12
HOW TO CHECK BATTERY VOLTAGE
WARNING: DANGEROUS VOLTAGES PRESENT DURING THIS TEST, TRAINED
PERSONNEL TO PERFORM THIS TEST. CONFIRM THERE ARE NO FLAMMABLE GASSES
PRESENT WHILE PERFORMING TEST. ARC FLASH HAZARD – APPROPRIATE PPE
REQUIRED WHILE WORKING ON THE FOLLOWING:
Solar System
•
Use Voltmeter set to measure DC voltage
•
Place Red lead in terminal block 1 and Black lead in terminal block 2
•
Voltage reading must be between 11.5 and 13.5 VDC
Note: If Voltage readings fail to meet minimum requirements,
follow trouble shooting steps below
•
Check Solar Panel power source:
o
Confirm Solar panel is clear of any obstruction with the southern sky.
o
Use Voltmeter set to measure DC voltage
o
Place Red lead in terminal block 9 and Black lead in terminal block 2
o
Voltage reading must be between 14 VDC and 17 VDC depending of solar exposure.
Note: If voltage readings fails to meet minimum requirements, check wiring
connections from the solar panel into the TotalArc enclosure. The solar panel has a
junction box in the back side. Open junction box and check terminations. Note that
there will be power at the solar panel terminations, power source can not be
disconnected since it comes directly from solar panel. Follow proper procedures while
performing this test. If no areas of concern are found please call OGI Service
Department.
o
If proper voltage readings are found on previous check, continue with troubleshooting procedure
below:
o
Use Voltmeter set to measure DC voltage
o
Place Red lead in terminal block 3 and Black lead in terminal block 2
o
Voltage reading must be between 12 VDC and 14 VDC depending of solar exposure.
Note: If voltage readings fails to meet minimum requirements, check wiring
connections from the solar panel into the TotalArc enclosure terminal blocks and from
the solar converter SK-6 to the panel terminal blocks.
o
If there are no areas of concern, please contact OGI Service Department for further trouble
shooting.
VAC System
•
Use Voltmeter set to measure DC voltage
•
Place Red lead in terminal block 3 and Black lead in terminal block 2
•
Voltage reading must be between 11.5 and 13.5 VDC
•
Use Voltmeter set to AC voltage
•
Please leads in terminal blocks L and N – reading should be between 120 and 230 VAC
•
Check Battery Status Lights on battery inside enclosure:
•
Red Light Solid – Alarm
•
Yellow Light Solid - Unit in Battery Mode
•
Yellow
Light
Flashing – Battery Charging
•
Green Light Solid – Unit Power On
•
Green Light Flashing - Overload
Summary of Contents for TotalArc BMS 460246 SOLAR POWER
Page 5: ...IV FIGURE 4 Clamshell Installation FIGURE 5 Battery Connection Detail SOLAR OPTION ONLY...
Page 6: ...V FIGURE 6 Ignition Rod Installation Figure 7 BASO Pilot Safety Valve...
Page 7: ...VI Figure 8 Solar Panel Assembly...
Page 8: ...VII Figure 9 Solar Panel Assembly...
Page 18: ...9 TYPICAL HEATER WITH TOTALARC RELIGHTER P ID ARRANGEMENT...