Operating manual
DKS - classic DKS - expert
27
4.5
8th level - Solar function
4.5.1
Basic functions solar
If the collector temperature is higher than the buffer tempe increase "on"
(parameter 8-1) the solar pump is switched on. If it is smaller than the buffer tem-
pe increase "out" (parameter 8-2), the solar pump is switched off. The so-
lar charge can be affected by following functions/parameters, definition of the solar
use (parameter 8-3).
4.6
10th-11th level - Boiler management
In level 10, 11 the adjustments for the boilers are made.
4.6.1
Basic functions heat generator management
According to the heat requirement from the heat management the boiler is swit-
ched on/off. An activated protective function has priority.
Parameter
Code
Function
8-1
1
Increase ON
8-2
1
Increase OFF
8-3
1
Solar charge mode
8-8
1
DHW minimal temperature with solar application
Parameter
Code
Function
10-4
1
Heat generator minimal protection temperature TKmin
11-4
1
Cancel operating data
11-5
1
Gen. Power controller (one ore two stages)