CORRECTION FACTORS
To calculate the correct capacity of a given dryer based on actual operating conditions, multiply the nominal
inlet flow by the appropriate correction factor(s). CORRECTED CAPACITY = NOMINAL FLOW CAPACITY x C
OP
x
C
AT
x C
IN
x C
DP
OPERATING PRESSURE
DEW POINT
[bar]
4
5
6
7
8
10
12
14
°C
3
5
7
10
[psi]
58
72
87
100
115
145
174
203
°F
37,4
41
44,6
50
C
OP
0,77 0,86 0,93
1
1,05 1,14 1,21 1,27
C
DP
1
1,099 1,209 1,385
INLET TEMPERATURE
AMBIENT TEMPERATURE
°C
≤25
30
35
40
45
50
55
°C
≤25
30
35
40
45
°F
77
86
95
104
113
122 131
°F
77
86
95
104
113
C
IN
1,2 1,12
1
0,83 0,69 0,59 0,5
C
AT
1
0,96 0,9 0,82 0,72