6
© 2015 OJ Electronics A/S
1.
Switch on dIP-3 to activate learning mode. - the power Led will flash quickly
2.
each red channel Led on the master should now be lit if a room sensor/controller is present on
that channel.
3.
Switch off dIP-3 to deactivate learning mode again – the power Led will stop flashing.
4.
Set the setpoint on all adjustable room sensors/controllers to minimum.
5.
Switch on dIP-1 on the master to activate install mode. Install mode will remain active for 2
hours. Pumps, boiler, mixing valve and actuators should now be OFF.
NOTe: during install mode, the boiler will not fire unless dIP-2 is also activated. This is
designed to reduce energy consumption and boiler cycling during the testing process.
6.
Set the knob on the adjustable room sensor/controller in room 1 to maximum. The red channel
1 Led should light up and the actuator on output 1 should activate.
Important: If the room sensor/controller is of wireless type, a delay of up to 5 minutes may
occur before the channel Led lights up. (Pressing the initialization button inside the room
sensor/controller for 30 sec. speeds this up.)
7.
With an FS master, check that the uHF pump starts running and that the mixing valve opens.
8.
Repeat step 6 for all rooms.
9.
Boiler test function:
Switch on dIP-2.
This activates the boiler relay contacts for 1 minute.
10.
To end system testing:
- Switch off dIP-1 to deactivate install mode.
Switch off dIP-2 to deactivate the boiler test.
- Set all temperature knobs to default positions.
Set WLTA3,WLTd3,WLTM3 and WLdT3 room sensors to zero (centre position /no offset).
Set WLCT3 room controllers to 21°C (recommended).
- Set all WLTM3, WLTd3 and WLdT3 room sensors to automatic mode (clock symbol).
11.
The system will now operate automatically.
Other important settings can be found in the user Manual.