55
ENGLISH
3.1.9
ALARMS (fig. 40)
The Alarms
icon calls up the window that shows the current alarms, current overrides and the alarms history.
To cancel the current alarms press the Reset
icon and confirm.
To reset the alarms history, press the Reset icon, then enter the Service password and confirm.
Alarms on internal unit display
Table shows the alarms or overrides that can appear on the control panel display.
Overrides DO NOT represent system malfunctions; they signal particular temporary operating conditions. Overrides
DO NOT require the intervention of technical support.
When an alarm is triggered, an alarm window appears on the display together with an audible signal that lasts for a
maximum of sixty seconds. Press the
icon in the alarms window to call up the Alarms window, or press the
icon
to return to the main window; the audible signal can be stopped by touching one of the two icons. When an alarm is
triggered the alarm contact between terminals 16 and 17 is also closed (figs. 20, 21).
Override/Alarm Code
Mnemonic on display
Override/Alarm Description
Override #1
Or1
Incoming water temperature lower that 10°C in heating mode
Override #2
Or2
Main exchanger evaporator frost protection
Override #3
Or3
External heat source activation request
Override #4
Or4
TA contact open
Override #5
Or5
External unit capacity limit
Override #6
Or6
External unit defrosting cycle active
Override #7
Or7
External unit DHW not available
Override #8
Or8
DHW flow switch intervention
Override #9
Or9
DHW evaporator exchanger evaporator frost protection
Override #10
Or10
DHW compressor temperature protection
Override #11
Or11
Main circulation pump maintenance
Override #12
Or12
Water filter maintenance
Override #13
Or13
DHW circulation pump maintenance
Alarm #1
A1
Inlet water sensor faulty
Alarm #2
A2
Outlet water sensor faulty
Alarm #3
A3
DHW storage tank temperature sensor faulty
Alarm #4
A4
T4 outside air sensor faulty
Alarm #5
A5
Main exchanger frost protection
Alarm #6
A6
Main circuit flow switch alarm
Alarm #7
A7
Communication error with the external unit
Alarm #8
A8
Anti-legionella cycle non completed
Alarm #9
A9
RS485 serial port communication error
Alarm #10
A10
Overcurrent protection (external unit alarm **)
Alarm #11
A11
Power voltage protection (external unit alarm **)
Alarm #12
A12
External unit phase sequence (external unit alarm **)
Alarm #13
A13
External unit temperature sensors faulty (external unit alarm **)
Alarm #20
A20
DHW circuit flow switch alarm
Alarm #21
A21
DHW evaporator frost protection
Alarm #22
A22
DHW compressor overheating
Alarm #23
A23
DHW compressor flow temperature sensor faulty
Alarm #24
A24
DHW condenser temperature sensor faulty
Alarm #25
A25
DHW evaporator temperature sensor faulty
Alarm #100
A100
Internal unit electronic malfunction
Alarm #101
A101
Internal unit electronic malfunction
Alarm #102
A102
Internal unit electronic malfunction
Alarm #105
A105
Internal unit electronic malfunction
** Check alarm type on external unit board sect. 3.5.2
3
Summary of Contents for OS-CEBCH36EI
Page 1: ......
Page 2: ...2 1 3 2 U H A S G I F C N E T D R N O M U B L V Z ...
Page 3: ...3 5 4 A B C ...
Page 4: ...4 7 D D D C A M H G I F E B D L 6 A B 6a A A ...
Page 6: ...6 16 15 A B E F E G H C D 14 13 C D A B A H B C D E F E G 11 12 B A ...
Page 10: ...10 B C A D C E F C G 25 27 26 29 28 31 30 ...
Page 11: ...11 33 32 35 34 36 37 A C D B 2 3 1 E 4 5 6 7 8 9 ...
Page 12: ...12 39 38 41 40 43 42 45 44 ...
Page 13: ...13 47 46 49 48 51 50 52 ...
Page 14: ...14 ...
Page 38: ...3 ...
Page 62: ...3 ...
Page 86: ...3 ...
Page 87: ...3 ...
Page 88: ...www olimpiasplendid it info olimpiasplendid it 277415B 1 ...