background image

 

BA_OLW I OTE3_SW5x_EN_20160815_V2 

5 /  48 

 

3  Description of the appliance  

 

3.1  Heat pump OLWI 

 
The  appliance  is  an  air/water  heat  pump  which  oper-
ates  as  a  heat  pump  for  heating  purposes.  The  appli-
ance  extracts  heat  at  a  low  temperature  from  the  out-
side  air  and  emits  it  at  a  higher  temperature  to  the 
water 

in 

the 

heating 

system.  

The water for heating can be heated to a flow tempera-
ture of up to 60 °C. 
The  appliance  has  an  electrical  emergency/auxiliary 
heater  (DAE)  with  8.8  kW  rating.  In  the  monovalent 
mode,  the  electrical  emergency/auxiliary  heater  is 
activated  as  soon  as  the  temperature  falls  below  the 
bivalent  point,  so  that  the  heating  operation  and  hot 
water  heating  is  guaranteed.  In  the  mono-energetic 
operation,  the  electrical  emergency/auxiliary  heater  is 
activated as an auxiliary heater. 

Further properties 

Suitable for under-floor and radiator heating 

Low-temperature heating systems are preferred. 

Heat  can  be  extracted  down  to  -20°C  outside  air 
temperature 

The  external  cladding  is  of  corrosion-protected, 
galvanised steel plate with additional stove enam-
elling. 

All  components  and  safety  equipment  necessary 
for operation are built in to the appliance. 

Contains non-flammable safety refrigerant 

 

 

If the heat pump is to be installed in the 
proximity of the sea, ensure that a distance 
>2km is maintained between the sea and 
the place of installation! 

 

3.2  Function  

 
The heat from the outside air is extracted by means of 
an  air  heat  exchanger  (evaporator).  The  refrigerant 
vaporises  and  is  then  compressed  by  means  of  the 
compressor. Electrical energy is necessary for this.  
The  refrigerant  is  now  at  a  higher  temperature  level 
and  transfers  the  heat  from  the  air  via  a  further  heat 
exchanger  (condenser)  to  the  heating  system.  The 
refrigerant expands and the process begins again.  
At  air  temperatures  below  ca.  +7  °C,  the  humidity  in 
the air forms icing on the evaporator fins. This icing is 
automatically thawed. The water formed by de-icing is 
collected  in  a  thawing  sump  and  drained  away  by 
means of a hose. 
The fan switches off during the de-icing phase and the 
heat pump circuit is reversed. The heat required for de-
icing is extracted from  
 
 
 

 
the buffer storage tank or heating circuit. At the end of 
the  de-icing  phase  the  heat  pump  switches  automati-
cally back to the heating circuit 
 

3.3  Scope of delivery 

 
The  appliance  cladding  is  delivered  in  a  separate 
package. 
 

 

Basic appliance 

 

Rating label. 

 

Functional module with diverter valve and 
heat generator pump 

 

Front panel 

 

Rear panel 

 

Side panels left/right 

 

Pipe bend heating circuit flow 

 

Pipe bend heating circuit return 

 
Necessary accessories 
 
 

 

Hydraulic connection group, consisting of:  

o

 

Immersion sleeve 

o

 

Special fittings 5/4“ ET – 5/4“ Sleeve 
Nut  

o

 

T-

piece 5/4“-172“-5/4“ IT 

 

Sensor set OTE Thermostat 

 

Cable temperature sensor 

 

Flow rate sensor DN 20 kvs 10 

 

Air hoses 

 

Wall conduit 

 
 

 

 

Summary of Contents for OLWI 9

Page 1: ...BA_OLW I OTE3_SW5x_EN_20160815_V2 1 48 Operating Instructions Installation Instructions OLWI Air Water Heat pump Heating hot water...

Page 2: ...BA_OLW I OTE3_SW5x_EN_20160815_V2 2 48...

Page 3: ...ats 16 8 2 2 Insulation 17 8 3 Mounting the cladding 17 8 4 Installing the air hoses 17 8 4 1 General 17 8 4 2 Installing the air hoses 17 8 4 3 Insulating the wall 17 9 Commissioning 18 9 1 Required...

Page 4: ...ed to the control heat gen erator pumps safety thermostats etc Contact with the terminal strips wires connected to them or non connected wires by persons or by means of elec trically conductive materi...

Page 5: ...ed between the sea and the place of installation 3 2 Function The heat from the outside air is extracted by means of an air heat exchanger evaporator The refrigerant vaporises and is then compressed b...

