[6] tun = Autotuning 
Available:
 when o1.F = PID
ALL = the Autotuning is performed at every start up and  

parameters Pb, Ti and Td are hidden.

onE = the Autotuning is performed only at the next start up.
ub = Manual start up through 

 key (parameters Pb, Ti and 

Td are visible).

Note: When the Autotuning and the soft start, or the delay at 

the start up, have been programmed, the instrument 
performs first the soft start (with the parameters it has in 
memory) and then performs the Autotuning.

[7] Pb = Proportional band
Available:
 when o1F=PID and tun = ub.
Range: from 1 to 999 engineering units.
[8] ti = Integral time
Available:
 when o1F=PID and tun = ub.
Range: from 1 to 500 seconds and OFF (excluded).
[9] td = Derivative time
Available:
 when o1F=PID and tun = ub.
Range: from 0 (= OFF) to 200 seconds.
[10] SEn = Input type

[11] dP = Decimal point
Range:

YES = Autoranging display;
nO = display without decimal point.

[12] CA = Offset on the displayed value
Range:
 -300 to 300 engineering units.
[13] Ft = Filter on the displayed value
Range:
 from 0 (OFF) to 20 seconds.
[14] o1F = Out 1 function
Range: 
 H.rE = PID control with heating action (reverse);

C.rE = PID control with cooling action (direct);
on.H = ON/OFF control with heating action (reverse);
on.C = ON /OFF control with cooling action (direct).

[15] tr1 = Out 1 cycle time
Range:
 from 1 to 250 seconds.
[16] o2F = Out 2 function 
Range:

When o1F is equal to H.rE or C.rE:

no = Not used
HAL = Absolute high alarm;
LAL = Absolute low alarm;
b.AL = Band alarm (simmetric to the set point);
dHA = Deviation high alarm;
dLA = Deviation low alarm.

When o1F = on.H or on.C:

no = Not used;
HAL = Absolute high alarm ;
LAL = Absolute low alarm;
b.AL = Band alarm (simmetric to the set point);
dHA = Deviation high alarm ;
dLA = Deviation low alarm;
SP.C = SP2 - ON /OFF control with cooling action ;
SP.H = SP2 - ON /OFF control with heating action ;
nr = ON/OFF Neutral Zone (o2F will make the opposite 
action to the one programmed on o1F, while the hysteresis  
[par. d1] becomes the neutral zone).

Note: The Neutral Zone functioning is used to control the plants 

with an element that causes a positive increase (ex. 
Heating, Humidifying etc.) and an element that causes a 
negative increase (ex. Cooling, Dehumidifying etc.).

The control works on the programmed outputs depending on 
the measure, on the active Set point "SP", and on the 
programmed hysteresis "d1".
The regulator works in the following way: it switches off the 
outputs when the process value reaches the Set and activates 
the heating output when the process value is lower than [SP-d1],
or it switches on the cooling output when the process value is 
higher than [SP+d1].
Accordingly, the element that causes positive increase must be 
connected to the output programmed as heating, while the 
element of negative increase must be connected to output 
programmed as cooling.

Table of the possible combinations

[17] d1 = Out 1 hysteresis or neutral zone
Available:
 when Out 1 is equal to hn.H or on.C.
Range: 0.1 to 999 engineering units.
[18] d2 = Out 2 hysteresis
Available:
 when o2F is different from nr.
Range: 0.1 to 999 engineering units.

[19] AL.F = Alarm function
Available:
 when o2F is programmed as alarm output.
Range: AL = Automatic reset Alarm;

AL.n = Latched Alarm;
AL.A = Aknowledgeable Alarm.

AL = Automatic reset Alarm

AL.n = Latched Alarm

AL.A = Acknowledgeable alarm

[20] AL.t = Inhibition time of the alarm at the start up or after 
a change of set point
Range:
 from 0 = OFF (any hidding) to 9.59 HH.mms
Note: When the measure reaches the alarm threshold, the 

instrument disables the hidding of the alarm.

[21] Pct = Compressor protection time
The protection prevents the output cycling and therefore 
reduces relay wear by waiting for the time setting to elapse 
before allowing a subsequent switching of the output.
In other words, it defines the minimum time that will pass between
the switch off of a cooling output and its following reactivation.
Available: if at least one output is programmed as cooling output.
Range: from 0=OFF to 9.59 HH.mm
Note: This parameter has effect to ALL the cooling outputs.
[22] SSt = Soft start time
Range:
 0=OFF to 9.59 HH.mm.
Note: When the control is ON/OFF type, the time of the soft 

start becomes an output time delay, the power is forced 
to 0 and the parameter SSP is hidden.

[23] SSP = Power during Soft Start
Available:
 when Sst is different from 0.
Range: 0 to 100%.
Note: if programmed = 0, also the alarms and/or the second 

control output remains = 0 and the instrument visualizes 
"od" for the programmed time.

[24] ub.F = 

 key function

Range: no = No function

Tun = It activates the manual tuning;
Sb = Stand-by mode;
Sb.o = Stand-By  mode with display off.

[25] PP = Parameters protection Password
Range:
 1 to 999.
[26] Lo = Time for the Key lock automatic enable
This parameter allows to set the time that the instrument will 
wait before to automatically enable the key lock.  The time count 
will re-start after a key pressure.
Range: from OFF (lock disabled) to 30 minutes.

5.1 - OUT OF RANGE SIGNALS
The display shows the OVER-RANGE and UNDERRANGE 
conditions with the following indications:

The sensor break will be signaled as follows:

Note: When an over-range or an under-range is detected, the 

alarms operate as in presence of the maximum or the 
minimum measurable value respectively.

To check the out of span Error condition, proceed as follows:
1) Check the input signal source and the connecting line;
2) Make sure that the input signal is in accordance with the 

instrument configuration.  Otherwise, modify the input con-
figuration (see section 4).

3) If no error is detected, send the instrument to your supplier 

to be checked.

5.2 - LIST OF POSSIBLE ERRORS
AtE
 - Auto-tune not finished within 12 hours.
EPr - Possible problem of the instrument memory.
The messages disappears automatically.
When the error continues, send the instrument to your supplier.

6.1 - PROPER USE
Every possible use not described in this manual must be 
considered as a improper use.
This instrument is in compliance with EN 61010-1 "Safety 
requirements for electrical equipment for measurement, control 
and laboratory use"; for this reason it must not be used as a 
safety equipment.
Whenever a failure or a malfunction of the control device may 
cause dangerous situations for persons, thing or animals, 
please remember that the plant has to be equipped with 
additional safety devices.
OMEGA Engineering Inc. and its legal representatives do not 
assume any responsibility for any damage to people, things or 
animals deriving from violation, wrong or improper use or in any 
case not in compliance with the instrument's features.
6.2 - WARRANTY AND REPAIRS
We warrant that the products will be free from defects in material 
and workmanship for 18 months from the date of delivery.  Prod-
ucts and components that are subject to wear due to conditions 
of use, service life, and misuse are not covered by this warranty.
The warranty is limited to repairs or to the replacement of the 
instrument.
The tampering of the instrument or an improper use of the product 
will bring about the immediate withdrawal of the warranty's effects.
In the event of a faulty instrument, either within the period of war-
ranty or further to its expiry, please contact our sales department 
to obtain authorisation for sending the instrument to our company.
The faulty product must be shipped to OMEGA Engineering with a 
detailed description of the faults found, without any fees or charge 
for OMEGA Engineering, except in the event of alternative 
agreements.
Before supplying tension to the instrument, make sure that it is 
perfectly dry.

Model Selection Sensor

Measuring range

F

J .C

TC J

-40 to 999 °C

Ca.C

TC K

-40 to 999 °C

J .F

TC J

-40 to 999 °F

Ca.F

TC K

-40 to 999 °F

A

Pt.C

PT 100

-50.0 to 850 °C (autoranging)

Pt.F

PT 100

-58.0 to 999 °F (autoranging)

T

nC.C

NTC

-50.0 to 109 °C (autoranging)

PC.C

PTC

-50.0 to 150 °C (autoranging)

nC.F

NTC

-58.0 to 228 °F (autoranging)

PC.F

PTC

-58.0 to 302 °F (autoranging)

P1.C

Pt 1000 -50.0 to 850 °C (autoranging)

P1.F

Pt 1000 -58.0 to 999 °F (autoranging)

O1F

O2F

Displayed 

parameters

H.rE

H.AL, L.AL, b.AL, dHA, dLA

SP1, AL

C.rE

H.AL, L.AL, b.AL, dHA, dLA

SP1, AL

on.H

H.AL, L.AL, b.AL, dHA, dLA

SP1, AL

2

P

S

 ,

1

P

S

H

.

P

S

 ,

C

.

P

S

y

l

n

o

 

1

p

S

r

N

on.C

H.AL, L.AL, b.AL, dHA, dLA

SP1, AL

2

P

S

 ,

1

P

S

H

.

P

S

 ,

C

.

P

S

y

l

n

o

 

1

P

S

r

N

0N

O2F = nr 
(heating)

O1F = on.H 
(heating)

SP

PV

OFF

0N

OFF

time

D1
D1

OFF

OFF

0N

5. ERROR MESSAGES

Time

Measure

Meas

Alx

Alarm hysteresis

Status

ON

OFF

Time

Automatic 

reset

Automatic

Time

Measure

Meas

Alx

Alarm hysteresis

Status

ON

OFF

Time

Manual 

reset

Manual 

reset

Latched

Time

Measure

Ambient 

temp.

Alx

Alarm hysteresis

Status

ON

OFF

Time

Automatic 

reset

ACK

Acknowledgeable

Over range

Under range

Sensor break

6. GENERAL NOTES

7. PARAMETERS TABLE

no. Par.

Description

Range

Default Protec-

tion

1

SPL

Minimum Set 

Point value

From –99.9 to SPH 

E.U.

-99

Yes

2

SPH

Maximum Set 

Point value

From SPL to 999 

E.U.

999

Yes

3

SP1 

Set point 

From SPL to SPH 

E.U.

0

No

4

SP2

Second Set 

Point

From SPL to SPH 

E.U.

0

Yes

5

AL

Alarm threshold

From – 99.9 to 999 

E.U.

0

Yes

6

tun

Autotuning

ALL

 =Performed at 

every start up

onE

 =Performed at 

the first start up

ub

 = Performed 

when U key is 

pressed

onE

Yes

7

Pb

Proportional 

Band

From 1 to 999 E.U. 50

Yes

8

ti

Integral time

From 1 to 500 

seconds and OFF

100

Yes

9

td 

Derivative time

From 0 (OFF) to 

200 seconds

25

Yes

10 SEn

Input type

F type

A type

T type

JC

 = TC J (°C)

CA.C

 = TC K (°C)

JF

 = TC J (°F)

CA.F

 = TC K (°F)

Pt.C

 = PT 100 (°C)

Pt.F

 = PT 100 (°F)

nC.C

 = NTC (°C)

PC.C

 = PTC (°C)

nC.F

 = NTC (°F)

PC.F

 = PTC (°F)

P1C

 = PT 1000 (°C)

P1F

 = PT 1000 (°F)

J.C

Pt.C

nC.C

Yes

11 DP

Decimal point

YES

 = Autoranging 

visualization

no

 = Visualization 

without decimal 

point

no

Yes

12 CA

Offset on the 

displayed value

From -300 to 300 

E.U.

0

Yes

13 Ft

Filter on the 

displayed value

From 0 (OFF) to 20 

seconds

0

Yes

14 O1F

Out 1 function

H.rE

 = PID control 

with heating action

C.rE

 = PID control 

with cooling action 

on.H

 = ON/OFF 

control with 

heating action 

on.C

 = ON/OFF 

control with 

cooling  action 

HrE

Yes

15 tr1

Out 1 cycle time

From 1 to 250 

seconds

30

Yes

no. Par.

Description

Range

Default Protec-

tion

16 o2F

Out 2 function 

When o1F = H.rE 

or C.rE

When o1F = on.H 

or on.C

no

 = Not used

HAL

 = Absolute 

high alarm 

LAL

 = Absolute low 

alarm

b.AL

 = Band alarm 

(simmetric to the 

set point)

dHA

 = Deviation 

high alarm 

dLA

 = Deviation 

low alarm

no

 = Not used

HAL

 = Absolute 

high alarm 

LAL

 = Absolute low 

alarm

b.AL

 = Band alarm 

(simmetric to the 

set point)

dHA

 = Deviation 

high alarm 

dLA

 = Deviation 

low alarm

SP.C

 = SP2 

ON /OFFcontrol 

with cooling action 

SP.H

 = SP2

 ON /OFF control 

with heating action 

nr

 = ON/OFF  

neutral zone 

No

Yes

17 d1

Out 1 hysteresis 

or neutral zone 

From 0.1 to 999 

E.U.

1

Yes

18 d2

Out 2 hysteresis

From 0.1 to 999 

E.U.

1

Yes

19 ALF

Alarm function

AL

 = Automatic 

reset Alarm

AL.n

 = Latched 

Alarm

AL.A

 = 

Aknowledgeable 

Alarm

AL

Yes

20 ALt

Inhibition time 

of the alarm at 

the start up or 

after a change of 

set point  

From 0 (OFF) to 

9.59 HH.mm

0

Yes

21 Pct

Compressor 

protection time

From 0 (OFF) to 

9.59 HH.mm

0

Yes

22 Sst

Soft start time

From 0 (OFF) to 

9.59 HH.mm

0

Yes

23 SSP

Power during 

Soft Start

From 0 to 100%

0

Yes

24 UbF

 key 

function

no

 = No function

Tun

 = It activates 

the manual tuning 

Sb

 = Stand-by 

mode

Sb.o

 = Stand-By  

mode with display 

off

tun

Yes

25 PP

Parameters 

protection 

Password 

From 1 to 999

0

Yes

26 Lo

Key lock time 

out

From 0 (key lock 

disabled) to 30 

minutes

0

Yes

TEMPERATURE

   

Thermocouple, RTD & Thermistor 

Probes, Connectors, Panels & 

Assemblies

   

Wire: Thermocouple, RTD & 

Thermistor

  

Calibrators & Ice Point References

   

Recorders, Controllers & Process 

Monitors

  

Infrared Pyrometers

PRESSURE, STRAIN 

AND FORCE

  

Transducers & Strain Gages

  

Load Cells & Pressure Gages

  

Displacement Transducers

  

Instrumentation & Accessories

FLOW/LEVEL

   

Rotameters, Gas Mass Flowmeters 

& Flow Computers

  

Air Velocity Indicators

  

Turbine/Paddlewheel Systems

  

Totalizers & Batch Controllers

pH/CONDUCTIVITY

  

pH Electrodes, Testers & Accessories

  

Benchtop/Laboratory Meters

   

Controllers, Calibrators, Simulators 

& Pumps

   

Industrial pH & Conductivity Equipment

DATA ACQUISITION

   

Data Acquisition & 

Engineering Software

   

Communications-Based 

Acquisition Systems

   

Plug-in Cards for Apple, IBM 

& Compatibles

  

Data Logging Systems

  

Recorders, Printers & Plotters

HEATERS

  

Heating Cable

  

Cartridge & Strip Heaters

  

Immersion & Band Heaters

  

Flexible Heaters

  

Laboratory Heaters

ENVIRONMENTAL

MONITORING AND 

CONTROL

   

Metering & Control Instrumentation

  

Refractometers

  

Pumps & Tubing

  

Air, Soil & Water Monitors

   

Industrial Water & Wastewater 

Treatment

   

pH, Conductivity & Dissolved 

Oxygen Instruments

Where Do I Find Everything I Need for

 

Process Measurement and Control?

 

OMEGA…Of Course!

Shop online at omega.com

 sm

It is the policy of OMEGA Engineering, Inc. to comply with all worldwide safety and

EMC/EMI regulations that apply. OMEGA is constantly pursuing certification of its

products to the European New Approach Directives. OMEGA will add the CE mark to

every appropriate device upon certification.

The information contained in this document is believed to be correct, but OMEGA 

accepts no liability for any errors it contains, and reserves the right to alter 

specifications without notice. WARNING: These products are not designed for use 

in, and should not be used for, human applications. 

RETURN REQUESTS/INQUIRIES

Direct  all  warranty  and  repair  requests/inquiries  to  the  OMEGA  Customer 

Service  Department.  BEFORE  RETURNING  ANY  PRODUCT(S)  TO  OMEGA, 

PURCHASER  MUST  OBTAIN  AN  AUTHORIZED  RETURN  (AR)  NUMBER 

FROM  OMEGA’S  CUSTOMER  SERVICE  DEPARTMENT  (IN  ORDER  TO 

AVOID  PROCESSING  DELAYS).  The  assigned  AR  number  should  then  be 

marked on the outside of the return package and on any correspondence.

The  purchaser  is  responsible  for  shipping  charges,  freight,  insurance  and 

proper packaging to prevent breakage in transit.  

FOR WARRANTY RETURNS, please 

have the following information 

available BEFORE contacting 

OMEGA:
1.  Purchase Order number 

under which the product was 

PURCHASED,

2.  Model and serial number of the 

product under warranty, and

3.  Repair instructions and/or specific 

problems relative to the product.

FOR NON-WARRANTY REPAIRS, 

consult OMEGA for current repair 

charges. Have the following 

information available BEFORE 

contacting OMEGA:
1.             Purchase Order number to cover 

the COST of the repair,

2.  Model and serial number of the 

product, and

3.  Repair instructions and/or specific 

problems relative to the product.

OMEGA’s  policy  is  to  make  running  changes,  not  model  changes,  whenever  an 

improvement is possible. This affords our customers the latest in technology and 

engineering.
OMEGA is a registered trademark of OMEGA ENGINEERING, INC.
© Copyright 2014 OMEGA ENGINEERING, INC. All rights reserved. This document 

may  not  be  copied,  photocopied,  reproduced,  translated,  or  reduced  to  any 

electronic  medium  or  machine-readable  form,  in  whole  or  in  part,  without  the 

prior written consent of OMEGA ENGINEERING, INC.

WARRANTY/DISCLAIMER

OMEGA ENGINEERING, INC. warrants this unit to be free of defects in materials 

and workmanship for a period of 

13 months

 from date of purchase. OMEGA’s 

WARRANTY adds an additional one (1) month grace period to the normal 

one 

(1) year product warranty

 to cover handling and shipping time. This ensures 

that OMEGA’s customers receive maximum coverage on each product. 

If  the  unit  malfunctions,  it  must  be  returned  to  the  factory  for  evaluation. 

OMEGA’s Customer Service Department will issue an Authorized Return (AR) 

number  immediately  upon  phone  or  written  request.  Upon  examination  by 

OMEGA, if the unit is found to be defective, it will be repaired or replaced at 

no charge. OMEGA’s WARRANTY does not apply to defects resulting from any 

action  of  the  purchaser,  including  but  not  limited  to  mishandling,  improper 

interfacing, operation outside of design limits, improper repair, or unauthorized 

modification.  This  WARRANTY  is  VOID  if  the  unit  shows  evidence  of  having 

been tampered with or shows evidence of having been damaged as a result of 

excessive corrosion; or current, heat, moisture or vibration; improper specifica-

tion; misapplication; misuse or other operating conditions outside of OMEGA’s 

control. Components in which wear is not warranted, include but are not limited 

to contact points, fuses, and triacs.

OMEGA  is  pleased  to  offer  suggestions  on  the  use  of  its  various 

products.  However,  OMEGA  neither  assumes  responsibility  for 

any  omissions  or  errors  nor  assumes  liability  for  any  damages  that 

result  from  the  use  of  its  products  in  accordance  with  information 

provided by OMEGA, either verbal or written. OMEGA warrants only 

that  the  parts  manufactured  by  the  company  will  be  as  specified 

and  free  of  defects.  OMEGA  MAKES  NO  OTHER  WARRANTIES  OR 

REPRESENTATIONS  OF  ANY  KIND  WHATSOEVER,  EXPRESSED  OR 

IMPLIED,  EXCEPT  THAT  OF  TITLE,  AND  ALL  IMPLIED  WARRANTIES 

INCLUDING  ANY  WARRANTY  OF  MERCHANTABILITY  AND 

FITNESS  FOR  A  PARTICULAR  PURPOSE  ARE  HEREBY  DISCLAIMED. 

LIMITATION  OF  LIABILITY:  The  remedies  of  purchaser  set  forth 

herein  are  exclusive,  and  the  total  liability  of  OMEGA  with  respect 

to  this  order,  whether  based  on  contract,  warranty,  negligence, 

indemnification,  strict  liability  or  otherwise,  shall  not  exceed  the 

purchase price of the component upon which liability is based. In no 

event  shall  OMEGA  be  liable  for  consequential,  incidental  or  special 

damages.

CONDITIONS:  Equipment sold by OMEGA is not intended to be used, nor shall 

it be used: (1) as a “Basic Component” under 10 CFR 21 (NRC), used in or with 

any nuclear  installation  or  activity;  or  (2)  in  medical  applications  or  used  on 

humans. Should any Product(s) be used in or with any nuclear installation or 

activity, medical application, used on humans, or misused in any way, OMEGA 

assumes no responsibility as set forth in our basic WARRANTY/ DISCLAIMER 

language, and, additionally, purchaser will indemnify OMEGA and hold OMEGA 

harmless from any liability or damage whatsoever arising out of the use of the 

Product(s) in such a manner.

 

The information contained in this document is believed to be correct, but OMEGA accepts no

liability for any errors it contains, and reserves the right to alter specifications without notice.

Servicing North America:

U.S.A.:

 

Omega Engineering, Inc., One Omega Drive, P.O. Box 4047

  

Stamford, CT 06907-0047 US

A

Toll-Free: 1-800-826-6342 (USA & Canada only)

Customer Service: 1-800-622-2378 (USA & Canada only)

Engineering Service: 1-800-872-9436 (USA & Canada only)

Tel: (203) 359-1660   Fax: (203) 359-7700

e-mail: [email protected]

For Other Locations Visit omega.com/worldwide

omega.com   [email protected]

Reviews: