Basic Settings
The
Basic Settings
screen enables you to view and change the unit basic settings as
User
. You can change the values that are shown in black on the screen by tapping on
the values. Values that are shown in gray are read-only, and cannot be changed.
Basic Settings screen ver. 2
Position
Item
Description
1
Unit 1 cold side inlet value
Unit will not start unless the inlet value is over this
value.
2
Unit 1 warm side inlet
Unit will not start unless the inlet value is under this
value.
3
Liquid flow
If the value is shown in gray, it comes straight from the
flow meter. If the value is shown in black, manual input
is required.
4
Buffer start value
The heat pump starts after the high-level sensor is
below the value.
5
Buffer stop value
The heat pump stops after the low-level sensor is above
the value.
6
Buffer start value
The heat pump starts after the low-level sensor is above
the value.
7
Buffer stop value
The heat pump stops after the high-level sensor is
below the value.
8
Buffer variables
If the value is shown in gray, the buffer is not in use and
the value is not needed. If the value is shown in black,
the buffer is in use.
Advanced Settings
The
Advanced Settings
screen enables you to make changes to the advanced
operational settings as
Expert
user.