Page 6: ...on can however lead to undesired increase in the sound level under unfavourable circumstances NOTE You can find information on the sound power level in the Technical Data Data Table section 4 2 Air du...

Page 7: ...liance is accessible from all sides Make sure that the foundation is horizontal level firm and permanent Ensure that the appliance frame fits uniformly on the foundation Uneven ground can influence th...

Page 8: ...Two screws are provided in the bottom of the heat pump frame one for each side panel Unscrew the 6 fixing screws in the frame and keep them for later use Place the appliance on the prepared foundation...

Page 9: ...connection Connect the functional module to the heat pump with the pressure hoses supplied 1 Pressure hose flow 2 Pressure hose return Fig 8 Hydraulic connection functional module Check the plug conne...

Page 10: ...ystems in conjunction with steel pipework can lead to oxygen diffusion corrosion of the steel pipework The products of such corrosion such as rust silting can be deposited on the heat pump condenser a...

Page 11: ...p must be installed Take the constructional fac tors into consideration When using a condensate pump make sure that its rating is at least 6l min Condensate drain 1 Drain with odour trap 2 Drain hose...

Page 12: ...e drain After laying the condensate hose make sure that the condensate is draining freely Proceed as follows Pour water onto the evaporator so that it flows into the de icing sump Ensure the maximum c...

Page 13: ...heat pump All three phase drives compressor pumps fans MUST be connected to a CLOCKWISE field of rotation 7 1 Cable cross sections Position min cross section Connection cable 230V pumps valve motors C...

Page 14: ...als will be transmitted between the control OTE and the Airstation A 5 pole control cable W5 5x 1 0mm is used for this This is already fitted in the functional module and only has to be connected to t...

Page 15: ...Ochsner hot water tanks are fitted with corresponding sleeves for the installation The current electromagnetic compatibility guidelines are to be adhered to during laying The sensors are to be checke...

Page 16: ...tape The tape is in the accessory heat insulated air hose Fig 20 Seal the appliance inside 2 Hang the foil with the pre cut holes on the hooks on the appliance Fig 21 Seal the appliance inside 3 Remo...

Page 17: ...and air outlet sides Do not make more than four 90 bends The bend ing radius must be at least 600 mm based on the hose middle Use a sharp knife to cut the hose The wire spirals can be cut with wire c...

Page 18: ...invoiced separate ly 9 2 Non self resetting safety thermostat At outside temperatures below 15 C the non self resetting safety thermostat can trigger the electric emergency auxiliary heater Check whet...

Page 19: ...y devices for the compressor High pressure pressostat Start delay to avoid compressor chopping Frost protection function Start up and run down times of the fans 10 2 Running costs During the first hea...

Page 20: ...ied system service intervals as well as the system checks must be adhered to If during larger reconstruction work or after burst pip ing the majority of the water in the heating system has to be drain...

Page 21: ...t may only be de commissioned by an authorised specialist firm cool ing air conditioning heating The refrigerant resp brine fluid is to be evacuated removed correctly by the specialist firm and and re...

Page 22: ...lked up Contact heating installer clean and decalcify heat exchanger Hot water temperature not reached or no longer reached Hot water heat exchanger too small Increase heat exchanger size Heat exchang...

Page 23: ...ce sensor 116 Er 10 Outside sensor defect Replace sensor 117 Er 14 Mixer sensor defect Replace sensor 124 Er 20 TWR sensor defect Replace sensor 120 Er 22 Switch off sensors TWR TPM de fect Replace se...

Page 24: ...c11 Safety group e22 Hot water Flow External thread G 1 1 4 A e23 Hot water Return External thread G 1 1 4 A E01 Heating flow External thread G 1 1 4 A e02 Heating return External thread G 1 1 4 A g0...

Page 25: ...BA_OLW I OTE3_SW5x_EN_20160815_V2 25 48 14 2 Hydraulic diagram...

Page 26: ...BA_OLW I OTE3_SW5x_EN_20160815_V2 26 48 14 3 Electric circuit diagrams OTE...

Page 27: ...BA_OLW I OTE3_SW5x_EN_20160815_V2 27 48...

Page 28: ...BA_OLW I OTE3_SW5x_EN_20160815_V2 28 48...

Page 29: ...BA_OLW I OTE3_SW5x_EN_20160815_V2 29 48 14 4 Wiring overview...

Page 30: ...or R3 Start up resistance F5 Non self resetting thermostat DAE X1 Terminal strips K1 Start up resistance relay X3 Power supply terminal strip K2 Compressor start up relay X4 Control terminal strip K5...

Page 31: ...sor suction air PT1000 X33 5 pole plug expansion valve B7 Temperature sensor compressor inlet PT1000 X34 7 pole plug sensors B8 Temperature sensor evaporator outlet PT1000 X35 6 pole plug temperature...

Page 32: ...9 5 1 3 7 11 15 19 Air tempearture C Power draw kW 6 7 8 9 10 11 12 13 14 15 16 17 21 19 17 15 13 11 9 7 5 3 1 1 3 5 7 9 11 13 15 17 19 21 Heating power kW 35 C 45 C 55 C 60 C Leistungskurven OLWA OL...

Page 33: ...3 5 7 9 11 13 15 17 19 21 Heating power kW 35 C 45 C 55 C 60 C Leistungskurven OLWA OLWI 18 Air temperature C 0 1 2 3 4 5 6 21 17 13 9 5 1 3 7 11 15 19 Air temperature C COP 14 8 Performance diagram O...

Page 34: ...Capacity kW 8 9 12 9 16 6 8 9 12 9 16 6 Total Power Consumption kW 2 2 9 5 1 2 2 9 5 1 Coefficient of Perfomance EN 14511 EN 255 4 4 4 4 4 0 4 4 4 4 4 0 Drawn Current A 3 5 6 4 9 9 3 5 6 4 9 9 Heatin...

Page 35: ...al available external pressure differential hPa 1 0 1 0 1 0 1 0 1 0 1 0 Max available external pressure differential on suction side hPa 0 8 0 8 0 8 0 8 0 8 0 8 Construction Type Fin package material...

Page 36: ...um portion 2 2 0 3 5 0 4 1 0 5 6 0 6 0 5 7 5 0 8 0 5 9 1 5 10 0 5 11 3 5 12 0 5 13 3 0 14 0 5 15 0 5 16 0 5 17 2 0 18 0 5 19 1 5 20 0 5 21 0 5 22 0 5 23 1 5 25 1 5 25 0 5 Table 5 Voltage quality in th...

Page 37: ...BA_OLW A I OTE3_SW5x_DE_20160510_V2 37 48 15 Declaration of Conformity...

Page 38: ...BA_OLW I OTE3_SW5x_EN_20160815_V2 38 48...

Page 39: ...BA_OLW A I OTE3_SW5x_DE_20160510_V2 39 48 16 ERP Data...

Page 40: ...BA_OLW I OTE3_SW5x_EN_20160815_V2 40 48...

Page 41: ...umps CO d 1 5 T 15 C if TO 20 C T 15 C if TO 20 C Bivalent temperature Tbiv 5 C or air to water heat pumps TO 10 C Operation limit temperature ower input compressor off 0 Heating water operating limit...

Page 42: ...n as otherwise any war ranty claims and or claims for damages and or claims for avoidance on account of an error shall be excluded Deviations of the ordered products from the deliv ered products such...

Page 43: ...ernal control interference with the control soiling during construction phase insuffi cient water quality lack of hydraulic separation non specified valves viii if dimensioning is incorrect or if the...

Page 44: ...Fig 32 Switch on heat generator pump 2 The measured flow rate is displayed this must correspond to the nominal flow Fig 33 Reading flow rate Setting p c Set the flow rate by turning the red adjustmen...

Page 45: ...RS 25 7 5 922523 2 12 35 33 110 1 12 OLWA 18 Yonos Para RS 25 7 5 922523 2 64 44 00 200 2 04 OLWI 9 Stratos Para 25 1 8 internal 1 55 25 83 70 0 71 OLWI 13 Stratos Para 25 1 8 internal 2 12 35 33 110...

Page 46: ...Power supply to the heat pump 13 Fig 17 OLWI distribution box 14 Fig 18 Heating buffer 14 Fig 19 Seal the appliance inside 1 16 Fig 20 Seal the appliance inside 2 16 Fig 21 Seal the appliance inside 3...

Page 47: ...BA_OLW I OTE3_SW5x_EN_20160815_V2 47 48...

Page 48: ...inz kontakt ochsner at www ochsner com Zentrale Werk Ochsner Stra e 1 A 3350 Haag Tel 43 0 5 042458 Fax 43 0 5 04245 349 kontakt ochsner at www ochsner com Partner Hotline 0820 201020 Ochsner W rmepum...

Reviews: