19.2. TABLE 2
TABLE OF PARAMETERS
In so far as the 2
nd
level of configuration is concerned access to the parameters included in the
table below is allowed. The remaining parameters belong to 3
rd
level of configuration and can be
modified only in liaison with and subject to agreement of the manufacturer.
PARAMETER
DESCRIPTION
INDICATIVE
VALUE OF
PARAMETER
bio 2
3
Heat Up Phase Feeder OFF
Time: 0,5’’second
5
4
Heat Up Phase Feeder ON
Time: 11,5’’ seconds
115
10
Power 1 = Feeder ΟΝ
12
18
Power 5 = Feeder ΟΝ
38
19
Fan Speed in FIRE STOP sequence
97
20
Fan speed in TEST FIRE sequence
98
24
Fan speed at POWER 1
95
28
Fan speed at POWER 5
145
50
Difference of degrees at start up of burner (51-50)
5
51
Desired Water / Air Temperature of boiler water
75
53
Safety limit of boiler water temperature (51+53)*
5
67
Water pump turn ON temperature in (
o
C).
35
68
Water pump turn OFF temperature in (
o
C).
30
70
Heat Up sequence duration (in seconds)
55
92
Defines one of the three pellets fuel quality types
2
IMPORTANT
If the boiler water temperature exceeds the safety limit set (sum of parameters 51 and 53
plus 1
o
C) for more than one (1) minute the burner will automatically switch to FIRE STOP phase.