17
6.
Alarm/Safeguard
6-1 Alarm
(1) E1
:
High Temp. Alarm
When the internal temperature reaches 45
℃
(factory setting), the alarm output
terminals will break and make contact as set in AS and Ao to light alarm lamp (See the
assignment table of alarm output terminals in page 14).
The display shows the current
internal temperature and E1 by turns to indicate that the internal temperature is too
high. Cooling operation will be continued.
When the internal temperature falls to 43
℃
(factory setting) or lower, the alarm output
contact returns to the original state and the alarm lamp turns off.
(2) E3
:
Radiation Error Alarm
If the cooling unit radiates too much heat due to some problems like clogged filters or fins
or fan failure, the overheat detector in the refrigerant circuit is activated to stop cooling
operation. The alarm output terminals will break and make contact as set in AS and Ao
to light alarm lamp (See the assignment table of alarm output terminals in page 14).
The display shows the current internal temperature and E3 by turns to indicate
abnormal radiation.
Clean the filters and the fins or replace the fan and them press the SET button of the
temperature controller for more than 3 seconds to cancel the alarm. The cooling unit will
restart operation.
(3) E4
:
Maintenance reminder
When the cumulative operating hour reaches the set value, the alarm output terminals
will break and make contact as set in AS, Ao and Fo to light alarm lamp (See the
assignment table of alarm output terminals in page 14).
Current internal temperatures
and E4 are displayed by turns to remind you to carry out maintenance work. Cooling
operation will be continued.
After completion of maintenance of filter and others, press SET button to cancel
the alarm.
Change of the parameter for this function makes the cumulative hours by that time zero
and operating hours are counted anew.
(4) E5
:
Temperature Sensor Disconnection Alarm
Cooling operation will stop in the event of disconnection of the internal temperature
sensor for some reasons. The alarm output terminals will break and make contact as set
in AS and Ao to light alarm lamp (See the assignment table of alarm output terminals in
page 14).
The display shows E5.
In the event of this failure, turn off the power immediately and contact your supplier.
(5) E8
:
Type Error
Contact the supplier.
(6) SE
:
System Error
This error occurrs when the parmeters cannot be read correctly due to a memory fault.
The display shows SE only.
In the event of this failure, turn off the power immediately and contact your supplier.
6-2 Safeguard
As a safeguard, this product is designed to stop operation under an abnormal current or
a temperature.
In this event, the alarm E1 or E3 will occur.
7.
Maintenance
Caution
Be sure to disconnect power before carrying out any maintenance work.
Use the specified filter for replacement. Use of fine filters will cause
efficiency loss in heat releasing which leads to reduced cooling
performance and/or breakdown of the unit.
Cleaning and user maintenance shall not be made by children.
The appliance shall not be cleaned with a water jet.
Summary of Contents for Cool Cabi OCA-S1300BCD-A200
Page 1: ...OCA S350BCD A200 OCA S700BCD A200 OCA S1300BCD A200 OCA S2300BCD A200...
Page 2: ...2 20 50 85 RH 70...
Page 3: ...3 OCA S1300BCD A200 OCA S1300BCD A200 14 35 85 RH 3...
Page 4: ...4 M6 2 200mm 30...
Page 5: ...5 P 6 P 7 OCA S1300BCD A200 OCA S700BCD OCA S1300BCD OCA S2300BCD A200...
Page 6: ...6 OCA S350BCD A200 OCA S700BCD A200 OCA S1300BCD A200 OCA S2300BCD A200...
Page 7: ...7 OCA S350BCD A200 OCA S1300BCD A200 35 85 RH...
Page 10: ...10 OCA S2300BCD A200 1 30mA...
Page 15: ...15 35 5 35 30 4 P 14 3 30 1 30 5 35 30 ON OFF ON OFF 35 30 ON OFF ON OFF...
Page 16: ...16 7 3 5 5 35 30 ON OFF ON OFF 30 35 45 ON OFF ON OFF...
Page 17: ...17 45 P 14 43 P 14 Set 3 P 14 Set 1 P 14 OFF...
Page 20: ...20 OCA S2300BCD A200 50 45 P 11 P 4 P 18 19 P 19 OFF No 7 5kW 1 4 P11 5 4...
Page 22: ...22 OCA S350BCD A200 OCA S700BCD A200 12 12 2 M8 13 4 M6 14 4 M6 14...
Page 23: ...23 OCA S1300BCD A200 OCA S2300BCD A200 12 12 2 M8 13 4 M6 14 2 M8 13 6 M8 14...
Page 24: ...24 1 13 64 19 10 4 431 1304 7000 21 TEL 053 522 5572 FAX 053 522 5573 8 2019 5...