14
OMEGA ENGINEERING, INC.
Output Control
The OMA-D560 includes a straightforward output controller that enables you to
activate or reset equipment remotely on demand or automatically in response to
input set-points or alarm conditions.
Configuring an Output
Each output has several parameters that define how and when they will activate. To check or modify these
parameters, type OUT S and select an output.
COMMAND>OUT S
SET/CHECK OUTPUT SETTINGS
--------- ------ --------
1 = Out #1 #1 Relay
2 = Out #2 #2 Relay
3 = Out #3 #3 Relay
4 = Out #4 #4 Relay
0 = Previous Menu
Choose a Number>1
Out #1
PRESENT SETTINGS
------- --------
1 = Label #1 Relay
2 = On Time per Minute 60 Sec
3 = Control Mode 1
4 = Pulse Width 4 Sec
5 = Power-up State Off
6 = Alarm Mask FF
0 = Previous Menu
Choose a Number>
Label
A label is a short descriptive name that you assign to each output. By typing =HIDE=, you are able to remove
an output from all reports (although it will continue to operate). To bring the input "out of hiding," simply enter
a new label for that output.
On Time per Minute
This parameter is used to 'throttle' an output (rather than have it constantly on or off). If an output has been
turned on, and this parameter is set for 40, then the output will cycle on for 40 seconds and off for 20 seconds
(ad infinitum). If the parameter is set for 60, the output remains on constantly. The minimum value is one. The
default value is 60 seconds. This feature is useful when controlling heaters and chemical feed pumps.