Ochsner OLWI 9 Operating Instructions & Installation Instructions Download Page 13

 

BA_OLW I OTE3_SW5x_EN_20160815_V2 

13 /  48 

 

 

7  Electrical connection 

 

DANGER of electrocution

 

 

 

Install  all  electrical  connections  according 
to national and local Standards 

 

The  regulations  of  the  responsible  energy 
utility and the relevant EN-standards are to 
be strictly adhered to.  

 

Connecting  work  may  only  be  carried 
out  by  a  certified  specialist  according 
to this instruction! 

 

The  heat  pump  connection  must  have 
been  approved  by  the  competent  utility 
before it is carried out. 

 

 
The  stated  voltage  must  be  the  same  as  the  house 
circuit voltage. Observe the rating label! 

 

The circuit breaker for the main power supply circuit is 
to  be  a  4-pole  fuse  that  switches  off 

all  poles

  in  the 

event of a malfunction (for currents, see technical data 
Pt.  14/).  The  supply  cable  must  be  protected  against 
overload and short circuiting. The control cable is also 
to be protected by means of an all pole circuit breaker 
C16A. 

 

The  values  for  the  circuit  breaker  fuses  in  the  Annex 
are  guideline  values  only!  The  correct  sizing  of  the 
safety measures is the sole responsibility of the electri-
cian connecting the heat pump. 

 

OCHNSER  provides  no  guarantee  in  cases of  system 
damage  occurring  due  to  incorrectly  sized  safety  de-
vices!  

 

Fig.16:  Power supply to the heat pump 

 

All 

three-phase 

drives 

(compressor, 

pumps,  fans)  MUST  be  connected  to  a 
CLOCKWISE field of rotation. 

 

 
 
 
 
 

7.1  Cable cross sections 

 

Position  

min.  cross-
section 

Connection cable 230V~: 

(pumps, valve motors)  
Connecting cables are always to 
be sized according to on-site 
conditions 

1.5 mm². 
 

Sensor cables:

  

(outside  sensors,  etc.)  must  al-
ways  be  run  separately  (min.  20 
cm) from 230V/400V cables.  
The maximum cable length must 
not exceed 50 m. 

1.0 mm². 
 

Bus cables  

(e.g.

 

room remote control) bus 

cables must always be laid as 
sheathed cables. The sheathing is 
to be earthed on one end -- > to 
the heat pump on PE. 
OCHSNER recommends the 
following conventional cables: 
Y(ST)Y) 2x2x0.8 

0.8 mm². 
 

Signal cables: 

(5x 1.0mm²,  2x 1.0mm²) 
The signal cables between the 
switching box Airstation and the 
OTE control can be run according 
to the hydraulic plan, without 
sheathing. 

1.0 mm². 

Table 1:

  

Wiring cross sections 

 

Should  the  minimum  clearances  between 
sensor  wiring  and  230V/400V  (100mm) 
not  be  able  to  be  adhered  to,  sheathed 
wiring is to be used. 

 
 
This  is  to  be  especially  considered  for  the  outside 
sensor  wiring.  OCHSNER  accepts  no  warranty  claims 
for  damage  caused  by  insufficient  protection  against 
electro-emission 
 

7.2  Power supply wiring 

 
The  voltage  supplies  400V~  and  230V~  are  to  be  run 
separately  according  to  the  circuit  diagram.  See  also 
Fig. 15 

 

400V~ for the compressor  

 

230V~ control voltage 

 

400V~ DAE 

 

400V~  optional  for  auxiliary  heater  for  Le-
gionella treatment (outside unit). 

 

 

Summary of Contents for OLWI 9

Page 1: ...BA_OLW I OTE3_SW5x_EN_20160815_V2 1 48 Operating Instructions Installation Instructions OLWI Air Water Heat pump Heating hot water...

Page 2: ...BA_OLW I OTE3_SW5x_EN_20160815_V2 2 48...

Page 3: ...ats 16 8 2 2 Insulation 17 8 3 Mounting the cladding 17 8 4 Installing the air hoses 17 8 4 1 General 17 8 4 2 Installing the air hoses 17 8 4 3 Insulating the wall 17 9 Commissioning 18 9 1 Required...

Page 4: ...ed to the control heat gen erator pumps safety thermostats etc Contact with the terminal strips wires connected to them or non connected wires by persons or by means of elec trically conductive materi...

Page 5: ...ed between the sea and the place of installation 3 2 Function The heat from the outside air is extracted by means of an air heat exchanger evaporator The refrigerant vaporises and is then compressed b...

Page 6: ...on can however lead to undesired increase in the sound level under unfavourable circumstances NOTE You can find information on the sound power level in the Technical Data Data Table section 4 2 Air du...

Page 7: ...liance is accessible from all sides Make sure that the foundation is horizontal level firm and permanent Ensure that the appliance frame fits uniformly on the foundation Uneven ground can influence th...

Page 8: ...Two screws are provided in the bottom of the heat pump frame one for each side panel Unscrew the 6 fixing screws in the frame and keep them for later use Place the appliance on the prepared foundation...

Page 9: ...connection Connect the functional module to the heat pump with the pressure hoses supplied 1 Pressure hose flow 2 Pressure hose return Fig 8 Hydraulic connection functional module Check the plug conne...

Page 10: ...ystems in conjunction with steel pipework can lead to oxygen diffusion corrosion of the steel pipework The products of such corrosion such as rust silting can be deposited on the heat pump condenser a...

Page 11: ...p must be installed Take the constructional fac tors into consideration When using a condensate pump make sure that its rating is at least 6l min Condensate drain 1 Drain with odour trap 2 Drain hose...

Page 12: ...e drain After laying the condensate hose make sure that the condensate is draining freely Proceed as follows Pour water onto the evaporator so that it flows into the de icing sump Ensure the maximum c...

Page 13: ...heat pump All three phase drives compressor pumps fans MUST be connected to a CLOCKWISE field of rotation 7 1 Cable cross sections Position min cross section Connection cable 230V pumps valve motors C...

Page 14: ...als will be transmitted between the control OTE and the Airstation A 5 pole control cable W5 5x 1 0mm is used for this This is already fitted in the functional module and only has to be connected to t...

Page 15: ...Ochsner hot water tanks are fitted with corresponding sleeves for the installation The current electromagnetic compatibility guidelines are to be adhered to during laying The sensors are to be checke...

Page 16: ...tape The tape is in the accessory heat insulated air hose Fig 20 Seal the appliance inside 2 Hang the foil with the pre cut holes on the hooks on the appliance Fig 21 Seal the appliance inside 3 Remo...

Page 17: ...and air outlet sides Do not make more than four 90 bends The bend ing radius must be at least 600 mm based on the hose middle Use a sharp knife to cut the hose The wire spirals can be cut with wire c...

Page 18: ...invoiced separate ly 9 2 Non self resetting safety thermostat At outside temperatures below 15 C the non self resetting safety thermostat can trigger the electric emergency auxiliary heater Check whet...

Page 19: ...y devices for the compressor High pressure pressostat Start delay to avoid compressor chopping Frost protection function Start up and run down times of the fans 10 2 Running costs During the first hea...

Page 20: ...ied system service intervals as well as the system checks must be adhered to If during larger reconstruction work or after burst pip ing the majority of the water in the heating system has to be drain...

Page 21: ...t may only be de commissioned by an authorised specialist firm cool ing air conditioning heating The refrigerant resp brine fluid is to be evacuated removed correctly by the specialist firm and and re...

Page 22: ...lked up Contact heating installer clean and decalcify heat exchanger Hot water temperature not reached or no longer reached Hot water heat exchanger too small Increase heat exchanger size Heat exchang...

Page 23: ...ce sensor 116 Er 10 Outside sensor defect Replace sensor 117 Er 14 Mixer sensor defect Replace sensor 124 Er 20 TWR sensor defect Replace sensor 120 Er 22 Switch off sensors TWR TPM de fect Replace se...

Page 24: ...c11 Safety group e22 Hot water Flow External thread G 1 1 4 A e23 Hot water Return External thread G 1 1 4 A E01 Heating flow External thread G 1 1 4 A e02 Heating return External thread G 1 1 4 A g0...

Page 25: ...BA_OLW I OTE3_SW5x_EN_20160815_V2 25 48 14 2 Hydraulic diagram...

Page 26: ...BA_OLW I OTE3_SW5x_EN_20160815_V2 26 48 14 3 Electric circuit diagrams OTE...

Page 27: ...BA_OLW I OTE3_SW5x_EN_20160815_V2 27 48...

Page 28: ...BA_OLW I OTE3_SW5x_EN_20160815_V2 28 48...

Page 29: ...BA_OLW I OTE3_SW5x_EN_20160815_V2 29 48 14 4 Wiring overview...

Page 30: ...or R3 Start up resistance F5 Non self resetting thermostat DAE X1 Terminal strips K1 Start up resistance relay X3 Power supply terminal strip K2 Compressor start up relay X4 Control terminal strip K5...

Page 31: ...sor suction air PT1000 X33 5 pole plug expansion valve B7 Temperature sensor compressor inlet PT1000 X34 7 pole plug sensors B8 Temperature sensor evaporator outlet PT1000 X35 6 pole plug temperature...

Page 32: ...9 5 1 3 7 11 15 19 Air tempearture C Power draw kW 6 7 8 9 10 11 12 13 14 15 16 17 21 19 17 15 13 11 9 7 5 3 1 1 3 5 7 9 11 13 15 17 19 21 Heating power kW 35 C 45 C 55 C 60 C Leistungskurven OLWA OL...

Page 33: ...3 5 7 9 11 13 15 17 19 21 Heating power kW 35 C 45 C 55 C 60 C Leistungskurven OLWA OLWI 18 Air temperature C 0 1 2 3 4 5 6 21 17 13 9 5 1 3 7 11 15 19 Air temperature C COP 14 8 Performance diagram O...

Page 34: ...Capacity kW 8 9 12 9 16 6 8 9 12 9 16 6 Total Power Consumption kW 2 2 9 5 1 2 2 9 5 1 Coefficient of Perfomance EN 14511 EN 255 4 4 4 4 4 0 4 4 4 4 4 0 Drawn Current A 3 5 6 4 9 9 3 5 6 4 9 9 Heatin...

Page 35: ...al available external pressure differential hPa 1 0 1 0 1 0 1 0 1 0 1 0 Max available external pressure differential on suction side hPa 0 8 0 8 0 8 0 8 0 8 0 8 Construction Type Fin package material...

Page 36: ...um portion 2 2 0 3 5 0 4 1 0 5 6 0 6 0 5 7 5 0 8 0 5 9 1 5 10 0 5 11 3 5 12 0 5 13 3 0 14 0 5 15 0 5 16 0 5 17 2 0 18 0 5 19 1 5 20 0 5 21 0 5 22 0 5 23 1 5 25 1 5 25 0 5 Table 5 Voltage quality in th...

Page 37: ...BA_OLW A I OTE3_SW5x_DE_20160510_V2 37 48 15 Declaration of Conformity...

Page 38: ...BA_OLW I OTE3_SW5x_EN_20160815_V2 38 48...

Page 39: ...BA_OLW A I OTE3_SW5x_DE_20160510_V2 39 48 16 ERP Data...

Page 40: ...BA_OLW I OTE3_SW5x_EN_20160815_V2 40 48...

Page 41: ...umps CO d 1 5 T 15 C if TO 20 C T 15 C if TO 20 C Bivalent temperature Tbiv 5 C or air to water heat pumps TO 10 C Operation limit temperature ower input compressor off 0 Heating water operating limit...

Page 42: ...n as otherwise any war ranty claims and or claims for damages and or claims for avoidance on account of an error shall be excluded Deviations of the ordered products from the deliv ered products such...

Page 43: ...ernal control interference with the control soiling during construction phase insuffi cient water quality lack of hydraulic separation non specified valves viii if dimensioning is incorrect or if the...

Page 44: ...Fig 32 Switch on heat generator pump 2 The measured flow rate is displayed this must correspond to the nominal flow Fig 33 Reading flow rate Setting p c Set the flow rate by turning the red adjustmen...

Page 45: ...RS 25 7 5 922523 2 12 35 33 110 1 12 OLWA 18 Yonos Para RS 25 7 5 922523 2 64 44 00 200 2 04 OLWI 9 Stratos Para 25 1 8 internal 1 55 25 83 70 0 71 OLWI 13 Stratos Para 25 1 8 internal 2 12 35 33 110...

Page 46: ...Power supply to the heat pump 13 Fig 17 OLWI distribution box 14 Fig 18 Heating buffer 14 Fig 19 Seal the appliance inside 1 16 Fig 20 Seal the appliance inside 2 16 Fig 21 Seal the appliance inside 3...

Page 47: ...BA_OLW I OTE3_SW5x_EN_20160815_V2 47 48...

Page 48: ...inz kontakt ochsner at www ochsner com Zentrale Werk Ochsner Stra e 1 A 3350 Haag Tel 43 0 5 042458 Fax 43 0 5 04245 349 kontakt ochsner at www ochsner com Partner Hotline 0820 201020 Ochsner W rmepum...

Reviews: