1. GENERAL DESCRIPTION

2

WARNING:   Never install a fuse rated more than 800mA

The DRA-RTM-8 is a multiplexer for 16 analog inputs - eight of which, marked
1-8, are direct inputs for Pt-100 sensors, while the remaining (9-16), are for 4-
20mA current loops.
The DRA-RTM-8 output format is a 4-20mA current loop, with a 28mA limitation.

Each Pt-100 input has its own signal conditioner, allowing each input to be
calibrated separately. Each signal conditioner includes six DIP switches for coarse
calibration and two potentiometers for fine tuning.

2. MOUNTING INSTRUCTIONS

The DRA-RTM-8 is designed for standard DIN rail mounting.

Place the unit on the upper part of the mounting rail with the fastening tab facing
down. Using a suitable flat screwdriver loosen the tab slightly and attach the unit
to the rail. Once the tab is loosened, ensure that the unit is fastened securely in
place.

3. REPLACING FUSES

To replace a blown fuse, disassemble the unit as follows:

a. Take off both terminal strips by removing the four screws at the edges.

Note: This does not require disconnecting the cables connected to the strips.

b. Remove the front panel using a suitable flat screwdriver. Press down gently on
    the plastic springloaded tabs located in the slots on either side of the unit.
c. Disconnect the flat connectors which connects the front panel printed circuit.
d. Replace the blown fuse.

4. ASSEMBLY

The DRA-RTM-8 unit includes two printed circuit cards designated as  P.N 7020
and  P.N 7021. The two printed circuit cards should occupy the slots in the
enclosure according to fig 1.

Summary of Contents for DRA-RTM-8

Page 1: ...DRA RTM 8 ANALOG MULTIPLEXER User sGuide http www omega com e mail info omega com...

Page 2: ...02 Certified Broughton Astley Leicestershire Irlam Manchester LE9 6TU England M44 5EX England Tel 44 1455 285520 Tel 44 161 777 6611 FAX 44 1455 283912 FAX 44 161 777 6622 Toll Free in England 0800 48...

Page 3: ...XER 7 CONNECTING Pt 100 TO THE MULTIPLEXER 8 CONNECTING THE MULTIPLEXER TO A PLC 9 CONTROL 9 1 Enable 9 2 Address 9 3 Address Polarity 9 4 Control Tables 10 CALIBRATION 10 1 Calibration Procedure 10 2...

Page 4: ...e fastening tab facing down Using a suitable flat screwdriver loosen the tab slightly and attach the unit to the rail Once the tab is loosened ensure that the unit is fastened securely in place 3 REPL...

Page 5: ...e return for all the current channels It is possible to connect any current source as long as a closed loop is maintained Figure 1 6 CONNECTING TRANSMITTERS TO THE MULTIPLEXER 6 1 TWO WIRE TRANSMITTER...

Page 6: ...e transmitter connection WARNING NEVER apply 24Vdc to the DRA RTM 8 s Io terminal as in two wire connection and make sure that the PLC s analog module is configured as a passive input 9 CONTROL The DR...

Page 7: ...1 and 1111 selects channel 16 Moving the jumper to the second alternative reverses the logic Figure 6 Note If the address contros voltages are generated from different power supplies then its negativ...

Page 8: ...temperature at which the output current is 20mA Tspan is the difference between Tmax and Tmin 10 1 CALIBRATION PROCEDURE a Remove the terminal strips to get access to the coarse calibration switches...

Page 9: ...206 205 272 270 338 336 404 401 470 1 1 1 1 1 1 1 1 1 1 1 1 0 0 0 0 0 0 0 0 0 0 0 0 CHANNELS 5 8 SW2 SW3 SW1 1 1 1 1 1 1 1 1 1 1 1 1 0 0 0 0 0 0 0 0 0 0 0 0 10 2 2 SPAN COARSE CALIBRATION TABLES SPAN...

Page 10: ...rent Input CONTROL INPUTS Logic Logic Levels OUTPUT SWITCHING TIME INDICATORS SUPPLY VOLTAGE SUPPLY CURRENT CONSUMPTION FUSE TEMPERATURE STABILITY OPERATING TEMPERATURE STORAGE TEMPERATURE HUMIDITY HO...

Page 11: ...EGA if the unit is found to be defective it will be repaired or replaced at no charge OMEGA s WARRANTY does not apply to defects resulting from any action of the purchaser including but not limited to...

Page 12: ...Paddlewheel Systems Totalizers Batch Controllers pH CONDUCTIVITY pH Electrodes Testers Accessories Benchtop Laboratory Meters Controllers Calibrators Simulators Pumps Industrial pH Conductivity Equipm...

Reviews: