COMMISSION DELEGATED REGULATION
(EU) No 811/2013, ANNEX IV
c space heating application
B 0
°C /
W 55
°C
B 0
°C /
W 55
°C
B 0
°C /
W 55
°C
B 0
°C /
W 55
°C
c water heating load profile
L
L
L
L
d seasonal space heating energy efficiency
class (starting from September 26, 2019*),
water 47/55 °C
A++ A++ A+++ A+++
d water heating energy efficiency class (starting
from September 26, 2016)
A
A
A
A
d energy efficiency class in DHW heating
(starting from September 26, 2019*)
A
A
A
A
e total rated heat output of heat pump and
supplementary heater
P
rated
+ P
sup
kW
5 + 6 7 + 6 9 + 6 12 +
6
f annual electricity consumption, space heating Q
HE
kWh
2821 3629 4689 5969
f annual electricity consumption, DHW heating AEC
kWh
1571 1526 1462 1472
g seasonal space heating energy efficiency
s
%
145
150
157
157
g Energy efficiency, DHW heating
wh
%
107
110
115
114
h sound power level
L
WA
dB(A) 40
44
45
47
i the combination heater can be timed to
operate outside off-peak periods
✓
✓
✓
✓
j specific precautions that shall be taken when
the space heater is assembled, installed or
maintained
1)
1)
1)
1)
STANDARD RATING CONDITIONS (BRINE
0/−3 °C, WATER 47/55 °C), COLDER AND
WARMER CLIMATE CONDITIONS
k total rated heat output of heat pump and
supplementary heater under colder climate
conditions
Prated
+ Psup
kW
5 + 6 7 + 6 9 + 6 12 +
6
k total rated heat output of heat pump and
supplementary heater under warmer climate
conditions
Prated
+ Psup
kW
5 + 6 7 + 6 9 + 6 12 +
6
l annual space heating energy consumption
under colder climate conditions
QHE
kWh
3259 4181 5413 6892
l annual electricity consumption under warmer
climate conditions, space heating
QHE
kWh
1808 2317 2997 3818
l annual electricity consumption under colder
climate conditions, DHW heating
AEC
kWh
1571 1526 1462 1472
l annual electricity consumption under warmer
climate conditions, DHW heating
AEC
kWh
1571 1526 1462 1472
m seasonal energy efficiency under colder
climate conditions, space heating
s
%
150
156
162
162
m seasonal energy efficiency under warmer
climate conditions, space heating
s
%
146
152
158
159
m energy efficiency under colder climate
conditions, DHW heating
wh
%
107
110
115
114
m energy efficiency under warmer climate
conditions, DHW heating
wh
%
107
110
115
114
52 (54)