16
Installing the stove
The floor on which the stove is installed must be even
and horizontal. The stove may only be installed on an
adequate loadbearing floor. The stove can be stood
on a metal floor sheet or glass sheet to protect the
flooring.
If the flooring or carpet is inflammable, a stable and
non-combustible spark protection plate must be used.
This must extend 50 cm to the front and 30 cm to each
side beyond the edge of the combustion chamber
opening. Under the stove no spark protection plate is
required.
Assembly sequence
● The Ø 150 stovepipe connection can be installed at
the top or rear. The stove is supplied ready for con-
nection from above. If you wish to connect it at the
rear, the following steps must be carried out to make
the necessary modifications:
- Break out the cover in the back panel.
- Replace the connector sleeve and the sealing
cover.
● Decide where the stove is to be installed. There
must be no objects made of combustible materials
within a distance of 80 cm of the stove‟s radiation
area, measured from the combustion chamber‟s in-
spection glass, nor may any be placed within this
area subsequently.
Depending on the installation position of the stove in
front of walls that need to be protected (flammable
or load-bearing), the following distances from walls
need to be observed in accordance with the position
of the combustion chamber door to the wall / side
panel or the back panel (see schematic diagram).
When not dealing with walls that need to be protect-
ed, you merely need to observe a minimum distance
of approx. 5 cm to allow for proper heat dissipation.
● Install the pipe lining (provided on site) in the chim-
ney. The connection height can be individually spec-
ified for a top stovepipe connection, however should
not exceed 1.5 m from the connector sleeve. For the
rear stovepipe connection heights please refer the
“Technical Data“ chapter. No combustible material is
permitted within a radius of 20 cm around the stove
pipe.
● Connect the stovepipe at both connection points
with stove putty so that the stove pipe is permanent-
ly sealed.
● Push the stove onto its planned position and orient it
so that the stovepipe fits into the pipe lining.
The stovepipe connections must be tight. The
stovepipe must not protrude into the chimney.
Bear in mind that on partition walls in accordance
with test specification EN 13240 the temperature
of 85°C can be reached, and with light wallpaper
or similar combustible construction materials this
Stove installed straight in corner
Stove installed diagonally in corner
Additional log retainer
Dimensions in cm
can result in colour changes.
An additional log retainer is packed in the wood storage
compartment. This decorative part can be exchanged
for the existing log retainer.
20
20
20
Dimensions in cm
20
20
Summary of Contents for 23/665
Page 6: ...6 Montage der PowerBloc Steine 1 a 1 b 2 a 2 b 3 a 3 b 4 a 4 b...
Page 17: ...17 Installation of PowerBloc stones 1 b 2 a 2 b 3 a 3 b 4 a 4 b 1 a...
Page 26: ...26 Installation des pierres PowerBloc 1 b 2 a 2 b 3 a 3 b 4 a 4 b 1 a...
Page 35: ...35 Installatie van PowerBloc steens 1 b 2 a 2 b 3 a 3 b 4 a 4 b 1 a...