contents, save packing material and carton 

in the event that reshipment is necessary.

2.2 Important Considerations Before Installation

  

CAUTION

THE FP7002 PADDLEWHEEL FLOW TRANSMITTER IS NOT 

EXPLOSION-PROOF, NOR IS IT INTRINSICALLY SAFE. IT 

IS NOT TO BE USED FOR FLAMMABLE OR HAZARDOUS 

LIQUIDS, NOR CAN IT BE USED IN HAZARDOUS AREAS. 

The FP7002 is intended for use with water and other low viscosity 

liquids ONLY; it can NOT be used with oils and other viscous 

FP7002/FP7002A Flow/Temperature Transmitter

1

1

Summary of Contents for FP7002

Page 1: ...FP7002 FP7002A Flow Temperature Transmitter TM e mail info omega com For latest product manuals www omegamanual info Shop online at omega com User sGuide NORWALK CT...

Page 2: ...rves the right to alter specifications without notice Servicing North America U S A Omega Engineering Inc Headquarters Toll Free 1 800 826 6342 USA Canada only Customer Service 1 800 622 2378 USA Cana...

Page 3: ...1 2 2 Important Considerations Before Installation 1 2 3 Flowmeter Installation 2 2 4 Electrical Connections 4 Section 3 Maintenance 5 Section 4 Calibration 5 4 1 Flow Calibration 5 4 2 Temperature C...

Page 4: ...SENSOR FAILURE 5 DO NOT OPERATE IN FLAMMABLE OR EXPLOSIVE ENVIRONMENTS 6 DO NOT USE IN HUMAN MEDICAL OR NUCLEAR APPLICATIONS 7 NEVER OPERATE WITH A POWER SOURCE OTHER THAN WHAT IS SPECIFIED IN THIS M...

Page 5: ...fittings are supplied with a brass locking nut to provide a secure metal to metal mounting to the threaded brass insert Section 2 Installation 2 1 Unpacking Remove the Packing List and verify that you...

Page 6: ...PPED AS WITH QUICK CLOSING AND SOLENOID OPERATED VALVES SURGES OCCUR WHEN FLOW IS SUDDENLY BEGUN AS WHEN A PUMP IS TURNED ON AT FULL POWER OR A VALVE IS QUICKLY OPENED LIQUID SURGES ARE PARTICULARLY D...

Page 7: ...FP7002 FP7002A Flow Temperature Transmitter 2 3 FLOW Figure 2 1 Horizontal Mounting Position FLOW Figure 2 2 Vertical Mounting Position...

Page 8: ...of the downstream obstruction Table 2 1 Concentric reducer 15 pipe diameters One elbow 20 pipe diameters 2 elbows in same plane 25 pipe diameters 2 elbows in two planes 40 pipe diameters or one expan...

Page 9: ...am from the FP7002 and to periodically shut down the line and remove the sensor from the installation fitting for cleaning 2 4 Electrical Connections CAUTION All electrical connections and wiring shou...

Page 10: ...on For our example we will use GPM This will be GPM Max 5 From the table on page 8 determine the proper K Factor for the model fitting you will be using 6 Determine your full scale calibration frequen...

Page 11: ...s 4 Place a reference temperature probe next to the body of the paddlewheel flow sensor with the unit removed from the flow line and lying on a work bench 5 Connect the reference probe to a thermomete...

Page 12: ...etup Figure 4 2 Temperature Calibration Setup 1 2 3 4 5 6 1 5 4 3 2 6 P2 P1 REMOVE RESISTOR AND WHITE WIRE FOR CALIBRATION TB3 TB6 TB1 TB4 4 00 mA 0 00 Hz MULTIMETER FREQUENCY GENERATOR 18 Vdc MAX PWR...

Page 13: ...FP7012 41 16 FP7012 GI 48 81 FP7015 29 46 FP7015 GI 35 52 FP7020 15 52 FP7020 GI 20 62 FP7025 11 40 FP7025 GI 12 44 FP7030 6 64 FP7030 GI 7 22 PART NUMBER K FACTOR ART NUMBER K FACTOR VISCOSITY and S...

Page 14: ...ERIALS Sensor Body Polypropylene body PVDF optional PVDF paddle Viton O ring 316SS shaft Model FP7002A includes brass locking nut Model FP7002 includes PVC locking nut MAX RECOMMENDED FLUID VISCOSITY...

Page 15: ...or otherwise shall not exceed the purchase price of the component upon which liability is based In no event shall OMEGA be liable for consequential incidental or special damages CONDITIONS Equipment...

Page 16: ...ne Paddlewheel Systems M U Totalizers Batch Controllers pH CONDUCTIVITY M U pH Electrodes Testers Accessories M U Benchtop Laboratory Meters M U Controllers Calibrators Simulators Pumps M U Industrial...

Reviews: