Operating manual
DKS - classic DKS - expert
4
1
Information for mounting
1.1
General information
Electrical installation and safety must correspond to local regulations. The control-
ler is to left under continuing tension in order to guarantee functional readiness at
any time. Pre-positioned power switches are, therefore limited to emergency or
main switches which are usually left in the ’on position.
Warning: Make sure all electricity is switched off or fuses removed be-
fore beginning wiring work. The electricity supply must be switched
off before connecting or removing connectors. Never change the wi-
res and connections of the controller.
Connections of sensors, remote controllers, data BUS etc. to the controller must
be installed separately from those to the mains.
It may be advisable to suppress inductive loads (such as contactors, relays, mixer
drive units etc.) in the vicinity of the programmable thermostat by means of RC
circuits over their coils. (Recommended: 0.047 mF/100W, 250 VAC)
Unused sensor and signal inputs and outputs must not be connected.
The respective symbols and temperatures will not be displayed when
checking the sensors. The parameter 7-0 must be set on 3 for an unu-
sed heating circuit.
The data in this chapter refers to the connector numbering at the con-
troller. This connector numbering may deviate with installation in a
switchgear cabinet etc. Please refer to the appropriate documents.