background image

 

 

Siemens V20_EN_rev01-08032019.docx 

 

0-2 

 

10.1

 

DISPLAY PARAMETERS ............................................................................................................. 10-9

 

10.2

 

INVERTER COMMISSIONING..................................................................................................... 10-9

 

10.3

 

PARAMETER LIST ....................................................................................................................... 10-9

 

10.4

 

CONFIGURATION PARAMETERS .............................................................................................. 10-9

 

10.4.1

 

Upwards ................................................................................................................................ 10-9

 

10.4.2

 

Power limitation................................................................................................................... 10-10

 

10.4.3

 

Downward ........................................................................................................................... 10-11

 

10.5

 

RUPTURE VALVE TEST ............................................................................................................ 10-11

 

11

 

ACTIVE FAULTS & ALERT ............................................................................................................ 11-11

 

11.1

 

FAULT CODES ........................................................................................................................... 11-12

 

11.2

 

ALERT CODES .......................................................................................................................... 11-13

 

12

 

CHECKS AND MAINTENANCE ....................................................................................................... 12-1

 

12.1

 

MEGGER TEST ............................................................................................................................ 12-1

 

 

 

 

 

 

Summary of Contents for SIEMENS SINAMICS V20

Page 1: ...Siemens V20_EN_rev01 08032019 docx 0 0 0 INVERTER SIEMENS V20...

Page 2: ...6 1 6 4 TECHNICAL DATA 6 1 7 POWER WIRING 7 3 7 1 POWER CIRCUIT CONNECTION 7 3 7 2 SAFETY INSTRUCTIONS 7 3 7 3 RULES FOR EMC COMPLIANT MOTOR INVERTER WIRING 7 3 7 4 SIEMENS V20 ELECTRICAL WIRING 7 5...

Page 3: ...10 9 10 3 PARAMETER LIST 10 9 10 4 CONFIGURATION PARAMETERS 10 9 10 4 1 Upwards 10 9 10 4 2 Power limitation 10 10 10 4 3 Downward 10 11 10 5 RUPTURE VALVE TEST 10 11 11 ACTIVE FAULTS ALERT 11 11 11...

Page 4: ...starting current peaks The maximum starting current is the rated current In Power factor correction Cos 0 98 Power saving Comfort optimization Setting parameters of high low speed Maximum power absor...

Page 5: ...on the equipment disconnect the power supply and wait a few minutes for the internal capacitors to discharge 4 The inverter must always be connected to the mains In case of an interruption wait at lea...

Page 6: ...otors The inverters are available in many frame sizes Component Rated output power Rated in put current Rated out put num ber Order number Filtered Frame size C with single fan 2 2 kW 27 2 A 11 A 6SL3...

Page 7: ...Siemens V20_EN_rev01 08032019 docx 3 2 3 1 3 Terminal description Terminal layout...

Page 8: ...Siemens V20_EN_rev01 08032019 docx 3 3 3 1 4 Dimension drawings Frame size C...

Page 9: ...shielded Shielded EMC compliant RE CE C2 1 Unshielded Shielded EMC compliant RE CE C2 2 Da FSB a FSC 50 m 25 m 25 m 200 m 200 m 5 m 1 For filtered variants only RE CE C2 refers to EMC compliance to EN...

Page 10: ...t In Peak current Imax Overload MAX A A 3AC 13 6 20 4 150 In x 60s 24 5 In x 240s Rated pulse frequency kHz 4 Power loss kW 0 114 24 VDC supply A 50 mA Fuses Rated current 3NA 3820 50A Connectors Line...

Page 11: ...the below shown additional requisites are respected Connection by use of a shielded cable at reduced capacity Motor cable shorter than 25 m Pulse frequency 4 kHz Current nominal input current in the...

Page 12: ...d the devices within the control cabinet have to be assigned to these zones following the rules below The different zones must be electromagnetically decoupled by using separate metallic housings or g...

Page 13: ...rter handle only the upward travel in consequence of that there are not cur rents generated and MUST NOT BE INSTALLED ANY BRAKING RESISTOR The downward direction is regulated by hydraulic valve To adj...

Page 14: ...ctions can be made 6 4 TECHNICAL DATA Following there are the technical data related to the user interface terminals No Terminal marking Description 1 10V 10V output tolerance 5 referred to 0V maximum...

Page 15: ...lity No Response time 4 ms 4 ms Pulse train input No 13 24V 24 V output tolerance 15 to 20 referred to 0 V maximum 50 mA non isolated 14 0V Overall reference potential for digital inputs Digital outpu...

Page 16: ...tem 2 The power cables for the inverter contactors and contactors motor connection must be as short as possible shielded four core three phases plus yellow green earth wire or four unshielded cables b...

Page 17: ...to the power cable even if shielded if parallel routing cannot be avoided they must be in sepa rate metal raceways 8 All earth connections must be as short and wide as possible 9 To avoid unwanted tri...

Page 18: ...ermissible I O terminal cable cross sections Cable type Permissible cable cross section Solid or stranded cable 0 5 to 1 5 mm2 Ferrule with insulating sleeve 0 5 mm2 1 Use shielded screw for analog in...

Page 19: ...parameters between the inverter and a standard MMC SD card Powering the inverter from the Parameter Loader when mains power is not available 9 2 THE BUILT IN BASIC OPERATOR PANEL BOP The Basic Operato...

Page 20: ...xt digit Clears faults Long press 2 s Quick parameter number or value edit M OK Hand Jog Auto Press to switch between different modes Note Jog mode is only available if the motor is stopped and it is...

Page 21: ...ection mode Motor rotates in the reversed direction Inverter is in HAND mode flashing Inverter is in JOG mode 9 2 1 Inverter menu Menu Description 50 60 Hz selection menu This menu is visible only on...

Page 22: ...es or val ues To increase or decrease the parameter number index or value press or for less than two seconds To quickly increase or decrease the parameter number index or value press or for longer tha...

Page 23: ...he existing leftmost digit above 9 to add more digits to the left Pressing or for over two seconds enters fast digit scrolling Example 1 Editing parameter numbers Example 2 Editing parameter indices I...

Page 24: ...g mode the LED flashes green at 0 5 Hz 9 3 QUICK COMMISSIONING 9 3 1 Quick commissioning through the Setup menu Structure of the setup menu The setup menu guides you through the steps required for qui...

Page 25: ...ond with the wiring of the motor star delta MOT V P0305 0 1 Rated motor current A Note that the input of rating plate data must correspond with the wiring of the motor star delta MOT A P0307 0 1 Rated...

Page 26: ...o accept the parameter settings from both the currently and the previously selected macros which may lead to undefined and unexplainable operation Funzionalit This menu defines certain common applicat...

Page 27: ...le edit High speed Low speed Speed of releveling Acceleration deceleration ramps Power limitation ATTENTION Only in case of change of the inverter or of the electric motor you must do motor recognitio...

Page 28: ...eters PARAMETER CABIN DEPARTURE WITH TEARING CABIN STARTING LATE CABIN SPEEDS UP TOO FAST P1120 increase the value of the parameter decrease the value of the parameter parameter has no effect Setting...

Page 29: ...BOP see below In general facing to a non compliance detected the inverter behaves as follows Errors Type A Alarm are minor errors that in principle have no influence on the behavior of the inverter LI...

Page 30: ...in regenerative mode r0949 0 Hardware reported r0949 1 or 2 Software reported Check the following Supply voltage P0210 must lie within limits indicated on rating plate Ramp down time P1121 must match...

Page 31: ...eck the following r0949 0 is the motor connected to the inverter r0949 1 49 are the motor data in P0304 P0311 correct Check what type of motor wiring is re quired star delta F80 AI lost input sig nal...

Page 32: ...y reduction de pending on parameterization in P0290 r0037 1 Chip junction temperature includes heat sink Check the following Ambient temperature must lie within specified limits Load conditions and lo...

Page 33: ...ntrol circuit board if possible by blowing with compressed air or using a vacuum cleaner 2 Make sure no screws are loose in the power or control terminal blocks 3 Make sure inverter operation is norma...

Page 34: ...OMARLIFT s r l Via F lli Kennedy 22 D 24060 Bagnatica BG ITALY Phone 39 035 689611 Fax 39 035 689671 Email info omarlift eu Web http www omarlift eu...

Reviews: