Siemens V20_EN_rev01-08032019.docx
11-12
If the fault has not been cleared and the button is pressed, the faults screen displays again.
If there is no key press for 60 seconds.
If a fault is active and there has been no key press for 60 seconds, the backlight (P0070) flashes.
11.1
FAULT CODES
Fault
Cause
Remedy
F1
Overcurrent
Motor power (P0307) does not corre-
spond to the inverter power (r0206).
Motor lead short circuit
Earth faults
r0949 = 0: Hardware reported
r0949 = 1: Software reported
r0949 = 22: Hardware reported
Check the following:
Motor power (P0307) must correspond to
inverter power (r0206).
Cable length limits must not be exceed-
ed.
Motor cable and motor must have no
shortcircuits or earth faults.
Motor parameters must match the motor
in use.
Value of stator resistance (P0350) must
be
correct.
Motor must not be obstructed or over-
loaded.
Increase ramp-up time (P1120)
Reduce starting boost level (P1312)
F2
Overvoltage
Main supply voltage too high
Motor is in regenerative mode
r0949 = 0: Hardware reported
r0949 = 1 or 2: Software reported
Check the following:
Supply voltage (P0210) must lie within
limits
indicated on rating plate.
Ramp-down time (P1121) must match
inertia of load.
Required braking power must lie within
specified limits.
Vdc controller must be enabled (P1240)
and
parameterized properly.
Note
:
Regenerative mode can be caused by fast
ramp downs or if the motor is driven by an
active load.
Higher inertia requires longer ramp times;
otherwise, apply braking resistor.
F3
Undervoltage
Main supply failed.
Shock load outside specified limits.
r0949 = 0: Hardware reported
r0949 = 1 or 2: Software reported
Check supply voltage.
F4
Inverter overtem-
perature
Inverter overloaded
Ventilation inadequate
Pulse frequency too high
Ambient temperature too high
Fan inoperative
Check the following:
Load or load cycle too high?
Motor power (P0307) must match invert-
er power (r0206)
Pulse frequency must be set to default
value
Ambient temperature too high?
Fan must turn when inverter is running
F5
Inverter I
2
t
Inverter overloaded.
Load cycle too demanding.
Check the following:
Load cycle must lie within specified limits.