The external unit is supplied with a mesh for covering the heat exchange battery; this is envisaged for installations
accessible to the public. Fitting the mesh may cause, in the event of high humidity at low temperature (fog) or snow, a
build-up of ice on the battery with reduced system performance.
2.3
OPERATING LIMITS
(fig.9)
The diagrams in fig.9 define the water (LWT) and outdoor air (ODT) temperature limits within which the heat pump can run in its
two modes, cooling and heating/production of domestic hot water (DHW).
2.4
REFRIGERANT CONNECTIONS
(fig. 10, 11)
To define the refrigerant connection lines between the internal unit and the external unit, see the table below.
OS-
CEBSH24EI
OS-
CEBCH36EI
OS-
CEINH48EI
OS-
CETNH48EI
OS-
CEINH60EI
OS-
CETNH60EI
Maximum length of
connecting pipes (m)
25
30
50
50
50
50
Limit of elevation difference
between the two units if the
external unit is positioned
higher (m)
12
20
25
30
25
30
Limit of elevation difference
between the two units if the
external unit is positioned
lower (m)
9
12
20
20
20
20
Additional charge of
refrigerant per metre over 5
metres piping (g/m)
60
60
60
60
60
60
Use solely pipes with diameters that comply with the required dimensions (5/8” gas pipe, 3/8” liquid pipe).
The maximum length of the connecting lines to the internal unit must comply with table 1, topping up the charge of R410A as
envisaged (see sect. 2.4.2). Do not install the units beyond the maximum height difference permitted between the internal unit
and the external unit.
Complete the refrigerant circuit by connecting the internal unit to the external unit using insulated copper pipes.
Use solely insulated copper pipes specific for cooling purposes, supplied clean and sealed at the ends.
The refrigerant connections of the internal unit are behind the electric panel; those of the external unit are on the right-hand side
and the safety panel must be removed in order to gain access.
A
5/8” gas line internal unit
B
3/8” liquid line internal unit
C
5/8” gas line valve external unit
D
3/8” liquid line valve external unit
Identify a route for the pipes that reduces the length and the bends in the pipes as much as possible to obtain maximum perfor-
mance from the system.
Insert the refrigerant lines into a suitably sized cable routing duct (if possible with internal separator) fastened to the wall for
routing the pipes and electrical wires.
Cut the lengths of pipe about 3-4 cm longer than the required length.
IMPORTANT: cut using a wheel pipe-cutter only, tightening at small intervals so as not to crush the pipe.
• Remove any burrs using an appropriate tool.
• Before flaring, insert the fastening nut into the pipe (fig.11 ref. A).
• Flare the ends of the pipes impeccably, without cracks, wrinkles or folds, using a special tool (fig.11 ref. B).
• Manually tighten the pipe nut onto the thread of the fitting.
• Definitively tighten using a fixed wrench to keep the threaded part of the fitting stationary to prevent deformation,
and a dynamometric wrench on the nut (fig. 12) calibrated with the following values depending on the size of the
pipes:
• Diameter 3/8’’ 34 N.m < tightening torque < 42 N.m
• Diameter 5/8’’ 68 N.m < tightening torque < 82 N.m
Summary of Contents for OS-CEBCH36EI
Page 1: ......
Page 2: ...2 1 3 2 U H A S G I F C N E T D R N O M U B L V Z ...
Page 3: ...3 5 4 A B C ...
Page 4: ...4 7 D D D C A M H G I F E B D L 6 A B 6a A A ...
Page 6: ...6 16 15 A B E F E G H C D 14 13 C D A B A H B C D E F E G 11 12 B A ...
Page 10: ...10 B C A D C E F C G 25 27 26 29 28 31 30 ...
Page 11: ...11 33 32 35 34 36 37 A C D B 2 3 1 E 4 5 6 7 8 9 ...
Page 12: ...12 39 38 41 40 43 42 45 44 ...
Page 13: ...13 47 46 49 48 51 50 52 ...
Page 14: ...14 ...
Page 38: ...3 ...
Page 62: ...3 ...
Page 86: ...3 ...
Page 87: ...3 ...
Page 88: ...www olimpiasplendid it info olimpiasplendid it 277415B 1 ...