INSTALLATION INSTRUCTIONS
1. In order to remove the front cover, unscrew the 4 retaining screws
.
2.
Mark the
4 points
in the installation area
.
After installing the plastic plugs in the wall mount
the luminaire with the mounting screws
.
3. Make sure that the battery’s cables are connected to the respective poles. Black cable to (-)
pole and red cable to (+) pole.
4.
Always use in any case round mains cable
,
with diameter
of
6-9
mm (H05RN-F
type 3x1mm²
or
any
other type
,
at least
equal
to it’s mechanical and electrical
properties).
ATTENTION!! The cable must not be deformed in any way (This requirement is
important to ensure the tightness isolation IP 65).
Install
the cable gland
,
pass the round
cable through
and tighten it all the way.
5.
Connect the wires to the terminal blocks
L for live wire,
Ν
for
neutral
and
for the
ground
.
6.
Battery protection fuses
.
When the spot lights
are not functional in emergency mode, check
these fuses and replace them if necessary
(
one fuse corresponds to each spot light)
.
7.
Refit with care the front cover, by fastening the 4 retaining screws (tightening torque 1Nm)
.
mains’ power
supply cable
entry
4
TEST button
and
charge indication
retaining
screws
front cover
1
1
Minimum distance from lighted objects.
Front cover retaining screw
Mettalic
washer
Rubber
washer
Mounting screw