octagon v2.16
Page 30
16. 2
nd
LEVEL - CONFIGURATION OF THE BURNER
The 2
nd
level of configuration of the burner is ONLY allowable to trained licensed technicians.
Access to this level of configuration is strictly forbidden to end users as there is a serious risk of
deregulation of the burner.
16.1 ACCESS TO PROGRAMMING
Navigate through the MENU button < > to the PROGRAMMING (gear symbol).
The indication OFF will appear on the screen.
When indication OFF appears on the screen and you press ENTER then the indication OFF will start blinking.
Press EDIT b, - to move to indications Hi or Lo.
Hi: enables deactivation of ON/OFF button
Lo: enables deactivation of ENTER button
Above options are used only by the service personnel in case of cleaning the screen and/or keyboard of the
burner etc.
Press once any of the EDIT b, - a number in brackets will appear on the screen
e.g. [ 2 ]
Press the EDIT to go to number [ 7 ] and press ENTER.
A four (4) digit number will appear. Add up the four digits plus one e.g. number [ 2025 ] =
= 9 +1 = 10 and press ENTER.
Press EDIT b, - to insert the sum (in our example above the sum is 10) and press
ENTER. The ON indication will appear on the screen.
Now you have full access to the 2
nd
configuration level including the parameter settings
of burning allowable by the manufacturer.
Press EDIT b, - go to number [ 8 ] and press ENTER. When “Par” indication appears
on the screen press ENTER. The screen will display P 000.
Press the EDIT , - to insert the code of the parameter you wish to change e.g.
number 28 refers to the Fan speed 5 (max. speed).
Press ENTER. The screen will display a blinking number e.g. 155 indicating the fan speed.
Press the EDIT , - to choose the new fan speed e.g. 156 and press ENTER. The new
fan speed 5 will be 156 i.e. higher than the previous setting.
See Table of parameters in Table 2, §19.2