Loading or Upgrading the Firmware Kernel
OEM Technology Solutions
Page 52
6.2.1.4 Setup
→
Target Configuration
The configuration parameters can be changed at any time once the
EMBEDDED
PLC kernel is running but
requires the Target to be reset (or powered cycle).
Select
Setup
→
Target Configuration…
Follow the instructions that appear in the message dialog box
and press
OK
.
The
EMBEDDED
PLC Utility will establish connection with the target to get the configuration parameters. If
connection is established the following window will appear.
Enter the desired configuration and press
OK
.
Configuration parameters:
•
Modbus Slave Number
: This is slave number used to communicate with the ISaGRAF Workbench
and a Modbus Master.
•
IP Address
: IP address of the target (must be static, DHCP is not supported).
•
Netmask
: Netmasks are used to identify which part of the address is the Network ID and which part
is the Host ID. For example: 255.255.255.0.
•
Default Gateway
: IP address of the default gateway.
•
Use Modbus TCP
: If this option is selected, the Modbus RTU over RS232/RS485 box is disabled.
Select this option if Modbus TCP is required.
•
Use RS232
: If this option is selected, the Modbus TCP configuration box is disabled. Select this
option if Modbus RTU over RS232 is required.
•
Use RS485
: If this option is selected, the Modbus TCP configuration box is disabled. Select this
option if Modbus RTU over RS485 is required.
•
Baud Rate
: Select between 600 to 19200 bits per second.
This operation can be repeated at any time but does require resetting (or power cycle) the Target.