DP6060 Dual-Input Process Meter
Instruction Manual
90
Reset Meter to Factory Defaults
When the parameters have been changed in a way that is difficult to
determine what’s happening, it might be better to start the setup
process from the factory defaults.
Instructions to load factory defaults:
1. Enter
the
Advanced
Features
menu. See
Advanced Features
Menu
, page 69.
2. Press Up arrow to go to
Diagnostics
menu
3. Press and hold Right arrow for three seconds, press
Enter when display flashes
reset
.
Note: If Enter is not pressed within three seconds, the display
returns to Run Mode.
4. The meter goes through an initialization sequence (similar as on
power-up), and loads the factory default settings.