Hardware Setup 

 

3.2

 

10-PIN Connector Wiring Diagrams 

The 10-pin universal input connector pin assignments are summarized in 

Table 4

.  

 

Table 4.   10-Pin Input Connector Wiring 

Pin 
No. 

Code 

Description 

ARTN 

Analog return signal (analog ground) for sensors and remote Setpoint 

AIN+ 

Analog positive input 

AIN- 

Analog negative input 

APWR  Analog power reference 

AUX 

Auxiliary analog input for remote Setpoint 

EXCT 

Excitation voltage output referenced to ISO GND 

DIN 

Digital input signal (latch reset, etc.), Positive at > 2.5V, ref. to ISO GND 

ISO 
GND 

Isolated ground for serial communications, excitation, and digital input 

RX/A 

Serial communications receive 

10 

TX/B 

Serial communications transmit 

 
Table 5 

summarizes the universal input pin assignments for different sensor inputs. All sensor selections 

are firmware-controlled and no jumper settings are required when switching from one type of sensor to 
another.  
 

Table 5

.   

Sensor Pin Assignments

 

Pin 

Diff 

Voltage 

Process 
Voltage 

Process 
Current 

2-Wire 

RTD 

3-Wire 

RTD 

4-Wire 

RTD 

Thermistor 

Remote

(1)

 

Setpoint 

1

 

Vref - 

(2)

 

Rtn 

 

(3)

 

RTD2- 

RTD2+ 

  

Rtn 

2

 

Vin + 

Vin +/- 

I+ 

RTD1+ 

RTD1+ 

RTD1+ 

TH+ 

  

3

 

Vin - 

 

I- 

  

  

RTD2- 

TH- 

  

4

 

Vref + 

(2)

 

  

  

RTD1- 

RTD1- 

RTD1- 

  

  

5

 

 

  

  

  

  

  

  

V/I In 

(1)

 Remote Setpoint cannot be used with RTD inputs. 

(2)

 Reference voltage required for Ratio-metric mode only. 

(3)

 2 Wire RTD Requires external connection of Pin 1 and Pin 4.

 

 

Figure 3

 shows the wiring diagram for connecting RTD sensors. For 2 wire RTD sensors use a jumper 

wire, included in the provided wire kit, to connect pins 1 and 4. 
 

 

Figure 3.   RTD Wiring Diagram 

 

 

 

10 

Summary of Contents for CS8DPT

Page 1: ...ervice 1 800 622 2378 USA Canada only Engineering Service 1 800 872 9436 USA Canada only Tel 203 359 1660 Fax 203 359 7700 e mail info omega com For Other Locations Visit omega com worldwide The infor...

Page 2: ...RATION AND PROGRAMMING 9 4 1 PLATINUM Series Navigation 9 4 2 Selecting an Input INIt INPt 10 4 3 Set the Setpoint 1 Value PRoG SP1 10 4 4 Set up the Control Output 11 4 4 1 Select an Output Channel P...

Page 3: ...onal safety and hazard symbols shown in the table below in accordance with 2014 35 EU Low Voltage Directive It is important to read and follow all precautions and instructions in this manual before op...

Page 4: ...the packing list it is important to verify all equipment shipped has been delivered as shown in Figure 1 and Table 1 If there are any questions about the shipment please email or call the Customer Se...

Page 5: ...Power Cord DM 230V 16A USA Canada Mexico Power Cord Molded 120V Italy Power Cord IT 230V 16A Continental Europe Power Cord E 10A 240V 10A Europe Power Cord E 16A 240V 16A 3 HARDWARE SETUP This section...

Page 6: ...l communications transmit Table 5 summarizes the universal input pin assignments for different sensor inputs All sensor selections are firmware controlled and no jumper settings are required when swit...

Page 7: ...rs R1 and R2 included in the provided Wire Kit across terminals 4 and 6 and terminals 1 and 8 respectively This allows the Bridge voltage to be measured When powering a bridge from the unit use an int...

Page 8: ...s Output 2 3 Ethernet Port RJ45 10 100Base T Optional 4 AC Main Input Plug IEC60320 C13 Power Socket 90 to 240 Vac 50 60 Hz 5 Output 1 Relay Output 90 240 VAC 3A Max 6 Output 2 SSR Output 90 240 VAC 5...

Page 9: ...es across a set of menu choices at a given level When changing numerical settings press the LEFT button to make the next digit one digit to the left active The RIGHT button moves across a set of menu...

Page 10: ...all process ranges MANL Rd 1 ____ Low display reading IN 1 ____ Manual input for Rd 1 Rd 2 ____ High display reading IN 2 ____ Manual input for Rd 2 LIVE Rd 1 ____ Low display reading IN 1 ____ Live R...

Page 11: ...ng Parameters oFF Turn off the output channel factory default PId Set the output to Proportional Integral Derivative PID Control oN oF Set the output to On Off Control Mode RtRN Set up the output for...

Page 12: ...tion ACtN parameter PRoG PID S ACtn as detailed below Setting Description RVRS Reverse Output increases the process value dRCt Direct Output decreases the process value 5 Set the Autotune Timeout A to...

Page 13: ...10 Volts factory default 0 5 0 to 5 Volts 0 20 0 to 20 mA 4 20 4 to 20 mA 0 24 0 to 24 mA 4 7 2 Set Mode to Retransmission Enable the output by setting the mode to Retransmission PRoG IAN 1 Mode RtRN...

Page 14: ...r electrical equipment for measurement control and laboratory EMC Measurement Category I Category I includes measurements performed on circuits not directly connected to the Mains Supply power Maximum...

Page 15: ...er calibration is available with adjustable gain and offset as well as ice point calibration Refer to the Platinum Series User s Manual M5451 for additional information on user calibration options Opt...

Page 16: ...ation misapplication misuse or other operating conditions outside of OMEGA s control Components in which wear is not warranted include but are not limited to contact points fuses and triacs OMEGA is p...

Reviews: