Operating manual
DKS - classic DKS - expert
29
Parameter
Function
Setting range
Factory setting
Basic setting
Date:
Heating circuit
Adaptions
Date:
Heating circuit
Un
ity
classic
expert
1(green) 2 (red) 1(green) 2 (red)
X =active
3-8
Heating limit depending on
calculated flow temperature
setpoint value
-10 ÷60 2
K
X
X
If calculated flow temperature setpoint is no more able to contribute to the heating (room temperature set point + set
value), heating system is turned off.
It is again activated if difference exceeds set value + 2 K.
2 = standard value
-10 = function disabled
3-9
Legionnella protection
0÷9
0
-
X
X
Legionnella protection function becomes enabled for 2 hours when producing DHW for the first time on the selected
day. (Legionnella protection temperature 60 °C)
1...7 = mon ... sun (1 = mon)
8 = everyday
9 = continuously 60 °C
0 = function disabled