OEG 516005260 Installation And Operating Instructions Manual Download Page 6

All storage tanks may only be used in closed systems. All connections are to be made 
pressurised. Connections that are not required must be sealed. In order to minimise  
heat losses, all lines should be insulated. 
 
The storage tank is to be installed in such a way that it can be drained without  
dismantling. 
 
IMPORTANT: If a smooth-pipe heat exchanger is not required, it has to be sealed to  
prevent the ingress of oxygen. Otherwise, due to the formation of condensing water  
in conjunction with oxygen, this might lead to corrosion. 
 
IMPORTANT: The smooth-pipe heat exchangers must not be locked on both ends if filled, 
because an overpressure might otherwise occur.  
 
IMPORTANT: Before commissioning / heating the storage tank via smooth-pipe heat  
exchangers or screw-in immersion heaters, the tank must be completely filled with  
drinking water. Otherwise, damages at the enamel are possible.

6

Connection

3.1

Mixed installations

3.2

According to technical rules, an appropriate electrical separation of the conductive  
connection between the different materials has to be provided for mixed installations.  
With the smooth-pipe heat exchangers flowed through by heating water, an electrical  
separation in the flow and return line has to be made additionally in order to prevent  
a short circuit via the mandatory grounding of the line.

Pressure shocks /  

water hammers

3.3

When installing fast-closing shut-off and water-tapping valves (solenoid valves, ball  
valves, single-lever mixers), it might come to short-term pressure shocks in drinking 
 water installations becoming noticable in the form of disturbing noises and eventually 
leading to wear and break of pipes and storage tanks. When using such components,  
appropriate water hammer dampers are to be provided. We assume no liability for  
damages caused by pressure shocks and water hammers.

Commissioning

3.4

Commissioning the storage tank is performed in the following steps: 
• filling the storage tank 
• opening the tapping points until the water streams out 
• setting the safety valve 
• heating up the storage tank after complete filling  
 
IMPORTANT: All pre-assembled connections (e.g magnesium protective anodes and  
service hatch) have to be checked for tightness before commissioning. After the first  
heating up, all connections must be checked for correct seat or have to be retightened  
if necessary. We assume no liability for damages caused by water. 
 
IMPORTANT: For an optimal insulating effect, there must not be any condensing humidity 
within the insulation. A damp insulation can be dried by lifting the top storage tank cover 
temporarily during active operation. 

Enamelled domestic water storage tanks

GB

Summary of Contents for 516005260

Page 1: ...www oeg net Installation and Operating Instructions Enamelled domestic water storage tanks GB...

Page 2: ...list Warranty Disposal Technical data and connections Hot water storage tanks 150 500 Hot water storage tanks 800 2 600 Solar storage tanks 200 500 Solar storage tanks 800 2 260 Heat pump storage tank...

Page 3: ...age tanks 1 GB Solar storage tank 200 500 litres page 29 800 2 250 litres page 30 Built under domestic water storage tank vertical 80 200 litres page 32 Hot water storage tank 150 500 litres page 27 8...

Page 4: ...ed specialists heating contractor contract installation company The high efficiency insulation of storage tanks of up to 1 500 litres is made of vacuum panels embedded in a PU foam jacket By e g prick...

Page 5: ...tructions The screw in immersion heaters are subject to the warranty conditions of the manufacturer The cold water connection of the storage tank is attached to the drinking water network the hot wate...

Page 6: ...to be made additionally in order to prevent a short circuit via the mandatory grounding of the line Pressure shocks water hammers 3 3 When installing fast closing shut off and water tapping valves sol...

Page 7: ...te sted yearly and replaced every two years Optionally maintenance free impressed current anodes of different makes can be retrofitted It is of utmost importance that all magnesium protective anodes...

Page 8: ...for preserving any warranty claims The cleaning is done through the flange aperture The enamelled internal surface prevents limestone formation as far as possible and allows for a quick cleaning of li...

Page 9: ...7400 517807402 517807340 517807355 R1 x 500 33 R1 x 700 33 M8 x 500 33 M8 x 500 40 Hot water storage tank 150 x 200 x 300 x 400 x x 500 x x 800 x x 1000 x x 1500 x x 2250 x x 2600 x x Solar storage ta...

Page 10: ...every two years incl replacement of the flange seal yearly cleaning with a drinking water hardness of over 20 dH The warranty claims expire in case of a breach against 6 Defects Warranty in the GT C o...

Page 11: ...695 1 370 895 300 500 507 B2 1 770 650 760 1 925 150 A 43 785 19 10 95 1 88 12 3 10 130 127 217 481 747 967 1 283 1 597 1 731 1 411 910 325 Hot water storage tanks Real volume according to EN 12897 F...

Page 12: ...torage tank pmax tmax bar C 10 95 10 95 10 95 10 95 10 95 Smooth pipe heat exchanger surface volume m l 2 8 18 3 3 21 3 4 5 29 7 4 9 32 5 9 39 Smooth pipe heat exchanger pmax tmax bar C 10 130 10 130...

Page 13: ...height including insulation Diameter without insulation Diameter with insulation Tilt height Weight Energy efficiency class according to EU regulation no 812 2013 Heat retaining loss according to EN...

Page 14: ...14 20 2 6 17 2 8 18 6 2 5 16 Smooth pipe heat exchanger pmax tmax bar C 10 130 10 130 10 130 10 130 Cold water connection R 1 A mm 153 153 88 67 Return smooth pipe heat exchanger bottom Rp 1 B mm 258...

Page 15: ...16 4 26 4 5 1 33 6 Smooth pipe heat exchanger pmax tmax bar C 10 130 10 130 10 130 Cold water connection R 1 A mm 132 120 127 Return smooth pipe heat exchanger bottom Rp 1 B mm 222 230 211 Sensor sle...

Page 16: ...Performance factor NL following DIN 4708 1 3 1 9 2 5 5 Storage tank pmax tmax bar C 10 95 10 95 10 95 10 95 Smooth pipe heat exchanger surface volume m l 0 53 3 44 1 6 8 1 3 8 5 1 48 9 7 Smooth pipe h...

Page 17: ...F r Ihre Notizen Notes Pour vos notes Voor uw aantekeningen...

Page 18: ...02196723 Free service number Phone 00 800 63 43 66 24 Fax 00 800 63 43 29 24 GB OEG GmbH Industriestra e 1 D 31840 Hess Oldendorf info oeg net www oeg net...

Reviews: