background image

7

240011511 REV. C [05/31/2017]

Chart 1- United Technologies 1158-120 (LRF)

Dip Switch Position

Blower Delay Times

1

2

3

4

On Seconds

Off Minutes

Off

Off

30

On

Off

60

Off

On

90

On

On

120

Off

Off

2

On

Off

3

Off

On

4

On

On

6

13b.  Fan Timer Board And Limit Control (LRFV) 

[See Figure 3, page 14]

United Technologies 1168-1 ECM tap board has adjustable fan on/

off delay and airflow settings that must be adjusted in accordance 

with furnace input rating (nozzle size).  Refer to Table A-10 for 

ECM blower set-up.

14.  Electrical Connections

•  Furnace is listed by Canadian Standards Association under 

NRTL (North American) Standard. 

• 

All field wiring shall conform to CAN/CSA C22.1 Canadian 

Electrical Code, Part 1, and by local codes, where they 

prevail.

•  United States, wiring shall conform to National Fire 

Protection Association NFPA-70, National Electrical Code, and 

with local codes and regulations.

•  Wire furnace to separate dedicated circuit in main electrical 

panel.

•  Suitably located circuit breaker can be used as service 

switch, separate service switch is advisable. 

•  Service switch is necessary if circuit breaker is close to the 

furnace, or furnace is located between circuit breaker and 

entry to furnace room. 

•  Clearly mark service switch. Install in accessible area 

between furnace and furnace room entry.  Locate so as 

to reduce possibility it can be mistaken as light switch or 

similar device.

•  Power requirement for all LRF models is: 120 VAC, 1 Ø, 60 

Hz., 12A.

•  Accessory equipment such as electronic air cleaners and 

humidifiers may be included on furnace circuit. 

•  Limit control is thermally operated and automatically 

resets. Limit control is factory installed, pre-set and is not 

adjustable.

•  If limit control opens with United Technologies 1158-120 

electronic fan control, circulating fan will energize. When 

limit closes, fan off timer begins. At the end of fan off time 

cycle burner is energized, initiating normal burner cycle.

•  Accessories requiring 120 VAC power sources such as 

electronic air cleaners and humidifier transformers may be 

powered from electronic

 

fan timer board where provisions 

have been made for connections, but should have their own 

controls.

•  Do not use direct drive motor connections as a power 

source, there is risk of damaging accessories. 

•  Thermostat wiring connections are shown in wiring 

diagrams in Appendix B. Some micro-electronic thermostats 

require additional controls and wiring. Refer to thermostat 

manufacturer's instructions.

•  ECM Blower note

 - Single stage cooling use terminal Y/Y2.  

Two stage cooling use terminal Y1 for first stage and Y/Y2 

for second stage.  When Y1 is energized, air flow is reduced 

by 20%.  Do not use terminal Y1 with single stage cooling or 

heat pump.

• 

Locate thermostat approximately 5 feet above floor, on 

inside wall, and where thermostat is exposed to average 

room temperatures. Avoid locations where thermostat 

is exposed to cold drafts, heat from nearby lamps and 

appliances, exposure to sunlight, heat from inside wall 

stacks, etc.

•  Adjust thermostat heat anticipator to amperage draw of 

heating control circuit as measured at "R" and "W" terminals 

of thermostat. Do not measure current with thermostat 

connected to the circuit. Measure amperage by connecting 

ammeter between two wires which connect to thermostat 

"R" and "W" terminals.

15.  Humidifier

• 

Humidifier is optional accessory available through most 

heating supplies outlets. 

• 

Follow humidifier manufacturer's installation instructions

•  Protect furnace heat exchanger from water or water droplets 

from humidifier.

•  Do not use direct drive motor connections as source of 

power for 120 VAC humidifiers and humidifier transformers.

16.  Piping Installation

•  Install fuel system in accordance with requirements of CAN/

CSA B-139, and local regulations. 

•  United States installation shall conform to NFPA No. 31 and 

local codes and authorities.

• 

Use only approved fuel oil tanks, piping, fittings and oil filter.

• 

Install oil filter as close to burner as possible. 

•  Refer to instructions and illustrations in oil burner and oil 

pump instructions shipped with the furnace.

17.  Oil Filter

Install oil filter between fuel oil storage tank and oil burner. When 

using oil burner nozzle smaller than 0.65 U.S. Gallons Per Hour, 

install additional 7 to 10 micron filter as close as possible to oil 

burner.

Summary of Contents for LRF100

Page 1: ...RFV Lowboy Rear Flue Model with ECM Blower Oil Fired Warm Air Furnaces P N 240011511 Rev C 05 31 2017 ECR International 2210 Dwyer Avenue Utica NY 13501 web site www ecrinternational com INSTALLATION...

Page 2: ...Weight Width A Length B Height C Supply D x E Return F x G Diameter Height H LRF LRFV 22 53 33 8 20 x 18 20 x 18 8 5 29 20 x 20 x 1 240 LB 55 8 cm 135 9 cm 85 4 cm 52 1 cm x 45 7cm 52 1 cm x 47 3cm 1...

Page 3: ...ifier 7 16 Piping Installation 7 17 Oil Filter 7 18 Oil Burner Nozzles 8 19 Oil Burner Adjustment 8 20 Burner Electrodes 8 21 Burner Primary Safety Control 8 22a Circulating Air Blower LRF LRFV 8 22b...

Page 4: ...stitute of Canada HRAI or by other means prescribed or approved by the local authority having jurisdiction United States Manual J titled Load Calculation published by the Air Conditioning Contractors...

Page 5: ...furnace in parallel with or upstream from evaporator coil to avoid condensation in heat exchanger When installed in parallel prevent chilled air from entering furnace by use of dampers or other air c...

Page 6: ...oint for most of furnace electrical components United Technologies 1158 120 has an adjustable fan on time set by selecting dipswitch combination displayed in Chart 1 Fan on delay can be set at 30 60 9...

Page 7: ...rom electronic fan timer board where provisions have been made for connections but should have their own controls Do not use direct drive motor connections as a power source there is risk of damaging...

Page 8: ...itive If problems persist call your service contractor WARNING Fire burn asphyxiation hazard Do not start the burner unless blower access door is secured in place Failure to follow these instructions...

Page 9: ...gs Blower speed and on off time delays are handled by ECM motor programming and are set via dipswitches per Table A 10 Heating airflow rate is SW1 and on off delay is SW4 both are set according to fir...

Page 10: ...all for heat Burner should start It may be necessary to press RESET button on primary combustion control relay 2 There is a fan on time delay before circulating fan is energized United Technologies 11...

Page 11: ...GPH Head Air Setting LRF65 LRFV65 66 000 AFG70MPSS 0 50 45 W 140 0 55 L2 4 LRF80 LRFV80 78 000 AFG70MPSS 0 50 45 W 175 0 65 L2 5 LRF90 LRFV90 89 000 AFG70MPSS 0 60 60 W 175 0 75 L2 7 LRF100 LRFV100 10...

Page 12: ...3 APPENDIX A CHECK OUT AND ADJUSTMENTS Table A 4 Riello 40BF Burner Set Up Riello 40BF3 40BF5 Series Oil Burners For use with direct vent units using outdoor combustion air only Furnace Model Output...

Page 13: ...ce above horizontal center line 13 64 inch Distance ahead of nozzle 5 64 to 7 64 inch Carlin Burners Electrode gap 1 8 inch to 5 32 inch Distance above horizontal center line 5 16 inch Distance ahead...

Page 14: ...blower motor Isolate AC line voltage pins on 5 pin power connector with electrical tape to prevent electric shock hazard C Restore electrical power to furnace D Set thermostat above room temperature E...

Page 15: ...15 240011511 REV C 05 31 2017 APPENDIX A CHECK OUT AND ADJUSTMENTS FIGURE 3 UNITED TECHNOLOGIES 1168 1 ECM TAP BOARD LRFV FIGURE 2 UNITED TECHNOLOGIES 1158 120 FAN TIMER BOARD LRF...

Page 16: ...A CHECK OUT AND ADJUSTMENTS TIP Formulas will assist with design of duct work and determination of air flow delivery CFM Bonnet Output 1 085 x System Temperature Rise T System Temperature Rise T Bonn...

Page 17: ...ON is approximately equal to 400 CFM SW3 ADJUST Increase OR decrease CFM respectively APPENDIX A CHECK OUT AND ADJUSTMENTS Table A 11 Direct Drive Blower Characteristics 1 2 HP ECM Variable Speed Cons...

Page 18: ...11 Direct Drive Blower Characteristics 1 2 HP ECM Variable Speed Constant CFM Motor continued DELAY PROFILE FOR OIL HEATING SW4 DELAY DIP SWITCH POSITION INPUT USGPH PRE RUN ON DELAY TIME CFM LEVEL SH...

Page 19: ...19 240011511 REV C 05 31 2017 APPENDIX B WIRING DIAGRAMS Chimney Vent Furnace Wiring Diagram LRF LRFV...

Page 20: ...20 240011511 REV C 05 31 2017 APPENDIX B WIRING DIAGRAMS Direct Vent Furnace Wiring Diagram LRF LRFV...

Page 21: ...at cool speed Thermostat ends call for cool G and Y terminals are de energized Cooling contactor is de energized immediately Circulator fan turns off immediately FAN Thermostat begins call for fan G...

Page 22: ...stage of two stage cooling Y1 while Y Y2 is not calling The 24 VAC input signal is passed to pin 6 of P1 Blower runs at 80 of cooling speed profile FAN Thermostat calls for fan G The 24 VAC input sig...

Page 23: ...ay burn out heat anticipator of standard 24 vac thermostat or cause harm to components within micro electronic thermostat Before checking oil primary control perform these preliminary checks repair or...

Page 24: ...epair light leak if necessary Open safety switch Check for open limit or auxiliary limit Check internal wiring connections loose connectors etc Furnace will not start without first pushing oil primary...

Page 25: ...supplier Frozen oil line Gently warm oil line Insulate oil line Outdoor piping size may require increased diameter Oil burner sputtering at nozzle Electrodes out of adjustment or defective Check elec...

Page 26: ...e rise is too high speed up blower fan Defective high limit control Test high limit function of all limit switches Use duct thermometer to verify accuracy of limit control Check for obstructions to ai...

Page 27: ...05 31 2017 Model No Serial No Date Installed Contractor Contact Address Postal Code Telephone No After Hours No Fuel Supplier Fuel Oil Supplier Contact Telephone No After Hours No APPENDIX D HOMEOWNER...

Page 28: ...pe Assembly 3002317 23 Flue Pipe Insulator Pipe 29713 24 Flue Pipe Flange 109009797 25 Flue Pipe Gasket 3 per unit 240011382 26 Observation Port Sight Glass 240008235 27 Sight Glass Washer 109009449 2...

Page 29: ...BOF 130 F 30388 40 Oil Burner Assembly Beckett AFG70MPSS 0 50 45 W 550003220 Oil Burner Assembly Riello 40F3 0 55 80 B 550003221 Oil Burner Assembly Carlin EZ LF 0 50 70 B 550003222 41 Filter Side Rai...

Page 30: ...sure Switch for use with Beckett Burners 0 65 WC Blocked Vent Safety Switch 240011862 5 x 4 Appliance Adapter Connects Furnace to Vent Pipe 240011898 Combustion Air Intake Collar 4 for Beckett Burner...

Page 31: ...0011511 REV C 05 31 2017 PARTS LISTING Model LRF LRFV Diagram 1 2 3 4 8 7 9 11 14 15 16 16 27 28 30 31 32 33 34 36 37 42 40 25 21 15 18 13 41 25 24 23 22 25 29 35 20 10 19 19 17 38 8 5 41 6 26 16 31 3...

Page 32: ...ECR International 2210 Dwyer Avenue Utica NY 13501 web site www ecrinternational com...

Reviews: