3
EVENT inputs/ CT function (optional) 1
0: None, 1: Event Input3, 2: RS-485 Communication
EVENT inputs/ CT function (optional) 2
0: None, 1: Event Input2, 2: CT measure input2.
EVENT inputs/ CT function (optional) 3
0: None, 1: Event Input1, 2: CT measure input1.
Specifications
Input Voltage
80 ~ 260Vac 50/60Hz; 24Vac 50/60Hz ±10%; 24 Vdc ±10%
Power Consumption
8VA max.
Display Method
LCD display. Process value (PV): Yellow color, Set point (SV): Green color
Sensor Type
Thermocouple: K, J, T, E, N, R, S, B, L, U, TXK
(Thermal couple measuring location are not intended to be directly connected to the MAINS supply.)
3-wire Platinum RTD: Pt100, JPt100
Resistance: Cu50, Ni120
Analog input: 0 ~ 5Vdc, 0 ~ 10Vdc, 0 ~ 20mA, 4 ~ 20mA, 0 ~ 50mVdc
Control Mode
PID, PID program control (Ramp/Soak control), FUZZY, Self-tuning, Manual and On/FF
Control Output
Relay output: Max. load 250Vac, 5A resistive load
Voltage pulse output: 12Vdc, Max. output current 40mA
Current output: DC 4 ~ 20m A output (Load resistance: Max. 500Ω)
Analog voltage output: 0 ~ 10Vdc
Alarm Output Type
Relay output: Max. load 250Vac, 3A resistive load
Display Accuracy
0 or 1 digit to the right of the decimal point (selectable)
Sampling Rate
Analog input: 0.1 sec/ per scan; Thermocouple or Platinum RTD: 0.1 sec/per scan
Vibration Resistance
10 to 55Hz, 10m/s
2
for 10min, each in X, Y and Z directions
Shock Resistance
Max. 300m/ s
2
, 3 times in each 3 axes, 6 directions
Ambient Temperature
0°C ~ +50°C
Storage Temperature
-20°C ~ +65°C
Altitude
Max. 2000m
Relative Humidity
35% ~ 80% RH
(
non-condensing
)
Operation
There are three modes of operation: operation, regulation and initial setting. When power is applied, controller gets into the operation
mode. Press the
key to switch to regulation mode. If the
key is pressed for more than 3 seconds, controller will switch to the
initial setting mode. Pressing the
key while in the regulation mode or initial setting mode, forces the controller to return to the
operation mode..
PV/SV: Sets the temperature set point and displays the temperature process value. Use
keys to set the temperature set
point.
Setting method: While in any function mode, press the
key to select the desired function and use
keys to change
settings. Press
key to save the changes.
The flow chart below shows how to switch the settings and internal functions:
Regulation Mode
Operation Mode
Initial Setting Mode
Press key less than 3 sec
Press key
Press key more than 3 sec
Press key
【
Operation
Mode
】
Parameter Setting:
Display
Description
Factory Setting
Use
to set temperature set point, use
to switch between the display parameter
RUN/STOP: Control setting RUN or STOP
RUN
PATTERN: Start pattern setting (set control mode to PROG mode)
0
STEP: Start step setting (set control mode to PROG mode)
0
SELECT POINT: Decimal point setting (0: integral ; 1: one decimal point)
1
LOCK: Setting lock mode (LOCK1: all; LOCK2: onlySV and F1/F2 key is allowed)
OFF
ALARM1 HIGH: Upper limit alarm 1 (display according to the setting in ALARM mode)
4.0
ALARM1 LOW: Lower limit alarm 1 (display according to the setting in ALARM mode)
4.0