OGI TotalArc BMS 460246 SOLAR POWER Operator'S Manual Download Page 21

 

12 

 

 
HOW TO CHECK BATTERY VOLTAGE 
 

 

WARNING: DANGEROUS VOLTAGES PRESENT DURING THIS TEST, TRAINED 

PERSONNEL TO PERFORM THIS TEST. CONFIRM THERE ARE NO FLAMMABLE GASSES 

PRESENT WHILE PERFORMING TEST. ARC FLASH HAZARD – APPROPRIATE PPE 

REQUIRED WHILE WORKING ON THE FOLLOWING: 

 

 

Solar System 

 

Use Voltmeter set to measure DC voltage 

 

Place Red lead in terminal block 1 and Black lead in terminal block 2 

 

Voltage reading must be between 11.5 and 13.5 VDC 

 

Note: If Voltage readings fail to meet minimum requirements, 
 follow trouble shooting steps below 

 

Check Solar Panel power source: 

o

 

Confirm Solar panel is clear of any obstruction with the southern sky. 

o

 

Use Voltmeter set to measure DC voltage 

o

 

Place Red lead in terminal block 9 and Black lead in terminal block 2 

o

 

Voltage reading must be between 14 VDC and 17 VDC depending of solar exposure. 

 

Note:  If  voltage  readings  fails  to  meet  minimum  requirements,  check  wiring 
connections from the solar panel into the TotalArc enclosure. The solar panel has a 
junction box in the back side. Open junction box and check terminations. Note that 
there  will  be  power  at  the  solar  panel  terminations,  power  source  can  not  be 
disconnected since it comes directly from solar panel. Follow proper procedures while 
performing  this  test.  If  no  areas  of  concern  are  found  please  call  OGI  Service 
Department. 

o

 

If proper voltage readings are found on previous check, continue with troubleshooting procedure 
below: 

o

 

Use Voltmeter set to measure DC voltage 

o

 

Place Red lead in terminal block 3 and Black lead in terminal block 2 

o

 

Voltage reading must be between 12 VDC and 14 VDC depending of solar exposure. 

 

Note:  If  voltage  readings  fails  to  meet  minimum  requirements,  check  wiring 
connections from the solar panel into the TotalArc enclosure terminal blocks and from 
the solar converter SK-6 to the panel terminal blocks. 

 

o

 

If there are no areas of concern, please contact OGI Service Department for further trouble 
shooting. 
 

 

VAC System 

 

Use Voltmeter set to measure DC voltage 

 

Place Red lead in terminal block 3 and Black lead in terminal block 2 

 

Voltage reading must be between 11.5 and 13.5 VDC 

 

Use Voltmeter set to AC voltage 

 

Please leads in terminal blocks L and N – reading should be between 120 and 230 VAC 

 

Check Battery Status Lights on battery inside enclosure: 

 

Red Light Solid – Alarm 

 

Yellow Light Solid  - Unit in Battery Mode 

 

Yellow

 

Light

 

Flashing – Battery Charging 

 

Green Light Solid – Unit Power On 

 

Green Light Flashing - Overload

Summary of Contents for TotalArc BMS 460246 SOLAR POWER

Page 1: ...ct of Quality integrity and innovation from concept to commissioning That promise along with proper maintenance will ensure that your TotalArc Relighter gives you years of rugged trouble free performa...

Page 2: ...or s manual Figure 1 1 ON OFF POWER SWITCH 2 STATUS INDICATOR LIGHT 3 IGNITION PUSH BUTTON 4 MAIN GAS SHUTOFF SOLENOID 5 TOTALARC ENCLOSURE 6 CUSTOMER POWER ENTRY 7 M12 RECEPTACLE 8 IGNITION MODULE CA...

Page 3: ...II FIGURE 2 IGNITION MODULE Installation in Flame Arrestor For details see Installation instructions on page 7...

Page 4: ...INSTALLATION TotalArc kit includes mounting feet for easy installation For details see Installation instructions on page 6 FIGURE 3B INSTALLATION MOUNTING PATTERN FOR TOTALARC ENCLOSURE SEE FIGURE 3B...

Page 5: ...IV FIGURE 4 Clamshell Installation FIGURE 5 Battery Connection Detail SOLAR OPTION ONLY...

Page 6: ...V FIGURE 6 Ignition Rod Installation Figure 7 BASO Pilot Safety Valve...

Page 7: ...VI Figure 8 Solar Panel Assembly...

Page 8: ...VII Figure 9 Solar Panel Assembly...

Page 9: ...mportant Safety Instructions 2 Symbols 3 4 Electrical 4 Features 5 Assembly 5 7 Operation 8 9 Maintenance 10 Trouble Shooting 11 12 Wiring Diagrams 13 14 Warranty 15 Parts Ordering and Service Back Pa...

Page 10: ...s system is provided with a solar panel and all required installation hardware The solar panel provided is sized to 35 Watts but solar systems can be supplied with a solar panel up to 50 Watts subject...

Page 11: ...ntrol cable periodically and if damaged have it replaced by an authorized service facility Make sure all control cable clam shell guards are properly and securely attached prior to power up stage Use...

Page 12: ...used on this product Please study them and learn their meaning Proper inter pretation of these symbols will allow you to operate the product better and safer SYMBOL NAME DESIGNATION EXPLANATION Safet...

Page 13: ...t 25 C OGI PART 460312 VAC Powered Control Panel Nominal System Voltage 85 264 VAC Rated Current Input 1 35A at 120 VAC 0 65A at 230 VAC OGI PART 460371 VDC Powered Control Panel Nominal System Voltag...

Page 14: ...ring shipping Carefully remove the product and any accessories from the box Make sure that all items listed in the packing list are included Donotdiscardthepackingmaterialuntilyouhavecarefully inspect...

Page 15: ...all clam shell around the connectors See Figure 4 pg IV These shells are required to maintain Class 1 Division 2 rating Failure to apply clam shells could lead to a hazardous work environment Do NOT c...

Page 16: ...tion is set tighten the set screw Ground connection remove one side of the metal clamp holding the ceramic insulator and install provided 12AWG THHN green ground wire with terminal connector and repla...

Page 17: ...matic control pressure to flow to the remainder of the burner specific safeties If the pilot flame is lost and not relit the BASO will trip isolating and shutting down the burner pilot and venting off...

Page 18: ...9 TYPICAL HEATER WITH TOTALARC RELIGHTER P ID ARRANGEMENT...

Page 19: ...und connection at pilot assembly e Visually check the Control Panel and instrumentation for moisture condensation connections etc f In Northern locations where snow accumulation could be a problem cle...

Page 20: ...h burner TCV RELEASED the system has maintained the main gas closed for a period of two minutes and has now been released TotalArc main gas valve released to OPEN BASO Pilot Guard should cool down and...

Page 21: ...s power source can not be disconnected since it comes directly from solar panel Follow proper procedures while performing this test If no areas of concern are found please call OGI Service Department...

Page 22: ...SCHEMATICS 13 SOLAR POWER TOTALARC P N 460246 120VAC POWER TOTALARC P N 460312 12 24VDC POWER TOTALARC P N 460371...

Page 23: ...14 Enclosure Connections for all systems Trouble and Gas Shut Off Relay Connections for all systems TOTALARC TROUBLE RELAY DRY CONTACT SET CLOSED TROUBLE OPEN OKAY...

Page 24: ...nufacturer s warranty and Seller must authorize return of such material prior to its return shipment Buyer shall bear the expense of packing and shipping proposed defective parts and components and th...

Reviews: