Check the frost protection, pH value and reserve
alkalinity.
»
Check that the mixing ratio is correct using a refrac-
tometer. These checks must be carried out with a
representative liquid quantity (e.g. 3x 1/4 l).
i
Information
As the heat transfer medium’s protection against
corrosion decreases over time, we recommend
carrying out a liquid analysis every two years.
10.3.3 Filling the brine circuit
»
Fill the brine circuit via the drain and fill valve.
»
Flush the brine circuit.
»
Allow the brine to flow into the brine circuit.
»
Vent the brine circuit.
11_02_200_204_01_020
1
1
Drain and fill valve with hose screw connector (spe
-
cial thread M21x1.5)
i
Information
The drain and fill valve has a special thread
(M21x1.5) for the hose screw connection.
»
Take care of the hose screw connector provid-
ed and keep it close to the heat pump.
11_02_200_202_01_028
1
2
4
3
1
Drain and fill valve
2
Locking ring for closing and opening the drain and fill
valve
3 Hose screw connector (special thread M21x1.5)
4 Cover
Material damage
Operating the heat pump with too little or no heat
transfer medium (brine) will damage the appliance.
10.3.4 Safety valve drain
i
Information
The indoor unit has an internal safety valve for the
heat source system (brine).
»
Observe national and regional regulations re-
garding the design of the drain and prescribed
regular operational tests.
i
Information
The maximum operating pressure of the heat
transfer medium is 3 bar. However, due to closing
pressure differences, the safety valve may begin
to open from a pressure of 2.4 bar.
If the valve is triggered, the liquid exits via a hose on the
rear of the indoor unit.
»
Size the safety valve drain so that the liquid can drain
unobstructed into a brine collection container.
»
Install the hose with a consistent fall to the brine col-
lection container. Avoid kinking the hose.
11_02_200_204_01_009
Material damage
The liquid (brine) drained via the right-hand safety
valve must not end up in the domestic drain!
»
Collect the liquid in a brine collection contain-
er.
Summary of Contents for TERRA 11
Page 2: ......
Page 80: ...80 www ochsner com 982001 TERRA M2 M4 EN04 1 INSTALLATION Declaration of conformity ...
Page 81: ...982001 TERRA M2 M4 EN04 1 www ochsner com 81 INSTALLATION Declaration of conformity ...
Page 82: ...82 www ochsner com 982001 TERRA M2 M4 EN04 1 INSTALLATION Declaration of conformity ...
Page 90: ...90 www ochsner com 982001 TERRA M2 M4 EN04 1 ...
Page 91: ...982001 TERRA M2 M4 EN04 1 www ochsner com 91 ...