INSTALLATION | Troubleshooting
40
www.ochsner.com | 982001-TERRA-M2-M4-EN04.1
Code Fault code
history
Display message
Possible cause and solution
115
Er 01: DHW sensor faulty
Replace sensor
116
Er 10: Outside sensor faulty
Replace sensor
117
Er 14: Mixer sensor faulty
Replace sensor
124
Er 20: TWR sensor faulty
Replace sensor
120
Er 22: TPM or TWR shutdown sensor faulty Replace sensor
136
Er 23: TPV sensor faulty
Replace sensor
118
Er 24: Buffer sensor faulty
Replace sensor
114
Er 29: TWV sensor faulty
Replace sensor
11
11
Er 30: Phase monitor
Check power supply
134
Er 32: THG sensor faulty
Replace sensor
138
Er 33: High pressure sensor faulty
Check sensor
137
Er 34: Low pressure sensor faulty
Check sensor
5
5
Er 36: High pressure
Deficient heat distribution, faulty circulation pump, valve closed or air in the
system, check hydraulics
18
18
Er 37: Low pressure
Lack of source energy, lack of refrigerant, expansion valve, check refrigerant
circuit (by OCHSNER Customer Service)
16
16
Er 38: Hot gas
Expansion valve, lack of refrigerant, target temperature too high, check re-
frigerant circuit (by OCHSNER Customer Service)
10
10
Er 39: Compressor motor protection
Motor overload relay, phase fault/overload, source temperature too high,
check compressor in refrigerant circuit (by OCHSNER Customer Service)
8
8
Er 42: Heat sink frost protection
Deficient heat distribution, faulty circulation pump, valve closed or air in the
system, check buffer charging pump or hydraulics (brine antifreeze level)
Er 46: TSG sensor faulty
Replace sensor
9
9
Er 47: Defrost fault
Too little de-icing energy, evaporator/sensor, check refrigerant circuit (by
OCHSNER Customer Service)
129
129
Er 48: TQE sensor/Evaporator 1 is faulty
Replace sensor
130
130
Er 49: TQA sensor/Evaporator 2 is faulty
Replace sensor
12
12
Er 50: Expansion valve
Check function of electronic expansion valve (by OCHSNER)
1
1
Er 56: Heat source flow rate
Lack of source energy, heat source pump/filter, flow rate at heat source too
low
2
2
Er 57: Heat source frost protection
Lack of source energy, source temperature too low, check heat source,
check heat source pump/filter, clean water filter, submersible pump faulty
3
3
Er 58: Heat source motor protection
Check motor protection, check wiring to motor, motor protection relay, phase
fault/overload, thermal cutout
143
143
Er 59: TWV + TWR sensor break
Check sensor
144
144
Er 60: TQA + TQE sensor break
Check sensor
42
42
Er 71: Bus fault, room remote control
Check eBus wiring
30
30
Er 80: Heat generator 1 address
Check addressing
31
31
Er 81: HG 2 address
Check addressing
32
32
Er 82: HG 3 address
Check addressing
33
33
Er 83: HG 4 address
Check addressing
34
34
Er 84: HG 5 address
Check addressing
35
35
Er 85: HG 6 address
Check addressing
36
36
Er 86: HG 7 address
Check addressing
37
37
Er 87: HG 8 address
Check addressing
20
20
Er 91: Heat sink flow rate
Water pressure too low, circulation pump faulty, valve closed/air in system,
check hydraulics
21
21
Er 90: Overheating
Check refrigerant circuit (by OCHSNER Customer Service)
98
98
Er 98: Auxiliary heat generator running as
only heat generator
Check operation mode of heat pump
104
104
Er104: Sum fault, heat pump
OCHSNER Customer Service
108
108
Er108: Outdoor unit, general
Check wiring
109
109
Er109: Compressor overheating
Automatic acknowledgement
100
100
Er200: Condensation temperature too low
Check refrigerant circuit (by OCHSNER Customer Service)
102
102
Er 202: Evaporation temp. too low
Check refrigerant circuit (by OCHSNER Customer Service)
103
103
Er 203: Evaporation temp. too high
Check refrigerant circuit (by OCHSNER Customer Service)
240
240
Er240: OTE cannot recognise a Modbus
PCB
Check by OCHSNER Customer Service
241
241
Er241: Modbus communication error
Power shutdown? Check the wiring of the Modbus cable between indoor and
outdoor units. Otherwise check by OCHSNER Customer Service
242
242
Er242: CAN bus communication fault
Check wiring of CAN bus cable and Modbus cable (possible consequential
fault of Er 241), otherwise check by OCHSNER Customer Service
Summary of Contents for TERRA 11
Page 2: ......
Page 80: ...80 www ochsner com 982001 TERRA M2 M4 EN04 1 INSTALLATION Declaration of conformity ...
Page 81: ...982001 TERRA M2 M4 EN04 1 www ochsner com 81 INSTALLATION Declaration of conformity ...
Page 82: ...82 www ochsner com 982001 TERRA M2 M4 EN04 1 INSTALLATION Declaration of conformity ...
Page 90: ...90 www ochsner com 982001 TERRA M2 M4 EN04 1 ...
Page 91: ...982001 TERRA M2 M4 EN04 1 www ochsner com 91 ...