 BS-634, BS-636

 4 and 6 zone Fire Detection Panels

921636000_09_023

Thank you for purchasing this product of Olympia Electronics. A European manufacturer.

GENERAL

The family of  fire detection panels consist of  2 types( 4  and  6 zone) with identical operation and indications. The  panels have 
2    independent  siren  outputs, Alarm  relay,  Programmable  output  for  telephone  operators  and  a  relay  per  zone  . The  required 
battery for the panels  is the type  Α-986 (12V/7Ah). All functions and indications  are  according  to  European  Norms  ΕΝ 54-2 
and EN 54-4.

Top cover 
retaining screws

Control Keyboard and 
indication leds

Mounting holes

Battery compartment 
Α-986

 MODE selection 
    microswitch

Relay  per  zone 
connection  terminals

Zone connection terminal

General output connection 

(Sirens,

relay alarm,24V)

P

+

A

_

A

Operation adjustment
        of zone relay

Mains voltage connection 
terminal block (220-240V AC)

Figure 1. 

Schematic diagram of the panel

                

Mounting hole

Extra earth 
terminals

Page 1 from 9

High Quality European based Manufacturers

Summary of Contents for BS-634

Page 1: ...ired battery for the panels is the type 986 12V 7Ah All functions and indications are according to European Norms 54 2 and EN 54 4 Top cover retaining screws Control Keyboard and indication leds Mount...

Page 2: ...ss level 1 has all the functions that can be done directly from the user without using a code These operations are Buzzer silence Buzzer reactivation If an alarm of fault condition is issued then the...

Page 3: ...inute The default setting of this relay is set to be activated from a general alarm and immediately with no delay In this programming mode if the keys 1 and 2 are pressed we can toggle the LEDs ON or...

Page 4: ...ross section cable of 1 5mm Page 4 from 9 Figure 2 Connecting 4 detector bases to zone 1 Each base can accept BS 655 BS 660 or BS 667 detectors A remote indication LED BS 572 is connected to one of th...

Page 5: ...lt condition issued by the panel If it is required that this output be activated by an alarm condition then we must set the MODE switch 2 to the ON position To meet the requirements paragraph 8 8 of E...

Page 6: ...power on During installation use grounded antistatic wrist band to protect this equiment form ESD The panel must be installed permanetly It is not allowed to connect the device directly to any socket...

Page 7: ...wer Zone disable and General disable LEDs blink If an alarm is manually given by either activating a BS 536 call point or by activating a smoke detector with smoke or simulated smoke particles the cor...

Page 8: ...d from VdS Also VdS controls the production under CPD number Page 8 from 9 BS 636 6 zone fire detection panel KOLINDROS PIERIAS GREECE Provided options Output to fire alarm device s 0786 CPD 21016 10...

Page 9: ...put is protected with a self reseting electronic fuse Output 24M One Aux relay and each Under no circumstances should voltages or currents outside limits be connected All relays output must be protect...