Radiator heating, guideline values
Floor heating, guideline values
Room tempe1 °C → Increase by 6 (+6)
Room temperature −1 °C → Decrease by 6 (−6)
Room tempe1 °C → Increase by 3 (+3)
Room temperature −1 °C → Decrease by 3 (−3)
For example, if the flow temperature in the curve is +35 °C and the
Reduced
setting is
–3 °C, the target flow temperature will be +32 °C.
After changing a setting, wait for at least two or three days to see if the change has
made a difference. The setting for the
Normal
operating mode is also shown in the
Home
view.
Room temperature optimization enabled
If the system is equipped with an indoor temperature sensor and temperature
optimization is enabled, this setting will change the room temperature setpoint directly
instead. Changing the operating mode will directly increase or decrease the room
temperature setting. The room temperature setpoint influences flow temperature
through the room temperature optimization function.
After changing a setting, wait for at least two or three days to see if the change has
made a difference.
Settings
Device settings → Heating circuits
Status view → Heating
Heating curve
See sub-section
Heating curve.
The impact of
different operating
modes
See sub-section
The impact of different operating modes.
Schedule for
operating modes
See section
Home or Away function and Schedules.
Device settings → Heating circuit 1 → Settings
Stop heating
temperature
(summer break)
Heating will stop when the long-term outdoor temperature average is higher than
this temperature. Heating will resume when the long-term outdoor temperature
average is lower than this temperature.
●
Typical setting: +10...+15 °C
● Set the value slightly below the desired room temperature.
Outdoor
temperature, avg.
An automatically calculated long-term outdoor temperature average.
Max. flow
temperature
The maximum flow temperature when the outdoor temperature matches the
Design outdoor temperature
setting. The system will keep the flow temperature
determined by the heating curve below this temperature value.
●
Typical setting, floor heating:
conrete 35 °C, wooden 45 °C
● Check the temperature value from the floor or floor heating supplier (or from the
applicable plans and specifications).
Min. flow
temperature
The system will keep the flow temperature determined by the heating curve above
this temperature value.
●
Typical setting: +20...+25 °C
● Set the minimum flow temperature at or slightly above the required room
temperature.