INSTALLATION
| Specification
982001-TERRA-M2-M4-EN04.1 | www.ochsner.com 47
TERRA 18 HPLA
TERRA 22 HPLA
TERRA 27 HPLA
EVAPORATOR (HEAT SOURCE SYSTEM):
Type
Plate heat exchanger
Plate heat exchanger
Plate heat exchanger
Material
Stainless steel 1.4301 Stainless steel 1.4301 Stainless steel 1.4301
Number
[pce]
1
1
1
Max. refrigerant operating pressure
[bar]
12
12
12
Max. heat transfer medium operating pressure
[bar]
6
6
6
Heat transfer medium temperature differential
[K]
3
3
3
Application range
[°C]
-5/+20
-6/+20
-6/+20
Heat transfer medium
Brine
Brine
Brine
Test pressure
[bar]
54
54
54
Heat transfer medium flow rate
[m³/h]
4,15
5,62
6,38
Internal pressure differential
[mbar]
413
688
860
Flow meter, heat source
built-in
built-in
built-in
Circulation pump, heat source (heat source pump)
internal
Stratos Para 25/1-12
Stratos Para 25/1-12
Stratos Para 25/1-12
Residual head l
[mbar]
737
462
240
i
Information
Data on sound pressure levels refer to operation at
full load at a distance of 1 m. Sound pressure and
sound power levels are given +/-3 dB(A).
Summary of Contents for TERRA 11
Page 2: ......
Page 80: ...80 www ochsner com 982001 TERRA M2 M4 EN04 1 INSTALLATION Declaration of conformity ...
Page 81: ...982001 TERRA M2 M4 EN04 1 www ochsner com 81 INSTALLATION Declaration of conformity ...
Page 82: ...82 www ochsner com 982001 TERRA M2 M4 EN04 1 INSTALLATION Declaration of conformity ...
Page 90: ...90 www ochsner com 982001 TERRA M2 M4 EN04 1 ...
Page 91: ...982001 TERRA M2 M4 EN04 1 www ochsner com 91 ...