Specifications 

8-1 Standard specification 

Model 

OCA-S350BCD 

-A200 

OCA-S700BCD 

-A200 

OCA-S1300BCD 

-A200 

OCA-S2300BCD 

-A200 

Type of mounting 

Lateral mounting (External mounting only) 

Cooling capacity *1 

300/350W 

600/700W 

1150/1300W 

2100/2300W 

Rated voltage 

Single phase 200VAC 50/60Hz 

3 phase 

200VAC 50/60Hz 

Current 

consumption 

(50/60Hz) 

Rated *2 

1.4/1.4A 

2.1/2.2A 

3.5/3.6A 

3.5/3.6A 

With 

condensate *3 

1.3/1.2A 

2.1/2.1A 

3.4/3.5A 

3.4/3.7A 

Max. *2 

1.5/1.5A 

2.4/2.6A 

4.1/4.4A 

4.0/4.4A 

Starting 

current 

Max. *2 

3.7/3.6A 

6.1/5.9A 

12.6/11.9A 

14.6/14.8A 

Power 

consumption 

Rated *2 

235/260W 

390/425W 

630/705W 

975/1115W 

With 

condensate *3 

225/240W 

380/410W 

625/695W 

960/1150W 

Max. *2 

270/295W 

455/510W 

760/875W 

1160/1390W 

Compressor motor output 

100W 

250W 

400W 

650W 

Working temperature *4 

+20

  to +50

 

Working humidity 

85%RH or less, Free from condensation 

Noise (Characteristic A) 

62dB 

65dB 

65dB 

68dB 

Setting temperature range *4 

+30

  to +45

℃(

Initial setting : +35

℃)

 

Conditions for condensate-free 

+35

, 85%RH or less 

Display 

Internal temperature, Alarm code/Operating lamp/Alarm lamp 

Function 

Off-temperature alarm, Detection of abnormal heat 

dissipation, Detection of temperature sensor disconnection 

External output 

Alarm output, 1a 240V 1.5Ax2 Output (Common) 

Vibration resistance 

Vibratility 10-150Hz, Acceleration 1.0G, Sweep cycle 20 times 

Protective category 

Equivalent to IP54 for internal circuit 

Applicable 

standards 

EMC 

directive 

Conforming to EN61000-6-2 and EN61000-6-4 

Low voltage 

directive 

EN60335-1, EN60335-2-40 and EN62233 

Environmental 

standard 

RoHS2 

Refrigerant 

Type 

/Designation 

HFC R134a 

HFC R407C 

Amount 

130g 

190g 

355g 

620g 

GWP 

1430 

1770 

Body color 

Beige

5Y7/1 corresponding

 

Fuse rating of control board 

250V    1A 

Dimensions (WxHxD in mm)  300

×

500

×

200  350

×

600

×

200  390

×

900

×

250  450

×

1150

×

250 

Weight 

17.0kg 

22.0kg 

34.0kg 

52.0kg 

Note ) *1 Nominal values when temperatures both inside and outside the control panel is 35

 

*2 Values at 35

  temperature both inside and outside are indicated in 

Rated

 and 

values at 50

  outside and 35

  inside are indicated in 

Max.

*3 Nominal values with maximum condensate generation when enclosure interior is 35

,85%RH. 

*4 This product should not be used outside the temperature range specified here. 

 

8-2    A complete set of supply 

Item 

OCA-S350BCD 

-A200 

OCA-S700BCD 

-A200 

OCA-S1300BCD 

-A200 

OCA-S2300BCD 

-A200 

COOLCABI 

1   

Fixing bolt 

M6

×

35mm

M6

×

35mm

6  M8

×

35mm

Washer 

M6

M6

M8

Spring washer 

M6

M6

M8

Nut 

M6

M6

M8

Packing 

1 roll 

Drain hose 

2m 

Terminal board 

Alarm explanation label 

Instruction manual 

Summary of Contents for Cool Cabi OCA-S1300BCD-A200

Page 1: ...OCA S350BCD A200 OCA S700BCD A200 OCA S1300BCD A200 OCA S2300BCD A200...

Page 2: ...2 20 50 85 RH 70...

Page 3: ...3 OCA S1300BCD A200 OCA S1300BCD A200 14 35 85 RH 3...

Page 4: ...4 M6 2 200mm 30...

Page 5: ...5 P 6 P 7 OCA S1300BCD A200 OCA S700BCD OCA S1300BCD OCA S2300BCD A200...

Page 6: ...6 OCA S350BCD A200 OCA S700BCD A200 OCA S1300BCD A200 OCA S2300BCD A200...

Page 7: ...7 OCA S350BCD A200 OCA S1300BCD A200 35 85 RH...

Page 8: ...8 OCA S350BCD A200 OCA S700BCD A200 1 4 OCA S1300BCD A200 OCA S2300BCD A200 OCA S1300BCD 4 OCA S2300BCD 8...

Page 9: ...A S350BCD A200 OCA S700BCD A200 OCA S1300BCD A200 OCA S1300BCD A200 OCA S350BCD A200 OCA S700BCD A200 OCA S1300BCD A200 OCA S2300BCD A200 a 240V 1 5A 2 P 13 14 AC200V IN L N E 1 2 3 a 240V 1 5A 2 P 13...

Page 10: ...10 OCA S2300BCD A200 1 30mA...

Page 11: ...11 30 ON OFF 1 6 ON OFF ON OFF P 12 35 Set Up Down 35 30 45 Set Up Down 3 30 Down Up Set ALARM Set Down Up RUN...

Page 12: ...3 Set Up Down Set 5 3 10 1 6 ON OFF 30 0 99 Up Down 3 45 35 51 2 1 20 0 0 99 0 1 99 1 100 1 99 9900 24 412 0 0 1 0 1 0 0 1 0 P 17 6 1 2 1 P 17 6 1 2 1 0 1 OPEN CLOSE OPEN CLOSE 0 1 0 0 0 3 0 1 2 3 P...

Page 13: ...13 P 15 16 0 0 1 OPEN CLOSE 0 1 0 1 2 3 P 13 14 1 0 3 0 1 2 3 7 7 60 3 3 3 10 ON OFF Set 3 30 Set 3 AS Ao 1 2 2 3 OPEN 0 8 AS 0 AS 1 AS 2 AS 3...

Page 14: ...E3 E4 CLOSE E5 SE OPEN E1 E3 E4 OPEN 3 E3 E5 SE CLOSE E1 E4 CLOSE E3 E5 SE OPEN E1 E4 OPEN E4 P 12 0 Ao 1 AS 1 2 2 3 0 OPEN CLOSE CLOSE OPEN 1 OPEN CLOSE CLOSE OPEN 2 E5 SE OPEN E1 E3 E4 OPEN E5 SE C...

Page 15: ...15 35 5 35 30 4 P 14 3 30 1 30 5 35 30 ON OFF ON OFF 35 30 ON OFF ON OFF...

Page 16: ...16 7 3 5 5 35 30 ON OFF ON OFF 30 35 45 ON OFF ON OFF...

Page 17: ...17 45 P 14 43 P 14 Set 3 P 14 Set 1 P 14 OFF...

Page 18: ...300BCD OCA S2300BCD OCA S1300BCD A200 OCA S350BCD A200 FM 350BCDIN 200V FM 350BCDOUT 200V OCA S700BCD A200 FM 700BCDIN 200V FM 700BCDOUT 200V OCA S1300BCD A200 FM 1300BCDIN 200V FM 1300BCDOUT 200V OCA...

Page 19: ...19 OCA S1300BCD A200 P 18 OCA S1300BCD A200 35 85 RH OCA S350BCD OCA S700BCD OCA S1300BCD OCA S2300BCD...

Page 20: ...20 OCA S2300BCD A200 50 45 P 11 P 4 P 18 19 P 19 OFF No 7 5kW 1 4 P11 5 4...

Page 21: ...960 1150W 2 270 295W 455 510W 760 875W 1160 1390W 100W 250W 400W 650W 4 20 50 85 RH A 62dB 65dB 65dB 68dB 4 30 45 35 35 85 RH 1a 240V 1 5A 2 COMMON 10 150Hz 1 0G 20 IP54 EMC EN61000 6 2 EN61000 6 4 EN...

Page 22: ...22 OCA S350BCD A200 OCA S700BCD A200 12 12 2 M8 13 4 M6 14 4 M6 14...

Page 23: ...23 OCA S1300BCD A200 OCA S2300BCD A200 12 12 2 M8 13 4 M6 14 2 M8 13 6 M8 14...

Page 24: ...24 1 13 64 19 10 4 431 1304 7000 21 TEL 053 522 5572 FAX 053 522 5573 8 2019 5...

Page 25: ...ents 1 Safety Precautions 2 Part names and evaporation mechanism 3 Mounting 4 Wiring 5 Operation 6 Alarm Safeguard 7 Maintenance 8 Specifications 9 Warranty period 10 Waste disposal Please read this b...

Page 26: ...in short life or damage of the unit Shocks and vibrations should be strictly avoided at the site of use Never tamper or repair the main body Please consult with your local supplier for repairing servi...

Page 27: ...mperature Evaporation fin and the external air that passes through the fin the water vaporizes into the atmosphere Meanwhile such evaporation takes heat away from the surroundings and it brings about...

Page 28: ...as shown in the right Ground the wire without fail to prevent electrical shocks Electrical works required for installation of the unit must be done only by specialists Improper installation may result...

Page 29: ...nd the nuts from inside the control panel and secure them 6 To ensure keep the panel interior airtight caulk the gaps completely if any 7 Apply the enclosed Alarm description label to an appropriate p...

Page 30: ...6 Cutouts for mounting View from outside the panel OCA S350BCD A200 OCA S700BCD A200 OCA S1300BCD A200 OCA S2300BCD A200...

Page 31: ...deg C and humidity not exceeding 85 RH for both ambient and enclosure interior When the evaporation fin or the evaporation sheet is dirty When passing air volume in evaporation mechanism declined due...

Page 32: ...is hooked Unscrew first and then lift up the panel to remove 2 Detach the Maintenance panel by removing 4 screws 3 Absorb the water in the Evaporation pan and the Water pan with a syringe or a wiping...

Page 33: ...ured 6 For the application using crimp terminals the bar terminals made by Phoenix Contact 4 2 Circuit diagram OCA S350BCD A200 OCA S750BCD A200 OCA S1300BCD A200 Example OCA S1300BCD A200 The number...

Page 34: ...e made so as to assure stable operation without affected by such current as well as providing effective protection against possible overcurrent thereafter b For earth leakage breakers use a reference...

Page 35: ...ting temperature Caution Setting temperature should be basically at 35 Avoid setting at an unnecessarily low value which may cause excessive ondensation or drainage 1 Turn on the unit The current inte...

Page 36: ...tting range 0 99 This is the function to remind you maintenance works in a timely manner 0 This function is ineffective 1 99 1 means 100 hours Notification period can be set between 100 to 9900 hours...

Page 37: ...eriod for restarting the compressor after shutdown For prevention of frequent ON OFF of the compressor cooling operation is suspended during the set period Display of software version This is to displ...

Page 38: ...E3 E5 and SE OFF OPEN Alarm E1 and E4 OFF OPEN Alarm E4 is not output when Fo is set at 0 See page 12 Assignment table of Alarm output terminals Ao 1 AS Terminals 1 2 Terminals 2 3 Description Operati...

Page 39: ...eration will not start for a certain period of time initial setting 3 min after cooling operation has stopped even if the internal temperature goes up to the set temperature 1 Continuous run Cooling o...

Page 40: ...he air is not circulated by the internal fan For protection of the refrigerant circuit the internal fan will not stop for 5 minutes after cooling operation has stopped The internal fan runs continuous...

Page 41: ...See the assignment table of alarm output terminals in page 14 Current internal temperatures and E4 are displayed by turns to remind you to carry out maintenance work Cooling operation will be continu...

Page 42: ...0BCD CF S2 2 pcs set OCA S2300BCD 7 2 Replacement of external fan Example OCA S1300BCD A200 In the event of a fan failure go through the following steps to replace the fan 1 Remove the suction port fi...

Page 43: ...orking condition is within the specified range 35 deg C 85 RH both inside and outside an enclosure the Evaporation fin or the Evaporation sheet may be contaminated Carry out maintenance work according...

Page 44: ...here temperature exceeds 45 f Clean the filter g Check temperature setting and the internal temperature In case of fan failure replace the fan h To check whether the fan works properly execute forcibl...

Page 45: ...ection External output Alarm output 1a 240V 1 5Ax2 Output Common Vibration resistance Vibratility 10 150Hz Acceleration 1 0G Sweep cycle 20 times Protective category Equivalent to IP54 for internal ci...

Page 46: ...arm air Air from outside Cool air Air from inside External suction port filter white Evaporation sheet Terminal board Bottom view 4 M6 Depth 14mm For fixing bolt Top view 2 M8 Depth 13mm For eyebolt A...

Page 47: ...ottom view Top view Air from outside Warm air 2 M8 Depth 13mm For eyebolt External suction port filter white Drain pipe outer dia 12mm Evaporation sheet Cool air Air from inside Terminal board 6 M6 De...

Page 48: ...user Recovery of the refrigerant should be done by an authorized waste disposer Owner s management responsibility Check of equipment The enclosure cooling unit needs simple regular inspection Daily c...

Reviews: