background image

9

© 2015 OJ Electronics A/S

Room is too cold

(after running for at least 48 hours)

The room sensor is placed in a position that does not represent the general temperature in the room. For 

example mounted on an external wall or near to an external heat source.

If the room is controlled by a WLCT3 room sensor, check that the time and temperatures are set correctly.

If the room sensor has a mode switch (WLTM3, WLTd3 or WLdT3), the switch may be set to “OFF” or 

“NIGHT” position.

For rooms with floor sensors, the maximum floor limit setting could be preventing the room from reaching 

the desired temperature.

The system may have insufficient heating capacity.

Poor insulation may be causing large heat loss. 

Room is too hot

(after running for at least 48 hours)

This might be caused by draughts caused by internal wall cavities or open doors or windows which affect 

the temperature-measuring ability of the sensor. 

The room sensor is placed in a position that does not represent the general temperature in the room.

If the room is controlled by a WLCT3 room sensor, check that the time and temperatures are set correctly.

If the room sensor has a mode switch (WLTM3, WLTd3 or WLdT3), the switch may be set to the “dAy” 

position.

For rooms with floor sensors, the minimum floor limit setting could be maintaining the room temperature 

above the desired setting.

Solar gain or an external heat source.

Temperature is unstable

This could be caused by periodic solar gain or external heating. Try setting the master to simple ON/OFF 

control (dIP-10 set to ON).

Summary of Contents for WLM3

Page 1: ...WLDT3 WLM3 WLCT3 WLTD3 WLTA3 Installation Quick Guide www ojelectronics com 67347 02 15 HKT...

Page 2: ...2 2015 OJ Electronics A S Installation Quick Guide Page 3 Setting up the system Page 5 Wireless system only Page 5 Testing the system Page 6 Troubleshooting Page 7 CONTENTS QUICK GUIDE...

Page 3: ...LRC3 using the special cable included in the box NB For room sensors controllers with floor temperature limitation sensors please refer to the separate instructions included with the unit Installation...

Page 4: ...or bus or direct to master maintaining continuity of positive and negative connections Connect 230V AC power supply UFH circulating pump and boiler in accordance with electrical regulations With FS ma...

Page 5: ...press the OK button to go to the next channel CH 2 and repeat this step until all the required channels have been set 3 5 After all channels have been set select the ESC menu entry and press OK NB If...

Page 6: ...nel 1 LED should light up and the actuator on output 1 should activate Important If the room sensor controller is of wireless type a delay of up to 5 minutes may occur before the channel LED lights up...

Page 7: ...nel number The channel selector on the room sensor may be slightly out of position try rotating it and then set it again Channel LED does not light up when in install mode after the room sensor has be...

Page 8: ...ical connection between boiler and terminals During install mode the boiler relay will not operate The attached boiler may be faulty LED not lit Timing sequence delay is activated FS master only mixin...

Page 9: ...ay be causing large heat loss Room is too hot after running for at least 48 hours This might be caused by draughts caused by internal wall cavities or open doors or windows which affect the temperatur...

Page 10: ...10 2015 OJ Electronics A S...

Page 11: ...11 2015 OJ Electronics A S...

Page 12: ...ark warminster wiltshire ba12 8sp united kingdom T 44 01985 213 003 F 44 01985 213 310 sales ojuk co uk www ojUK co uk OJ ELECTRONICS A S c o Robert Bielecki UL walbrzyska 33 58 160 SWIEBODZICE POLska...

Reviews: